MCCB CHINT NM1LE-250S-4300-200A

MarcaModelo de substituição
SchneiderEZD250E4200ELN (integrated leakage)
SchneiderNSX250N 4P 200A TM200D + Vigi NSX 250
ABBA2C250 TMF200/2000 4P integrated leakage
ABBTmax T2N250 TMD200/2000 4P + RC221
Siemens3VM1250-4ED32-0AA0
MitsubishiNV250-SV 4P 200A
DELIXICDM1LE-250/4300 200A
DELIXICDM3LS-250S/4300A 200A
TENGENTGM1LE-250/4300 200A
Interruptor ChangshuCM1L-250/4300 200A
NADERNDM1L-250/4300 200A
HUYUHUM1LE-250/4300 200A

  • Detalhes do produto

NM1LE-250S-4300-200A is a moulded case residual current circuit breaker (RCCB/MCCB with earth leakage protection) from CHINT (NM1LE Series).

  1. Full Model Explanation

NM1LE: Series code

N: CHNT company code

M: Moulded case circuit breaker

1: Design sequence

LE: With earth leakage / residual current protection

250: Frame rating current 250A (maximum frame current for this series)

S: Breaking capacity class (Tipo padrão, ultimate breaking capacity Icu=30kA)

4300: Poloneses & funções

4: 4 postes (3P+N)

3: Thermal-magnetic trip with overload + proteção contra curto-circuito

00: No accessory trips (no undervoltage, no shunt trip)

200UM: Rated operational current In=200A (continuous permissible current)

  1. Principais parâmetros técnicos (NM1LE-250S/4300 200A)
ItemValor
Rated operational voltage UeAC 400V/415V (3-fase 4 fios)
Rated insulation voltage Ui800V
Rated impulse withstand voltage Uimp8kV
Rated frequency50Hz
Ultimate breaking capacity Icu30o (Type S standard)
Service breaking capacity Ics15o
Característica da viagemThermal-magnetic (distribution type)
Rated residual operating current IΔn50mA / 100mA / 200mA (3 adjustable steps)
Residual operating timeStandard type ≤ 0.1s (time‑delay optional)
Número de pólos4P (Pole N type A: no overcurrent trip, always closed)
MontagemTipo fixo (front connection mainly)
Applicable standardsGB/T 14048.2, CEI 60947-2
  1. Principais Funções
  2. Proteção contra sobrecarga: Thermal trip delays and trips when current exceeds 200A.
  3. Proteção contra curto-circuito: Magnetic trip operates instantly within 30kA short-circuit current.
  4. Residual current (earth leakage) proteção: Detects current imbalance between phase and neutral; trips quickly at set values (50/100/200mA) to prevent electric shock and electrical fires.
  5. Infrequent switching: Can be used as a main switch for circuits and equipment.
  6. Aplicações Típicas

3-phase 4-wire distribution systems, industrial equipment, construção de distribuição de energia, construction temporary power, main circuits in shopping malls and factories, and other occasions requiring earth leakage + sobrecarga + short-circuit triple protection.

Complete Technical Data Sheet

CHINT NM1LE-250S/4300 200A

All parameters are from CHINT official catalog and manual, applicable to NM1LE-250S/4300 200A (4-pole moulded case residual current circuit breaker).

  1. Basic Identification Parameters
ItemKey ValueNotas
Full product nameMoulded case residual current circuit breaker (disjuntor de fuga à terra)Distribution protection type
Brand/SeriesCHINT / NM1LE SeriesUpgraded first generation
Full modelNM1LE-250S/4300 200AStandard front connection, no accessory trips
Frame rating current250UMMax rated current supported by this frame
Rated operational current In200UMLong‑term permissible operating current
Poloneses4 postes (3P+N)Pole N has no overcurrent trip, always closed
Breaking capacity classType S (Padrão)Type H (high breaking) available for same frame
Tipo de viagemViagem termomagnéticaLong‑time delay overload + instantaneous short‑circuit protection
ConformidadeGB/T 14048.2, CEI 60947-2CCC certified
  1. Main Circuit Electrical Parameters
ItemKey ValueNotas
Rated operational voltage UeAC 400V/415VFor 3-phase 4-wire systems
Rated insulation voltage Ui800VMaximum insulation withstand voltage
Rated impulse withstand voltage Uimp8kVSurge & lightning overvoltage capability
Rated frequency50HzFor domestic mains power systems
Rated ultimate short-circuit breaking capacity Icu (AC400V)30oMax safe breaking short-circuit current
Rated service short-circuit breaking capacity Ics (AC400V)15oCan continue normal operation after breaking
Arc distance≤100mmMax arc flash during short-circuit breaking
ConexãoConexão frontal (padrão)Rear connection & plug-in type optional
Main terminal torque12N·mFor M8×16 terminal screws
Recommended copper conductor≥70mm² (solid) / 120mm² (stranded)Copper busbar / cable recommended
  1. Características de proteção
ItemKey ValueNotas
Proteção contra sobrecarga (viagem termal)Non-tripping at 7.2In; trips within 1h at 1.3InReference temp +30°C, inverse time delay
Proteção contra curto-circuito (viagem magnética)Instantaneous setting 12In (2400UM)Distribution type, reliable at 120% setting
Protection functionsSobrecarga, short-circuit, residual current (earth leakage)Can be used for infrequent circuit switching
Inlet/outletTop inlet, bottom outlet (padrão)Reverse connection strictly prohibited
  1. Earth Leakage Protection Parameters
ItemKey ValueNotas
Rated residual operating current IΔn50mA / 100mA / 200mA, 3 adjustable stepsDIP switch on device
Rated residual non-operating current IΔn00.5×IΔnThreshold to avoid nuisance tripping
Residual operating time (padrão)≤0,1s (fast type)Trips within 100ms on earth fault
Earth leakage typeAC typeReliable for sinusoidal AC residual current
Test circuitBuilt-in test circuitWith test button; test at least monthly
Earth fault indicationRed mechanical indicatorPops out after earth leakage trip
  1. Environmental & Parâmetros Mecânicos
ItemKey ValueNotas
Operating ambient temperature-5℃ ~ +40 ℃Derate required beyond this range
Storage temperature-25℃ ~ +70 ℃Non-energized storage
Altitude≤2000mDerate for higher altitude
Grau de poluição3Suitable for industrial distribution
Categoria de instalaçãoIIIFor distribution circuits and main equipment circuits
Ingress protectionIP30 (except terminals)Solid foreign object protection, not waterproof
Resistência mecânica10,000 operaçõesNo-load operating cycles
Resistência elétrica4,000 operaçõesAt rated load
Mounting orientationVertical or horizontal mounting allowedInverted mounting not permitted
  1. Dimensões (4-pólo, unit: milímetros)
DimensionValorNotas
Width W188Total width of 4-pole unit
Height L165Including terminals
Depth H102Body thickness
Horizontal mounting hole spacing140Center-to-center left-right
Vertical mounting hole spacing126Center-to-center up-down
Mounting hole diameter Ød4.5For M4 mounting screws
Minimum clearance≥25mm side, ≥5mm top/bottomFor side-by-side installation

Alternative Models from Other Brands

All below match the core specification:

4 postes (3P+N), 250Um quadro, 200A rated current, Icu ≥30kA at AC400V, thermal-magnetic overload + proteção contra curto-circuito, AC-type earth leakage (50/100/200mA adjustable), no accessory trips, front fixed connection.

  1. Domestic High-Compatible Alternatives

(Dimensões, preço, function highly matched; ideal for direct replacement)

  1. MarcaModelo de substituiçãoPrincipais parâmetros de correspondênciaDescrição
    DELIXICDM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA adjustable, thermal-magnetic1:1 design with NM1LE, high compatibility, no cabinet modification
    DELIXICDM3LS-250S/4300A 200AIcu=35kA, 4P 200A, adjustable leakage, thermal-magneticNew upgraded series, maior desempenho
    TENGENTGM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA adjustableDirectly compatible with NM1LE
    Interruptor ChangshuCM1L-250/4300 200AIcu=35kA, 4P 200A, adjustable leakageIndustrial rade high reliability
    NADERNDM1L-250/4300 200AIcu=35kA, 4P 200A, adjustable leakageStable for construction & industry
    HUYUHUM1LE-250/4300 200AIcu=30kA, 4P 200A, 3-step leakageCost-effective direct replacement

    Joint-venture / International Brands

(Higher performance for premium projects & severe conditions)

MarcaModelo de substituiçãoPrincipais parâmetros de correspondênciaDescrição
SchneiderEZD250E4200ELN (integrated leakage)Icu=36kA, 4P 200A, 30/100/300mA adjustableEconomic universal type
SchneiderNSX250N 4P 200A TM200D + Vigi NSX 250UTI=50kA, 4P 200A, multi‑range leakageHigh‑end industrial grade
ABBA2C250 TMF200/2000 4P integrated leakageIcu=36kA, 4P 200A, adjustable leakageEconomic building distribution
ABBTmax T2N250 TMD200/2000 4P + RC221Icu=36kA, 4P 200A, multi‑range leakageHeavy industrial & foreign projects
Siemens3VM1250-4ED32-0AA0Icu=36kA, 4P 200A, 30/100/300mA adjustableStandard international type
MitsubishiNV250-SV 4P 200AIcu=36kA, 4P 200A, 100/200/500mA adjustableHigh reliability for precision equipment
  1. Key Replacement Notes
  2. Mounting dimension check: Domestic models (CDM1LE, TGM1LE, etc.) are highly compatible with NM1LE for direct replacement. International brands often differ in size and hole spacing.
  3. Minimum breaking capacity: Icu at AC400V must be ≥30kA to ensure safety.
  4. Leakage matching: Prefer 50/100/200mA adjustable; use fast‑acting type ≤0.1s, not time‑delay.
  5. Poloneses & N-pole characteristic: Must be 4P (3P+N), with N-pole without overcurrent trip, always closed.
  6. Conformidade: All replacements must be CCC certified and comply with GB/T 14048.2 / CEI 60947-2.