MCCB CHINT NM1LE-250S-4300-200A

MarcaModelo de substituição
SchneiderEZD250E4200ELN (integrated leakage)
SchneiderNSX250N 4P 200A TM200D + Vigi NSX 250
ABBA2C250 TMF200/2000 4P integrated leakage
ABBTmax T2N250 TMD200/2000 4P + RC221
Siemens3VM1250-4ED32-0AA0
MitsubishiNV250-SV 4P 200A
DELIXICDM1LE-250/4300 200A
DELIXICDM3LS-250S/4300A 200A
TENGENTGM1LE-250/4300 200A
Interruptor ChangshuCM1L-250/4300 200A
NADERNDM1L-250/4300 200A
HUYUHUM1LE-250/4300 200A

  • Detalhes do produto

NM1LE-250S-4300-200A is a moulded case residual current circuit breaker (RCCB/MCCB with earth leakage protection) from CHINT (NM1LE Series).

  1. Full Model Explanation

NM1LE: Código da série

N: CHNT company code

M: Moulded case circuit breaker

1: Design sequence

O: With earth leakage / proteção de corrente residual

250: Frame rating current 250A (maximum frame current for this series)

S: Classe de capacidade de ruptura (Tipo padrão, ultimate breaking capacity Icu=30kA)

4300: Poloneses & funções

4: 4 postes (3P+N)

3: Thermal-magnetic trip with overload + proteção contra curto-circuito

00: No accessory trips (no undervoltage, no shunt trip)

200UM: Rated operational current In=200A (continuous permissible current)

  1. Principais parâmetros técnicos (NM1LE-250S/4300 200A)
ItemValor
Tensão operacional nominal UeAC 400V/415V (3-fase 4 fios)
Tensão nominal de isolamento Ui800V
Tensão nominal suportável de impulso Uimp8kV
Frequência nominal50Hz
Ultimate breaking capacity Icu30o (Type S standard)
Service breaking capacity Ics15o
Característica da viagemTermomagnético (distribution type)
Rated residual operating current IΔn50mA / 100mA / 200mA (3 adjustable steps)
Residual operating timeStandard type ≤ 0.1s (time‑delay optional)
Número de pólos4P (Pole N type A: no overcurrent trip, always closed)
MontagemTipo fixo (front connection mainly)
Applicable standardsGB/T 14048.2, CEI 60947-2
  1. Principais Funções
  2. Proteção contra sobrecarga: Thermal trip delays and trips when current exceeds 200A.
  3. Proteção contra curto-circuito: Magnetic trip operates instantly within 30kA short-circuit current.
  4. Corrente residual (vazamento de terra) proteção: Detects current imbalance between phase and neutral; trips quickly at set values (50/100/200mA) to prevent electric shock and electrical fires.
  5. Infrequent switching: Can be used as a main switch for circuits and equipment.
  6. Aplicações Típicas

3-phase 4-wire distribution systems, equipamentos industriais, construção de distribuição de energia, construction temporary power, main circuits in shopping malls and factories, and other occasions requiring earth leakage + sobrecarga + short-circuit triple protection.

Complete Technical Data Sheet

CHINT NM1LE-250S/4300 200A

All parameters are from CHINT official catalog and manual, applicable to NM1LE-250S/4300 200A (4-pole moulded case residual current circuit breaker).

  1. Basic Identification Parameters
ItemValor-chaveNotas
Full product nameMoulded case residual current circuit breaker (disjuntor de fuga à terra)Distribution protection type
Brand/SeriesCHINT / NM1LE SeriesUpgraded first generation
Full modelNM1LE-250S/4300 200AStandard front connection, no accessory trips
Frame rating current250UMMax rated current supported by this frame
Rated operational current In200UMLong‑term permissible operating current
Poloneses4 postes (3P+N)Pole N has no overcurrent trip, always closed
Classe de capacidade de rupturaTipo S (Padrão)Tipo H (high breaking) available for same frame
Tipo de viagemViagem termomagnéticaLong‑time delay overload + instantaneous short‑circuit protection
ConformidadeGB/T 14048.2, CEI 60947-2CCC certified
  1. Main Circuit Electrical Parameters
ItemValor-chaveNotas
Tensão operacional nominal UeAC 400V/415VFor 3-phase 4-wire systems
Tensão nominal de isolamento Ui800VTensão máxima suportável de isolamento
Tensão nominal suportável de impulso Uimp8kVSurge & lightning overvoltage capability
Frequência nominal50HzFor domestic mains power systems
Rated ultimate short-circuit breaking capacity Icu (AC400V)30oMax safe breaking short-circuit current
Rated service short-circuit breaking capacity Ics (AC400V)15oCan continue normal operation after breaking
Arc distance≤100mmMax arc flash during short-circuit breaking
ConexãoConexão frontal (padrão)Conexão traseira & tipo de plug-in opcional
Main terminal torque12N·mFor M8×16 terminal screws
Recommended copper conductor≥70mm² (solid) / 120mm² (stranded)Copper busbar / cable recommended
  1. Características de proteção
ItemValor-chaveNotas
Proteção contra sobrecarga (viagem termal)Non-tripping at 7.2In; trips within 1h at 1.3InReference temp +30°C, inverse time delay
Proteção contra curto-circuito (viagem magnética)Instantaneous setting 12In (2400UM)Distribution type, reliable at 120% setting
Funções de proteçãoSobrecarga, curto-circuito, corrente residual (vazamento de terra)Can be used for infrequent circuit switching
Inlet/outletTop inlet, bottom outlet (padrão)Reverse connection strictly prohibited
  1. Earth Leakage Protection Parameters
ItemValor-chaveNotas
Rated residual operating current IΔn50mA / 100mA / 200mA, 3 adjustable stepsDIP switch on device
Rated residual non-operating current IΔn00.5×IΔnThreshold to avoid nuisance tripping
Residual operating time (padrão)≤0,1s (fast type)Trips within 100ms on earth fault
Earth leakage typeTipo CAReliable for sinusoidal AC residual current
Test circuitBuilt-in test circuitWith test button; test at least monthly
Earth fault indicationRed mechanical indicatorPops out after earth leakage trip
  1. Ambiental & Parâmetros Mecânicos
ItemValor-chaveNotas
Operating ambient temperature-5℃ ~ +40 ℃Derate required beyond this range
Temperatura de armazenamento-25℃ ~ +70 ℃Non-energized storage
Altitude≤2000mDerate for higher altitude
Grau de poluição3Suitable for industrial distribution
Categoria de instalaçãoIIIFor distribution circuits and main equipment circuits
Proteção de entradaIP30 (except terminals)Solid foreign object protection, não à prova d'água
Resistência mecânica10,000 operaçõesNo-load operating cycles
Resistência elétrica4,000 operaçõesNa carga nominal
Orientação de montagemVertical or horizontal mounting allowedInverted mounting not permitted
  1. Dimensões (4-pólo, unidade: milímetros)
DimensãoValorNotas
Width W188Total width of 4-pole unit
Height L165Including terminals
Depth H102Body thickness
Horizontal mounting hole spacing140Center-to-center left-right
Vertical mounting hole spacing126Center-to-center up-down
Mounting hole diameter Ød4.5For M4 mounting screws
Minimum clearance≥25mm side, ≥5mm top/bottomFor side-by-side installation

Alternative Models from Other Brands

All below match the core specification:

4 postes (3P+N), 250Um quadro, 200Uma corrente nominal, Icu ≥30kA at AC400V, thermal-magnetic overload + proteção contra curto-circuito, AC-type earth leakage (50/100/200mA ajustável), no accessory trips, front fixed connection.

  1. Domestic High-Compatible Alternatives

(Dimensões, preço, function highly matched; ideal for direct replacement)

  1. MarcaModelo de substituiçãoPrincipais parâmetros de correspondênciaDescrição
    DELIXICDM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA ajustável, termomagnético1:1 design with NM1LE, high compatibility, sem modificação de gabinete
    DELIXICDM3LS-250S/4300A 200AUTI=35kA, 4P 200A, adjustable leakage, termomagnéticoNew upgraded series, maior desempenho
    TENGENTGM1LE-250/4300 200AIcu=30kA, 4P 200A, 50/100/200mA ajustávelDirectly compatible with NM1LE
    Interruptor ChangshuCM1L-250/4300 200AUTI=35kA, 4P 200A, adjustable leakageIndustrial rade high reliability
    NADERNDM1L-250/4300 200AUTI=35kA, 4P 200A, adjustable leakageStable for construction & industry
    HUYUHUM1LE-250/4300 200AIcu=30kA, 4P 200A, 3-step leakageCost-effective direct replacement

    Joint-venture / Marcas Internacionais

(Higher performance for premium projects & severe conditions)

MarcaModelo de substituiçãoPrincipais parâmetros de correspondênciaDescrição
SchneiderEZD250E4200ELN (integrated leakage)Icu=36kA, 4P 200A, 30/100/300mA ajustávelEconomic universal type
SchneiderNSX250N 4P 200A TM200D + Vigi NSX 250UTI=50kA, 4P 200A, multi‑range leakageHigh‑end industrial grade
ABBA2C250 TMF200/2000 4P integrated leakageIcu=36kA, 4P 200A, adjustable leakageEconomic building distribution
ABBTmax T2N250 TMD200/2000 4P + RC221Icu=36kA, 4P 200A, multi‑range leakageHeavy industrial & foreign projects
Siemens3VM1250-4ED32-0AA0Icu=36kA, 4P 200A, 30/100/300mA ajustávelStandard international type
MitsubishiNV250-SV 4P 200AIcu=36kA, 4P 200A, 100/200/500mA ajustávelHigh reliability for precision equipment
  1. Notas de substituição de chave
  2. Mounting dimension check: Modelos domésticos (CDM1LE, TGM1LE, etc.) are highly compatible with NM1LE for direct replacement. International brands often differ in size and hole spacing.
  3. Minimum breaking capacity: Icu at AC400V must be ≥30kA to ensure safety.
  4. Leakage matching: Prefer 50/100/200mA adjustable; use fast‑acting type ≤0.1s, not time‑delay.
  5. Poloneses & N-pole characteristic: Must be 4P (3P+N), with N-pole without overcurrent trip, always closed.
  6. Conformidade: All replacements must be CCC certified and comply with GB/T 14048.2 / CEI 60947-2.