The following is a detailed technical analysis and application guide for Disjuntores CC da série NB1-63DC da Chint. It is compiled in combination with official materials and industry standards, covering core performance, selection key points, and typical scenarios:
- Parâmetros técnicos principais
- Especificações básicas
| Item | Parâmetro |
| Tensão nominal | DC 250V, 500V, 1000V (Breaking capacity varies with voltage level) |
| Corrente nominal | 1~63A (1P/2P/4P optional, Tripping curve: Type C 5-10In, Type D 10-14In) |
| Quebrando Capacidade | – DC 250V: 10o (Tipo C) |
| – DC 500V: 8o (Tipo C) | |
| – DC 1000V: 6o (Tipo C) | |
| Arc Extinguishing Method | Air arc extinguishing + magnetic blowout technology (Accelerates arc extinguishing through the magnetic field, suitable for DC highly inductive loads) |
| Características de disparo | Proteção contra sobrecarga: Inverse time-limit characteristic, em conformidade com a IEC 60947-2 padrão. |
| Short-circuit Protection: Instantaneous tripping, Tipo C (5-10Em), Tipo D (10-14Em) |
- Environmental and Mechanical Performance
| Item | Parâmetro |
| Temperatura operacional | -35℃~+70℃ (Wide temperature design, adaptable to harsh environments) |
| Nível de proteção | IP20 (Front protection) |
| Método de instalação | 35mm standard rail installation (Supports DIN EN 50022) |
| Especificação de fiação | Main circuit: 2.5~16mm² single-core/stranded wire (M4 screw) |
- Certificações e Padrões
Certificações Internacionais: CCC, CE, EAC, TÜV, CB, SEMKO.
Standards Compliance: GB/T 14048.2, CEI 60947-2, RoHS environmental protection directive.
- Analysis of Key Features
- DC-specific Design
Arc Extinguishing Optimization: Adopts magnetic blowout arc extinguishing technology, which quickly stretches and cools the arc through the magnetic field to solve the problem of difficult arc extinguishing in DC circuits.
Polarity Protection: No built-in reverse connection protection, and anti-reverse connection function needs to be achieved through an external diode or MOS tube circuit.
- Intelligent Tripping and Protection
Proteção contra sobrecarga: Bimetallic inverse time-limit tripping, the larger the current, the shorter the tripping time (por exemplo: it will act within 2 minutes at 1.5 vezes a corrente nominal).
Short-circuit Protection: The electromagnetic trip unit responds instantaneously. Type C is suitable for conventional loads (such as LED lighting), and Type D is suitable for high-impact loads (como motores).
- Extended Functions
Auxiliary Contacts: Supports external connection of OF (contato auxiliar) and SD (alarm contact) to achieve indication of opening and closing states or remote monitoring.
Accessory Compatibility: Can be equipped with shunt trip units (XF9), undervoltage trip units (MN), etc.. for extended functions.
III. Selection and Application Scenarios
- Selection Guide
- Correspondência de tensão: Select the corresponding model according to the system voltage (por exemplo, choose NB1-63DC/500V for DC 500V).
- Current Calculation:
Continuous Load: Rated current ≥ 1.2 times the load current.
Impact Load: Type D tripping curve, rated current ≥ (Load starting current / 10).
- Quebrando Capacidade: Ensure that the breaking capacity (UTI) of the circuit breaker ≥ the system short-circuit current.
- Aplicações Típicas
| Cenário | Model Recommendation | Configuration Description |
| Photovoltaic String Protection | NB1-63DC/500V C16A | Suitable for 1500V photovoltaic systems (Needs to be derated for use), protects the string from overload and short-circuit |
| Energy Storage System | NB1-63DC/1000V D25A | High short-circuit breaking capacity, protects the battery pack and inverter interface |
| Industrial DC Motor | NB1-63DC/250V D32A | Type D tripping curve, can withstand the starting impact current of the motor |
| Communication Base Station | NB1-63DC/48V C6A | Low voltage and high reliability, protects the power supply of communication equipment |
- Instalação e Manutenção
- Installation Key Points
Especificação de fiação: The main circuit wiring needs to be tightened to a torque of 6N·m to avoid loose connection and heat generation.
Polarity Confirmation: Connect the positive and negative poles strictly according to the markings to avoid damage to the circuit breaker due to reverse connection.
Requisitos Ambientais: Avoid using in environments with high humidity (>90%RH) or corrosive gases.
- Sugestões de manutenção
Inspeção Regular: Clean the contacts every quarter and check the flexibility of the tripping mechanism.
Life Management: Mechanical life ≥ 200,000 vezes, electrical life ≥ 100,000 vezes (DC-21A load).
Fault Troubleshooting: Depois de tropeçar, confirm the cause of the fault, and manually disconnect the power supply before resetting.
- Comparação e soluções alternativas
| Modelo | Faixa de tensão | Quebrando Capacidade | Características |
| NB1-63DC | DC 250~1000V | 6~10kA | Magnetic blowout arc extinguishing, supports wide temperature environment, suitable for highly inductive loads |
| NB1Z-63 | AC/DC 220~400V | 6o (AC) | Suitable for both AC and DC, an economical choice with lower breaking capacity |
| NSX400N(Schneider) | DC 1000V | 50o | High short-circuit breaking capacity, suitable for large-scale energy storage systems, with a higher price |
- Precauções
- Derating for Use: When the ambient temperature exceeds 40℃, select the rated current according to derating 5% para cada aumento de 10℃.
- Short-circuit Withstand: The breaking capacity needs to match the system short-circuit current, otherwise it may lead to damage to the circuit breaker or the risk of fire.
- Modelos Alternativos: If a higher breaking capacity is required, Chint’s NB1-63H (AC) or NB1-DC (DC-specific, breaking capacity 15kA) pode ser selecionado.
For detailed technical manuals or customized solutions, you can visit Chint’s official web siteor contact local technical support.
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

















NH42-63-318x560.png)