(Pedido nº.: 269471)
Tipo de produto: Thermistor (PTC) Motor Protection Relay, Ex Explosion-proof, Dual Sensor Circuit
Eaton Moeller EMT6 series for PTC thermistor temperature monitoring of motor windings.
K = ATEX explosion-proof certification; DB = Dual sensor input circuit
✅ Model Code Explanation
EMT6: Série, PTC thermistor motor protection relay
K: Certificado ATEX, suitable for Ex e explosion-proof motor applications
BD: Two independent PTC sensor input circuits (simultaneously monitor 2 temperature points, por exemplo. estator + bearing, or pre-alarm + viagem)
Código do pedido: 269471
✅ Key Features
- Dual PTC circuit monitoring, two sensor channels evaluated independently to support pre-warning and protection logic
- Sensor wire break and short-circuit detection (unique to K variants: detects not only wire breakage but also short circuits of sensor cables)
- Zero-voltage safety protection (undervoltage lockout): the relay will not auto-reset after tripping due to power loss; configurable via DIP switch
- Resettable modes: local manual reset / reinicialização remota
- Front panel Test/Reset button for commissioning to simulate over-temperature faults
- LEDs de status: power indication, indicação de falha
- SIL 1 nível de segurança (SEU 50495), suitable for temperature protection of explosion-proof equipment
✅ Electrical Specifications
Tensão de alimentação: 24~240V AC/DC wide range
Contato auxiliar: 1NÃO + 1NC (contato de mudança), rated thermal current 6A
Tipo de sensor: PTC thermistor (130℃ / 150℃ PTC embedded in motor windings)
Limites: Over-temperature trip >1330Oh; reiniciar <550Oh; sensor short-circuit fault <50Oh
Montagem: Montagem de encaixe em trilho DIN, largura 22,5 mm
Terminais: Terminais de parafuso, tightening torque 1.2Nm
Enclosure protection: IP20 (apenas para instalação em gabinete)
Temperatura ambiente: Operando -25℃ ~ +60℃ (máx.. +45℃ for tightly sealed cabinets)
Padrões: IEC/EN 60947-8, ATEX, CE, UL, Certificação CCC
✅ Applications
Winding temperature protection for Ex-e increased safety explosion-proof motors (primary use case for K models)
Temperature protection for motors, gearboxes, pumps and fans via PTC thermistors
Dual-point temperature monitoring: por exemplo. one channel for winding over-temperature trip, one channel for bearing pre-alarm
Thermal protection for equipment in chemical, farmacêutico, coal and other explosion hazardous areas
✅ Comparison of Related Series Models
| Modelo | Número do pedido. | Não. of Circuits |
| EMT6-K | 269470 | Solteiro |
| EMT6-KDB | 269471 | Dual |
| EMT6-DB | 66167 | Dual |
| EMT6-DBK | 66168 | Dual |
✅ Troubleshooting Guide
- No LED on power-up: Check supply voltage 24~240V AC/DC
- Fault LED steady ON:
PTC over-temperature (resistência >1330Oh)
Sensor circuit wire break
Sensor cable short-circuit (KDB exclusive detection function)
- Cannot reset after trip: Zero-voltage lockout is activated; power cycle or disable undervoltage lockout via DIP switch
- Função de teste: Press front Test button to simulate over-temperature and trigger relay trip
✅ Alternative Selection Reference
Same brand alternative: EMT6-DBK (without ATEX explosion-proof certificate, other functions similar)
Alternativa doméstica: Domestic dual-channel PTC motor protection relay (observação: for explosion-proof applications, domestic alternative must provide valid ATEX certificate for direct replacement of EMT6-KDB)
EATON EMT6-KDB Ambient Temperature Specifications
- Open ventilated cabinet operating ambient temperature: -25℃ ~ +60 ℃
- Sealed cabinet installation (má dissipação de calor): -25℃ ~ +45℃ (reduced upper limit)
- Temperatura de armazenamento: -45℃ ~ +85℃
Notas Suplementares:
Under UL/CSA certified operating conditions, the nominal rated ambient temperature on nameplate is 40℃
For ATEX explosion-proof applications, ATEX code ambient limits must be followed, not solely the 60℃ upper limit
EATON EMT6 Full Series Model List (PTC Thermistor Motor Protection Relay)
Abbreviation Definition
K: ATEX explosion-proof certified, supports sensor cable short-circuit detection
BD: Dual PTC sensor circuit
EMT62: Dual normally open contact version
(230V): Fixed 230V AC supply; no suffix = wide voltage 24~240V AC/DC
| Modelo | Número do pedido. | Sensor Circuits | Fonte de energia | Descrição |
| EMT6 | 66166 | Solteiro | 24~240V CA/CC | Modelo básico, sem detecção de curto-circuito, non-explosion-proof |
| EMT6(230V) | 66400 | Solteiro | 230V e | Single circuit, fixed 230V power supply |
| EMT6-DB | 66167 | Dual | 24~240V CA/CC | Dual circuit, sem detecção de curto-circuito, non-explosion-proof |
| EMT6-DB(230V) | 66401 | Dual | 230V e | Dual circuit, fixed 230V power supply |
| EMT6-DBK | 66168 | Dual | 24~240V CA/CC | Dual circuit with sensor short-circuit detection, sem ATEX |
| EMT6-K | 269470 | Solteiro | 24~240V CA/CC | Single circuit, Certificado ATEX, com detecção de curto-circuito |
| EMT6-KDB | 269471 | Dual | 24~240V CA/CC | Dual circuit + ATEX + detecção de curto-circuito (modelo de destino) |
| EMT62 | 171889 | Solteiro | 24~240V CA/CC | Single circuit, dual NO output contacts |
| EMT62-DB | 171890 | Dual | 24~240V CA/CC | Dual circuit, dual NO output contacts |
Guia de seleção rápida
- Área perigosa de explosão (Ex-e motor) → EMT6-K / EMT6-KDB
- Indústria geral, require sensor cable short-circuit detection → EMT6-DBK
- Indústria geral, dual temperature monitoring, short-circuit detection not required → EMT6-DB
- Two independent normally open alarm outputs required → EMT62 / EMT62-DB
EATON EMT6-KDB (Order No.269471) Dimensões Físicas
montado em trilho DIN; housing dimensions identical across all EMT6 variants
Largura(C): 22.5 milímetros (nominal 23mm, standard 22.5mm DIN rail module width)
Altura(H): 83 milímetros
Profundidade(D): 103 milímetros (measured from DIN rail mounting surface to front face)
✅ Weight: 0.13 kg approx.
Observações:
- For cabinet layout calculation, usar 22.5 mm largura (1 módulo)
- Additional wiring clearance is required for terminal cabling
- EMT6, EMT6-K, EMT6-DB, EMT6-DBK, EMT6-KDB share identical housing dimensions