GV3P80 is a 3‑pole thermal‑magnetic disjuntor do motor from Schneider Electric TeSys GV3 series. It has an adjustment current range of 70–80A, suitable for 45kW (400V) / 55kW (690V) three‑phase motors. It integrates triple protection (sobrecarga, short‑circuit, falha de fase) and isolation function, serving as a core protection component in industrial motor circuits.
- Model Explanation
GV3: TeSys GV3 motor circuit breaker series (frame size 3)
P: Thermal‑magnetic release (triple protection: sobrecarga + short‑circuit + falha de fase)
80: Rated current 80A, adjustable range 70–80A (continuously adjustable)
- Key Specifications (Full Data)
| Item | Especificação |
| Poloneses | 3P (three‑phase) |
| Adjustment current range | 70–80A (continuously adjustable) |
| Tipo de viagem | Thermal‑magnetic |
| Short‑circuit trip multiplier | 14×In (1120UM) |
| Breaking capacity Icu | 65kA @ 230V; 50kA @ 400V; 6kA @ 690V |
| Rated operational voltage Ue | 690Vca 50/60 Hz |
| Insulation voltage Ui | 690V e |
| Impulse withstand voltage Uimp | 6kV |
| Suitable motor power | 45kW @ 400V; 55kW @ 690V; 22kW @ 230V |
| Terminais | EverLink screw terminals (25–35mm² cable) |
| Montagem | DIN rail (width 55mm), screw mountable |
| Degree of protection | IP20 (front) |
| Temperatura operacional | -20°C ~ +60°C (derating factor: 0.8 at +60°C) |
| Mechanical endurance | 50,000 operating cycles |
| Electrical endurance | 20,000 cycles (category AC‑3) |
| Isolation function | Complies with IEC 60947‑1, can be used as safety isolator |
| Certifications | CCC, CE, UL, CSA, IEC 60947‑4‑1 |
| Peso | Aprox.. 1.02 kg |
| Dimensões (W×H×D) | 55 × 105 × 78 milímetros |
- Funções principais & Vantagens
- Triple Protection
Thermal trip: Overload inverse‑time protection (simulates motor heating characteristics)
Magnetic trip: Short‑circuit instantaneous protection (fixed 14×In)
Proteção contra falha de fase: Automatic trip under three‑phase unbalance (IEC 60947‑4‑1)
- EverLink Terminal Technology
Maintenance‑free, anti‑loosening, oxidation‑resistant, suitable for large‑section cables, reduces wiring failure risks.
- Projeto de Segurança
Knob operation, lockable in OFF position (até 3 padlocks)
Clear current scale for precise adjustment
Complies with IEC isolation standards, usable as motor circuit isolator
- Wide Environmental Adaptability
Operating altitude: ≤3000m (no derating required)
Vibration resistance: 10–150Hz, 0.5mm amplitude
Shock resistance: 5Gn (11EM); 30Gn (1EM)
- Referência de seleção (TeSys GV3 Series)
| Modelo | Adjustment Current | Suitable Power (400V) | Tipo de viagem | Características |
| GV3P65 | 55–65A | 37kW | Thermal‑magnetic | Padrão, EverLink terminals |
| GV3P80 | 70–80A | 45kW | Thermal‑magnetic | This model, max adjustment current |
| GV3L80 | 70–80A | 45kW | Magnetic | Short‑circuit protection only |
| GV3ME80 | 40–80A | 45kW | Thermal‑magnetic | 3‑step adjustment (40–50/63–80), economy version |
| GV3P40 | 30–40A | 22kW | Thermal‑magnetic | For small‑medium motors |
- Applications
Direct starting / star‑delta starting circuits for three‑phase asynchronous motors
Main circuit protection for fans, bombas, compressores, transportadores, machine tools
Industrial automation lines, construction equipment motor control
Motor circuits requiring isolation and safety interlock (por exemplo, emergency stop loops)
Motors with frequent starting/stopping and fluctuating loads
- Replacement Options
- Schneider same series
GV3L80 (short‑circuit only, lower cost)
GV3ME80 (simplified adjustment, same mounting space)
- Competitor alternatives
Siemens: 3RV1041‑4JA10 (70–80A, 3P, thermal‑magnetic)
ABB: MS165‑80 (70–80A, 3P, thermal‑magnetic)
Chinese brands: Chint NM1‑125S, Delixi CDM1‑125 (motor protection curve matching required)
- Upgrade solution
Schneider GV4P08N (quadro 4, higher breaking capacity, for motors above 55kW)
Selection Tips
- Select adjustment range at 1.1–1.25 × motor rated current
- Confirm breaking capacity meets system short‑circuit current requirements
- For isolation function, prefer models with certified isolation
- For limited wiring space, choose EverLink terminal models to reduce faults
Complete Model List of Schneider Electric TeSys GV Series Motor Circuit Breakers
Schneider TeSys GV series motor circuit breakers include six sub‑series: GV1, GV2, GV3, GV4, GV5, GV6, covering an adjustment range from 0.06A to 800A, suitable for 0.03kW to 400kW (400V) three‑phase motors, with thermal‑magnetic, magnetic, and economy thermal‑magnetic protection types.
- GV1 Series (Miniature, discontinued, replaced by GV2ME)
GV1ME01: 0.1–0,16A
GV1ME02: 0.16–0.25A
GV1ME03: 0.25–0.4A
GV1ME04: 0.4–0.63A
GV1ME05: 0.63–1.0A
GV1ME06: 1.0–1.6A
GV1ME07: 1.6–2.5A
GV1ME08: 2.5–4.0A
- GV2 Series (Small, 0.06–16A, 0.03–15kW/400V)
2.1 GV2P (Thermal‑magnetic, full protection, knob)
| Modelo | Adjustment Current | Suitable Power (400V) |
| GV2P01 | 0.1–0,16A | 0.06kW |
| GV2P02 | 0.16–0.25A | 0.12kW |
| GV2P03 | 0.25–0.4A | 0.2kW |
| GV2P04 | 0.4–0.63A | 0.37kW |
| GV2P05 | 0.63–1.0A | 0.55kW |
| GV2P06 | 1.0–1.6A | 0.75kW |
| GV2P07 | 1.6–2.5A | 1.5kW |
| GV2P08 | 2.5–4.0A | 2.2kW |
| GV2P10 | 4.0–6.3A | 3kW |
| GV2P14 | 6.3–10A | 4kW |
| GV2P16 | 10–16A | 7.5kW |
2.2 GV2L (Magnetic, short‑circuit only, knob)
| Modelo | Adjustment Current | Suitable Power (400V) |
| GV2L01 | 0.1–0,16A | 0.06kW |
| GV2L02 | 0.16–0.25A | 0.12kW |
| GV2L03 | 0.25–0.4A | 0.2kW |
| GV2L04 | 0.4–0.63A | 0.37kW |
| GV2L05 | 0.63–1.0A | 0.55kW |
| GV2L06 | 1.0–1.6A | 0.75kW |
| GV2L07 | 1.6–2.5A | 1.5kW |
| GV2L08 | 2.5–4.0A | 2.2kW |
| GV2L10 | 4.0–6.3A | 3kW |
| GV2L14 | 6.3–10A | 4kW |
| GV2L16 | 10–16A | 7.5kW |
| GV2L20 | 14–20A | 11kW |
| GV2L22 | 18–25A | 15kW |
2.3 GV2ME (Economy thermal‑magnetic, pushbutton, 3‑step)
| Modelo | Adjustment Current | Suitable Power (400V) |
| GV2ME01 | 0.1–0,16A | 0.06kW |
| GV2ME02 | 0.16–0.25A | 0.12kW |
| GV2ME03 | 0.25–0.4A | 0.2kW |
| GV2ME04 | 0.4–0.63A | 0.37kW |
| GV2ME05 | 0.63–1.0A | 0.55kW |
| GV2ME06 | 1.0–1.6A | 0.75kW |
| GV2ME07 | 1.6–2.5A | 1.5kW |
| GV2ME08 | 2.5–4.0A | 2.2kW |
| GV2ME10 | 4–6.3A | 3kW |
| GV2ME14 | 6.3–10A | 4kW |
| GV2ME16 | 10–16A | 7.5kW |
2.4 GV2LE (Magnetic with electronic trip, special applications)
GV2LE01 ~ GV2LE22: matching current ratings as GV2L, with electronic trip
- GV3 Series (Médio, 9–80A, 5.5–45kW/400V, 55mm width)
3.1 GV3P (Thermal‑magnetic, full protection, EverLink)
| Modelo | Adjustment Current | Suitable Power (400V) |
| GV3P13 | 9–13A | 5.5kW |
| GV3P18 | 13–18A | 11kW |
| GV3P25 | 18–25A | 15kW |
| GV3P32 | 23–32A | 18.5kW |
| GV3P40 | 30–40A | 22kW |
| GV3P50 | 40–50A | 30kW |
| GV3P65 | 55–65A | 37kW |
| GV3P73 | 65–73A | 45kW |
| GV3P80 | 70–80A | 45kW |
3.2 GV3L (Magnetic, short‑circuit only)
GV3L25: 18–25A
GV3L32: 23–32A
GV3L40: 30–40A
GV3L50: 40–50A
GV3L65: 55–65A
GV3L80: 70–80A
3.3 GV3ME (Economy thermal‑magnetic, 3‑step)
| Modelo | Adjustment Current | Suitable Power (400V) |
| GV3ME40 | 40–50A | 30kW |
| GV3ME63 | 50-63A | 37kW |
| GV3ME80 | 40–80A (3 steps: 40–50/63–80) | 45kW |
- GV4 Series (Grande, 25–115A, 15–55kW/400V, 81mm width)
4.1 GV4P (Thermal‑magnetic, full protection)
| Modelo | Adjustment Current | Suitable Power (400V) |
| GV4P25 | 25–32A | 18.5kW |
| GV4P40 | 32–40A | 22kW |
| GV4P50 | 40–50A | 30kW |
| GV4P63 | 50-63A | 37kW |
| GV4P80 | 63–80A | 45kW |
| GV4P100 | 80–100A | 55kW |
| GV4P115 | 100–115A | 55kW |
4.2 GV4L / GV4LE (Magnetic type)
GV4L25 ~ GV4L115: matching current ratings as GV4P
GV4LE25 ~ GV4LE115: magnetic with electronic trip
4.3 Special GV4 Models
GV4PB80S: UL489 approved, 63–80A
GV4P02N: 2‑pole thermal‑magnetic, special applications
- GV5 / GV6 Series (Extra‑large, 100–800A, 55–400kW/400V)
GV5P100: 80–100A
GV5P125: 100–125A
GV5P160: 125–160A
GV5P200: 160–200A
GV6P250: 200–250A
GV6P315: 250–315A
GV6P400: 315–400A
GV6P500: 400–500A
GV6P630: 500–630A
GV6P800: 630–800A
- Model Naming Rules
| Letter/Number | Significado |
| GV | TeSys GV series motor circuit breaker |
| 1/2/3/4/5/6 | Frame size (1 = smallest, 6 = largest) |
| P | Thermal‑magnetic trip (sobrecarga + short‑circuit + falha de fase) |
| eu | Magnetic trip (short‑circuit only) |
| ME | Economy thermal‑magnetic trip (3‑step, cost‑optimized) |
| LE | Magnetic trip with electronic functions |
| Number | Current rating (por exemplo, 80 = 70–80A) |
- Guia de seleção rápida
- Select adjustment range at 1.1–1.25 × motor rated current
- For full protection (sobrecarga + short‑circuit + falha de fase): choose P series
- If thermal protection exists (por exemplo, VFD): choose L series (short‑circuit only)
- Cost‑sensitive, simple adjustment: choose ME series (3‑step)
- Small motors (≤15kW): GV2; médio (15–45kW): GV3; grande (≥55kW): GV4–GV6
- Notas
- All models are 3‑pole (3P) for three‑phase asynchronous motors
- Protection characteristics comply with IEC 60947‑4‑1
- Capacidade de ruptura: GV2/GV3 100kA@400V; GV4 65kA@400V
- Montagem: 35mm standard DIN rail
- Degree of protection: IP20 (front operating part)
Contator,disjuntor,inversor solar,medidor elétrico,baterias solares