Mini-MW W2YV Compact Dual-Output Isolator M-SYSTEM (Japão), Montagem em trilho DIN, 4-way galvanic isolation (Entrada / Output1 / Output2 / Fonte de energia). Designed for 4~20mA industrial signal isolation, ground loop interference suppression and 1-input 2-output signal distribution. ✅ Model Decoding W2YV-AAA-M W2YV ①②③ ④ ① A: Input signal = DC 4~20mA (Input resistance: 250Oh) ② A: ...

  • Detalhes do produto

Mini-MW W2YV Compact Dual-Output Isolator

M-SYSTEM (Japão), Montagem em trilho DIN, 4-way galvanic isolation (Entrada / Output1 / Output2 / Fonte de energia). Designed for 4~20mA industrial signal isolation, ground loop interference suppression and 1-input 2-output signal distribution.

✅ Model Decoding W2YV-AAA-M

W2YV ①②③ ④

  1. ① A: Input signal = DC 4~20mA (Input resistance: 250Oh)
  2. ② A: Saída 1 = DC 4~20mA (Max load ≤750Ω)
  3. ③ A: Saída 2 = DC 4~20mA (Max load ≤350Ω)
  4. ④ M: Power supply = AC 85~264V wide-range AC (47~66Hz)

Definição completa: 4~20mA input, two independent isolated 4~20mA outputs, AC85-264V powered signal distribution isolator

📋 Core Technical Specifications

ItemEspecificações
Isolation StructureGalvanic isolation between Input / SAÍDA1 / SAÍDA2 / Fonte de energia
Precisão±0.1% FS
Deriva de temperatura±0.015% /℃
Tempo de resposta≤0.5s (0~90%)
Suportar Tensão2000V e, 1 minuto (between each isolation barrier)
Resistência de Isolamento≥100MΩ @500VCC
Zero / Ajuste de amplitudeFront panel independent trimming; separate ZERO/SPAN adjustment for two outputs
MontagemTrilho DIN, dense side-by-side installation for high-density cabinet layout
Dimensões GeraisW29.5 × H88.5 × D124 mm
TerminaisParafuso M3, torque de aperto 0.8 N·m
Ambiente Operacional-5 ~ +55℃, 30~90% UR (sem condensação)
Consumo de energiaAprox.. 4VA @AC100V; Aprox.. 6VA @AC240V
PesoAprox.. 200g

🎯 Aplicações Típicas

  1. Eliminate ground loop interference between CLP e transmitters
  2. Distribute one 4~20mA measurement signal to PLC + recorder / indicator (1-input 2-output signal splitting)
  3. Provide galvanic isolation between field transmitters and control room systems to protect AI modules
  4. Impedance conversion for parallel acquisition by multiple receiving instruments

⚙️ Selection & Informações de substituição

Same series DC powered variant: W2YV-AAA-R2 (DC11~27V supply)

Alternativas domésticas: Yutong, Chenzhu, Wanxun and other 1-in-2-out 4-20mA isolators (compare isolation rating, accuracy and temperature drift)

Observação: The two current outputs have different maximum load limits. OUT2 max load is only 350Ω. Use OUT1 for high-load applications.

📌 Troubleshooting Guide

  1. Inaccurate output: Recalibrate ZERO/SPAN on front panel; check 250Ω matching resistor on input loop
  2. Nenhum sinal de saída: Verify AC supply 85~264V; check tightness of M3 terminal screws
  3. Desvio de sinal: Check earthing; ensure input side ground is separated from PLC ground. The isolator is used to break common ground.
  4. Excessive voltage drop under load: Connect the load to OUT1 channel (OUT1 has higher load capacity)

W2YV (Mini-MW Dual-Output Signal Conditioner) Complete Model Code + Common Model List

W2YV = W2YV-①②③-④⑤

①: Input signal; ②: OUT1 output; ③: OUT2 output; ④: Fonte de energia; ⑤: Sufixo opcional

Definição de código

① Input Code

UM: DC 4~20mA, input resistance 250Ω

6: DC 1~5V, input impedance ≥1MΩ

② OUT1 (Canal 1, higher load capacity: Max 750Ω)

UM: DC 4~20mA

6: DC 1~5V

③ OUT2 (Canal 2; Max 350Ω for current output; ≥5kΩ for voltage output)

UM: DC 4~20mA

6: DC 1~5V

S: Sem saída (single-output mode)

④ Power Code

M: AC85~264V (Wide AC)

R2: DC11~27V (24Alimentação CC)

⑤ Options (Suffix /Q, multiple options can be combined)

C01: Silicone coating (umidade & dust protection)

C02: Polyurethane coating

C03: Rubber coating

V01: Multi-turn trim potentiometer

S01: Stainless steel terminal screws

✅ Common Available Models of W2YV Series

  1. W2YV-AAA-M: 4~20mA input, dual 4~20mA outputs, AC85~264V (your target model)
  2. W2YV-AAA-R2: 4~20mA input, dual 4~20mA outputs, DC11~27V
  3. W2YV-6AA-M: 1~5V input, dual 4~20mA outputs, Alimentação CA
  4. W2YV-6AA-R2: 1~5V input, dual 4~20mA outputs, Alimentação CC
  5. W2YV-A6A-M: 4~20mA input, OUT1=1~5V, OUT2=4~20mA, Alimentação CA
  6. W2YV-AA6-M: 4~20mA input, OUT1=4~20mA, OUT2=1~5V, Alimentação CA
  7. W2YV-6A6-M: 1~5V input, OUT1=4~20mA, OUT2=1~5V, Alimentação CA
  8. W2YV-A66-R2: 4~20mA input, dual 1~5V voltage outputs, Alimentação CC
  9. W2YV-AAY-M: 4~20mA input, OUT1=4~20mA only, OUT2 no output (single output)
  10. W2YV-666-R2: 1~5V input, dual 1~5V voltage outputs, Alimentação CC

📌 Other W2 Family Models (Same DIN rail housing as W2 series)

W2XF: Arithmetic signal conditioner (addition / subtraction calculation)

W2VABS: Absolute value signal converter

W2RS: RTD resistance temperature detector isolator

W2YV is only for DC mA/V signal 1-in-2-out isolation and distribution. For temperature measurement or arithmetic functions, select other W2 series models above.

⚠️ Important Selection Notes

  1. Saída mista (one current + one voltage): Place current signal on OUT1. OUT1 has higher load capacity (750Ω vs 350Ω of OUT2)
  2. Coated versions C01 are recommended for high-humidity and chemical cabinet environments
  3. Side-by-side dense DIN installation; no heat dissipation gap required, which is the key advantage of this series

W2YV‑AAA‑M (M-SYSTEM) Dimensões Gerais

Largura(C) × Altura(H) × Profundidade(D) = 29.5 milímetros × 88.5 milímetros × 124 milímetros

Inch: 1.16″ × 3.48″ × 4.88″

Supplementary Dimension Information

  1. Montagem em trilho DIN: 35trilho DIN padrão mm. Modules can be closely mounted side by side, no heat dissipation gap required between modules, ideal for high-density cabinet arrangement
  2. Peso: Aprox.. 200g
  3. Método de montagem: DIN rail clip mounting, or base plate screw fixing (2×Φ4.2 mounting holes)
  4. Terminais: Terminais de parafuso M3. The terminal block protrudes forward; above dimensions refer to maximum overall outline of the unit.

W2YV‑AAA‑M Input Signal Description

For model W2YV-AAA-M specifically: Input is fixed as DC 4~20mA (1st character A), input resistance 250Ω

All Optional Input Types of W2YV Series (1st character in model code)

  1. UM: DC 4~20mA (Entrada atual)

Input resistance: 250Oh

This is the input specification of your W2YV-AAA-M

  1. 6: DC 1~5V (Entrada de Tensão)

Input impedance ≥1MΩ, high-impedance voltage acquisition

⚠️ Importante: W2YV series only has these two factory fixed input ranges. It is NOT programmable. It cannot be modified on-site for 0-10V, 0-20mA, thermocouple or RTD signals. If temperature measurement or multi-range programmable function is required, select other W2 series models such as W2XF.

Brief Comparison

CódigoTipo de sinalImpedância de entrada
UMDC 4~20mA250Oh
6DC 1~5V≥1MΩ

Suplemento

The input range of W2YV is locked at factory by model coding. It cannot be changed by hardware jumpers on site. Only A (4~20mA) ou 6 (1~5V) can be selected during ordering.