Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Schneider Air Circuit Breaker NW32H1F2-3200A - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

disjuntor/

Schneider Air Circuit Breaker NW32H1F2-3200A

Full Model Interpretation Model Segment Description Details NW Product Series MasterPact NW series air circuit breakers, for high‑current power distribution systems from 800 to 6300A 32 Frame Size Frame size 32, rated current range 800–3200A, single pole width 115 mm H1 Breaking Capacity Class H1: 65kA@440V AC (H2=100kA, H3=150kA also available) F2 Mounting & Configuration ...

  • Detalhes do produto

Full Model Interpretation

Segmento de modeloDescriçãoDetails
NWSérie de produtosMasterPact NW series disjuntores de ar, for high‑current power distribution systems from 800 to 6300A
32Frame SizeFrame size 32, rated current range 800–3200A, single pole width 115 milímetros
H1Classe de Capacidade de QuebraH1: 65kA@440V AC (H2=100kA, H3=150kA also available)
F2Montagem & ConfigurationF = Fixed mount (D = Draw‑out); 2 = Equipped with Micrologic 2.0 electronic trip unit
3200UMCorrente nominalRated operational current 3200A (a 40℃), fully adjustable via electronic trip
Official SKUPart Number48082 (3P fixed) / 48087 (4P fixed), used for procurement identification
  1. Key Technical Specifications
ItemValorNotas
Tensão nominal (Ui/Ue)1000V/690V AC 50/60HzSuitable for global high‑voltage power distribution systems
Corrente nominal (Em)3200UMContinuous current at 40℃; adjustable range 2560–3200A
Quebrando Capacidade (Icu/Ics)65kA/65kA@440V ACIcs=100%Icu, full breaking capacity
Short‑time Withstand Current (Icw)65kA/1s (extendable to 3s)Complies with IEC 60947‑2
Tensão nominal suportável ao impulso (Uimp)12kVHigh surge immunity
Mechanical / Electrical Endurance10,000 / 5,000 operaçõesAt 415V In, per IEC 60947‑2
Degree of ProtectionIP30 (padrão) / IP55 (with CDP cover)Basic dust protection, upgradeable
Dimensões (W×H×D)345×352×297mm (3P fixed)Design compacto, saves panel space
PesoAprox.. 47.3kg (3P fixed)Optimized structure for installation & manutenção
Pollution Class3Suitable for industrial environments
  1. Core Product Advantages

3.1 Outstanding Protection Performance

Full electronic precision protection: Micrologic 2.0E trip unit provides LI (long-time + instantâneo) proteção; long-time current adjustable 0.8–1.0In

65kA high breaking capacity: Reliably clears severe short-circuit faults

Selective protection: Coordinates perfectly with downstream breakers to avoid wide-area outages

Fault diagnostics: Built-in fault memory records trip cause (sobrecarga / short-circuit / falha de terra)

3.2 Alta confiabilidade & Durability

Double-break arc extinguishing: Combined vacuum + air system for fast arc quenching

Robust mechanical design: Shock and vibration resistant

Strong environmental adaptability: Operating temp -5℃ to +60℃; no derating up to 2000m altitude

Long service life: Reduces replacement and maintenance frequency

3.3 Flexible Installation & Easy Maintenance

Multiple mounting types: Fixo (F) or draw-out (D); draw-out supports hot-swap

Projeto modular: Trip and accessories field-replaceable

Universal accessory system: Reduces spare parts inventory

Smart connectivity: Supports Modbus, EtherNet/IP for remote monitoring

3.4 Segurança & Eco-compliance

Standard isolation function: Complies with IEC 60947-2

Visual indication: Clear contact position and trip cause display

Locking device: Prevents unauthorized operation

Green Premium certified: RoHS compliant, free of hazardous substances

  1. Operating Principle

NW32H1F2-3200A uses electronic tripping + double-break arc extinguishing:

  1. Proteção contra sobrecarga (long time delay): CTs monitor current; electronic trip calculates thermal buildup
  2. Proteção contra curto-circuito (instantâneo): Triggers immediately when current exceeds set threshold (typically 10–12In)
  3. Arc extinction: Double-break contacts separate; arc is split and extinguished rapidly
  4. Memória de falhas: Stores last 10 trip events for analysis
  5. Aplicações Típicas
  6. Industrial plants: Main LV distribution, transformer secondary protection
  7. Commercial complexes: Main incomers for high-rise buildings, malls, hotels
  8. Data centers: UPS input/output protection
  9. Renewable energy: Grid connection for PV and energy storage power stations
  10. Critical infrastructure: Aeroportos, hospitais, metros, railways
  11. Marine & offshore: Main switchboard protection (class-approved version)
  12. Instalação & Operation Guidelines
  13. Environment: Dry, below 40℃; max altitude 2000m
  14. Wiring: Copper/aluminum busbar or ≥185mm² cable; torque 25Nm
  15. Coordination: Selective coordination with downstream MCCBs
  16. Configurações: Adjust Ir (0.8–1.0In) and Isd based on load
  17. Maintenance: Annual full inspection including trip test
  18. Series Models & Alternatives

7.1 NW32H1 Series Full Model List (3200A Frame)

ModeloMontagemTrip UnitPolonesesSKU
NW32H1F2‑3200AFixoMicrologic 2.0E3P48082
NW32H1F2‑3200AFixoMicrologic 2.0E4P48087
NW32H1D2‑3200ADraw‑outMicrologic 2.0E3P48432
NW32H1D2‑3200ADraw‑outMicrologic 2.0E4P48437
NW32H1F5‑3200AFixoMicrologic 5.0P3PCustom

7.2 Replacement & Upgrade Options

DemandRecommended ModelCaracterísticas
Higher breakingNW32H2F2‑3200A100o
Advanced functionsNW32H1F5‑3200AEarth fault + metering
Draw‑out typeNW32H1D2‑3200AHot‑swap maintenance
Domestic alternativeCHINT NA1‑3200X‑3200A/63kACost‑effective
ABB equivalentEmax 2 E2N3200‑3200A/65kAGlobal service

NW32H1F2-3200A is a flagship product of the Schneider MasterPact NW series.

With 65kA high breaking capacity, precision electronic protection, flexible installation and excellent reliability, it is the ideal choice for main incomers and bus-couplers in heavy industrial and large commercial power distribution systems.

Detailed Application Scenarios

Schneider ACB NW32H1F2-3200A

MasterPact NW series high-end air circuit breaker

3200A rated current • 65kA breaking • fixed mount • Micrologic 2.0

Designed as main incomer / bus-coupler for high-current, high-reliability core LV systems, not for final subcircuits.

  1. Main Distribution in Large Industrial Plants

Primary application

  1. LV main incomer at transformer secondary

For 2000–2500kVA transformers, continuous 3200A duty

Withstands heavy short-circuit at transformer outlet

  1. LV main bus-coupler

For dual-bus / dual-transformer systems, backup & auto-switching

  1. Main power for heavy machinery

Steel, cimento, químico, automotive, paper plants

Fans, bombas, compressores, kilns, production lines

Why suitable: High current, high short-time withstand, 24/7 confiabilidade.

  1. Data Center / Computing Center Main Distribution
  2. LV main incomers and UPS front-end breakers
  3. HVAC, chilled water, precision cooling main circuits
  4. Bus-couplers and section breakers for IDC and modular data halls

Why suitable: No nuisance tripping, full selective coordination, long life.

  1. Main Distribution for Large Commercial Complexes & High-rises
  2. Main LV incomers for landmark offices, malls, hotels, convention centers
  3. Zone main incomers for super high-rises
  4. Main power for parking, central AC, fire-smoke extraction systems

Why suitable: High current capacity, strong breaking, safe isolation.

  1. Public Transport & Infraestrutura Crítica
  2. Main LV breakers for airports, high-speed rail, metro, light rail
  3. Main incomers for operating rooms, ICUs, radiology departments
  4. Main distribution for stadiums, theaters, exhibition centers

Why suitable: Highest safety level, fire-system compatible, stable in harsh environments.

  1. Nova Energia & Power Projects
  2. Grid-connection incomers for large PV and energy storage plants
  3. LV side of wind power box transformers, PCS front protection
  4. Microgrid and captive power plant grid connection

Why suitable: 690V rated, high surge immunity, strong short-time withstand.

  1. Mines, Metallurgy, Oil & Gas (Harsh Environments)
  2. Main substations in coal and metal mines
  3. High-harmonic, heavy-impact loads in metallurgy and refining
  4. Power distribution in explosive / high-pollution areas

Why suitable: Pollution class 3, vibration resistant, no derating at altitude.

  1. Marine & Offshore (Class-approved Version)
  2. Main switchboard breakers for large vessels, rigs, offshore wind platforms
  3. Certified by CCS, BV, DNV, LR, etc..

Why suitable: Anti-roll, anti-vibration, salt-spray resistant.

One-Sentence Positioning

NW32H1F2-3200A = High-capacity, high-reliability, high-breaking “system main gate”

Used only for:

Transformer main incomers

Main bus-couplers

Critical main power supplies

Not used for:

Small loads

Final subcircuits

Standard distribution boxes

Anterior:

Deixe uma resposta

Deixe um recado