Schneider GVAE11 Auxiliary Contact Block

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for ...

  • Detalhes do produto

GVAE11 is a 1NO + 1NC instantaneous auxiliary contact block of Schneider TeSys GV series. It is front-mounted and compatible with GV2/GV3 series motor circuit breakers. With a rated current of 2.5A and IP20 protection degree, it is used for status monitoring and signal feedback of motor control circuits, serving as a standard accessory for motor control in industrial automation systems.

Segmento de códigoSignificadoDescrição
GVACategoria de produtoAuxiliary contact block for GV series
EPosição de montagemFront mounting, different from side-mounted models
11Configuração de contato1 Normalmente aberto (NÃO) + 1 Normalmente fechado (NC) instantaneous contacts with mechanical linkage

Definição completa do modelo: GVAE11 = Schneider GV series, montado na frente, 1NO+1NC instantaneous auxiliary contact block

  1. Especificações Técnicas Principais
CategoriaEspecificaçõesObservações
General Characteristics
Tipo de produtoInstantaneous auxiliary contact blockMechanically linked, operates synchronously with main contacts of circuit breaker
Configuração de contato1NÃO + 1NC (Instantâneo)NO/NC status switches in sync with the main circuit of the circuit breaker
Compatible DevicesSchneider TeSys GV2/GV3 series motor circuit breakersCompatible with GV2L, GV2LE, GV2ME, GV2P, GV2RT, GV3L, GV3P and other models
Método de montagemFront snap-on installationTool-free assembly & quick removal with precise positioning
Parâmetros Elétricos
Tensão operacional nominal24–240V AC, 24–60V CCSuitable for standard voltages of control circuits
Corrente Operacional Nominal2.5UM (É)Continuous current carrying capacity
Tensão nominal de isolamento690V eComplies with insulation requirements for industrial control circuits
Resistência Mecânica100,000 ciclos operacionaisHigh reliability for frequent operations
Resistência Elétrica100,000 ciclos operacionais (AC-15 2.5A/240V)Meets long-term service requirements of control circuits
Tipo de terminalTerminais de parafusoCopper wire cross-section: 0.5–1.5mm²; Torque de aperto: 0.8–1.2Nm
Físico & Parâmetros Ambientais
Grau de ProteçãoIP20Impede o acesso dos dedos às peças energizadas
Dimensões (L × A × P)45 × 20 × 15mmEstrutura compacta, no extra installation space required for circuit breakers
Temperatura operacional-25℃ ~ +60 ℃Ampla faixa de temperatura para ambientes industriais
CorGreyMatches the appearance of GV series circuit breakers
CertificaçõesCCC, UL, CSA, EACMulti-standard certifications for global application
Informações sobre pedidos
Manufacturer Part No.VABE11Official Schneider model
Standard Order CodeVABE11Original imported version
Código EAN3.38911E+12International universal commodity code
  1. Lista completa de modelos (GVAE Series Auxiliary Contacts)
ModeloConfiguração de contatoPosição de montagemCompatible DevicesAplicação principal
GVAE11NO or 1NC (Opcional)FrenteGV2/GV3 SeriesSimple status indication, single signal output
VABE111NÃO + 1NCFrenteGV2/GV3 SeriesStandard status monitoring, output open/close signals simultaneously
GVAE202NÃOFrenteGV2/GV3 SeriesControl circuits requiring multiple NO signals
GVAE022NCFrenteGV2/GV3 SeriesControl circuits requiring multiple NC signals
GVAE141NÃO + 1NCLadoGV2/GV3 SeriesSide mounting for space-limited installations
GVAE242NÃOLadoGV2/GV3 SeriesSide mounting for multiple NO signal demands
GVAE042NCLadoGV2/GV3 SeriesSide mounting for multiple NC signal demands
  1. Modelos de substituição & Comparação de concorrentes

4.1 Internal Schneider Replacements

Modelo originalModelo de substituiçãoDiferençasCenários de aplicação
VABE11GVAE14Different mounting position (side mounting)Insufficient front space, side mounting required
VABE11GV2ME + Contatos integradosProjeto integrado, no extra assembly neededNew equipment selection for integrated layout
VABE11GV3P + Contatos integradosUpgraded series with enhanced functionsHigh-standard applications requiring advanced protection

4.2 Cross-brand Competitor Comparison

MarcaModeloConfiguração de contatoCompatible DevicesPrincipais diferenças
SchneiderVABE111NÃO + 1NCGV2/GV3 SeriesPrecise mechanical linkage, Proteção IP20, alta compatibilidade
ABBMS132-011NÃO + 1NCMS132 SeriesSide mounting, corrente nominal 3A, preço semelhante
Siemens3RV2091-1A1NÃO + 1NC3RV20 SeriesMontagem de plug-in, rated current 2A, complete certifications
EatonPKZM0-AUX111NÃO + 1NCPKZM0 SeriesFront mounting, rated current 2.5A, terminais de mola
ChintNXC-A111NÃO + 1NCSérie NXCEconômico, reliable domestic alternative
  1. Ambientes de aplicativos & Casos Típicos

5.1 Aplicativos recomendados

Motor Control Circuit: Feedback circuit breaker ON/OFF status for PLC/DCS system monitoring

Alarm System: Trigger audible and visual alarms via NC contacts when the circuit breaker trips

Interlock Control: Prevent simultaneous startup of multiple motors and realize sequence control

Monitoramento Remoto: Transmit status signals to SCADA system for remote diagnosis

Circuito de Segurança: Form safety protection circuits together with emergency stop buttons

5.2 Aplicativos não recomendados

Main Circuit Usage: Rated current is only 2.5A, not applicable for motor main circuits

High-frequency Switching: Sobre 1000 switching cycles per hour will shorten service life

Severe Electromagnetic Interference Environment: Additional shielding is required to avoid malfunction

Humid/Corrosive Environment: IP20 protection is insufficient; install extra enclosure or select higher protection grade products

5.3 Casos de aplicação típicos

Caso 1: Pump Unit Control in Wastewater Treatment Plant

Equipamento: 15kW submersible pump, GV2P32 circuit breaker + GVAE11 auxiliary contact

Configuração: NO contact of GVAE11 connected to PLC digital input module; NC contact connected to alarm circuit

Resultado: Real-time monitoring of pump operating status, automatic alarm and event recording upon faults

Caso 2: Conveyor System in Automotive Production Line

Equipamento: 12 conveyor lines, each equipped with GV2P32 + VABE11

Configuração: GVAE11 contacts linked with PLC to realize sequential startup and interlock protection for conveyors

Características: Mechanical linkage ensures accurate status feedback and reduces misjudgment of control systems

  1. Solução de problemas & Maintenance Manual

6.1 Falhas Comuns & Soluções

Fenômeno de falhaPossíveis causasSoluções
No change of contact signals1. Improper installation of contact block1. Reinstall the block and ensure the clip is fully engaged
2. Damaged mechanical linkage2. Inspect linkage mechanism and replace damaged unit
3. Burned or oxidized contacts3. Clean or replace the contact block
4. Fiação errada4. Check wiring and confirm correct connection of NO/NC contacts
Soldagem por contato1. Excessive current in control circuit1. Ensure control circuit current ≤ 2.5A
2. Overheating caused by frequent switching2. Reduce switching frequency or select higher-rated contacts
3. Erosão de arco3. Replace with a new contact block
Interferência de sinal1. Control wires not separated from main wires1. Separate control wires from main wires (spacing ≥ 100mm)
2. No shielded cable used2. Use shielded cable with single-end grounding
3. Aterramento deficiente3. Inspect and ensure reliable grounding
Loose installation1. Clip not fully locked1. Reinstall until a click sound is heard
2. Afrouxamento causado por vibração2. Fit shock-absorbing pads or reinforce installation

6.2 Maintenance Procedures

  1. Inspeção Diária (Semanalmente)

Check installation condition and ensure no looseness

Inspect terminals for overheating and looseness

Test contact switching to confirm synchronization with circuit breaker

  1. Manutenção de rotina (Todo 6 Meses)

Power off and remove dust on the contact block

Medir a resistência de contato (shall be ≤ 50mΩ)

Check flexibility of mechanical linkage

  1. Annual Maintenance

Replace frequently used contact blocks

Test insulation performance of control circuits

Retighten all electrical connections

6.3 Quick Diagnosis Tips

No signal? Check installation and linkage first.

Contact welded? Limit current and cut switching times.

Interferência de sinal? Separate wires, apply shielding and good grounding.

Loose fitting? Re-clip firmly and add shockproof measures for vibrating sites.

  1. Seleção & Installation Guidelines

7.1 Regras de seleção

Compatibilidade: Confirm matching with GV2/GV3 series circuit breakers; not applicable for other series

Configuração de contato: Select 1NO+1NC (VABE11), 2NÃO (GVAE20) or 2NC (GVAE02) according to control demands

Posição de montagem: Choose GVAE11 for front mounting, GVAE14 for side mounting

Correspondência atual: Control circuit current shall not exceed 2.5A; select higher-specification products if overloaded

7.2 Notas de instalação

Installation Sequence: Install circuit breaker first, then attach the contact block and fully lock the clip

Padrão de fiação: Use 0.5–1.5mm² copper wires with tightening torque of 0.8–1.2Nm; avoid over-tightening

Clear Marking: Label NO/NC contacts to prevent wiring errors

Linkage Test: Manually operate the circuit breaker after installation to verify synchronous contact action

Medidas de Proteção: Install extra enclosures for dusty or humid environments

  1. Production Status & Soluções de substituição

Current Status of GVAE11: Em produção, no discontinuation plan (as of June 2026)

Atualizar & Opções de substituição:

  1. Atualização Funcional: GV3 series models with built-in contacts (no extra assembly, fewer fault points)
  2. Atualização Inteligente: TeSys T series (with communication function for network-based status transmission)
  3. Alternativa Doméstica: Compatible domestic GVAE11 models (lower cost with equivalent performance)