Schneider PM750MG Multifunction Power Meter

Descontinuado (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement. Model Code Explanation PM750: High-end multifunction power monitor of PM700 series MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging Core Functions ...

  • Detalhes do produto

Descontinuado (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement.

Explicação do código do modelo

PM750: High-end multifunction power monitor of PM700 series

MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging

Funções principais

  1. True RMS full electrical measurement: 3-fase / single-phase voltage, atual, active/reactive/apparent power, fator de potência, freqüência; phase-wise & total active energy kWh, reactive energy kvarh, demanda / peak demand, máximo & minimum value recording.
  2. Power quality: Total Harmonic Distortion (THD), harmonic analysis up to 15th order, sampling rate 32 samples per cycle.
  3. Interface de E/S: 2 entradas digitais (DE), 1 static digital output (FAZER). DO configurable for pulse output (energy pulse), alarm output or remote control. DI for status acquisition or demand synchronization trigger.
  4. Alarm function: 15 groups of user-defined threshold alarms (sobretensão, subtensão, sobrecorrente, power limit violation, etc.), local indication + alarm report via communication.
  5. Comunicação: RS485, Protocolo Modbus RTU, up to 19200bps, compatible with PLC, SCADA and energy management systems.
  6. Mostrar: Backlit LCD, 6-line display, panel cutout mounting.

Principais especificações elétricas

ItemEspecificações
Measuring VoltageLine-to-line: 10~480V AC; Phase-to-neutral:10~277V AC, 45~65Hz
Entrada atualCT secondary 0.005~6A (5A/1A CT both supported)
Fonte de energiaAC:115~415V; CC:125~250V; Power consumption ≤5VA
PrecisãoCurrent ±0.4%; Voltage ±0.3%; Power ±0.5%; Active energy Class 0.5S (IEC62053-22)
DE12~36VDC, nominal 24VDC, 2.5isolamento de kV
FAZERStatic transistor output, supports pulse / alarm mode

Aplicação Típica

LV/MV switchgear, factory power distribution room, construção de distribuição de energia, computer room incoming cabinet. Used for power monitoring, energy consumption statistics, power quality monitoring and status acquisition; commonly used as spare parts for legacy project retrofits.

OEM Replacement Models (Chave)

PM750MG → METSEPM5330 (Modbus RS485); For Ethernet version: METSEPM5340 (Modbus TCP)

PM53 series is upgraded replacement for PM750, full & enhanced function coverage, identical panel cutout size for direct mounting. Modbus register addresses are incompatible, reconfiguração necessária. High-end alternative: PM8240/PM8243.

Common Troubleshooting Checklist

  1. Sem corrente / reversed current reading: CT S1/S2 reversed; CT secondary shorting link not removed; CT ratio not configured in meter.
  2. Modbus communication failure: Missing termination resistor, A/B wire reversal, mismatched address/baud rate; unstable meter supply.
  3. DO no action: Verify DO mode configuration (pulse/alarm) and polarity of external circuit.
  4. Abnormal harmonic reading: Fiação solta, insufficient PT/CT accuracy, heavy distortion on load side.

Notas Suplementares

Dimensão de recorte: 92×92mm, panel flush mounting

Padrões: CEI 62053, ANSI C12.20; compatible with 3P3L /3P4L / sistemas monofásicos

Second-hand spare note: LCD backlight aging, damaged RS485 transceiver chip, parameter loss due to internal battery depletion.

  1. PM750MG Modbus RTU Register Summary (Holding Registers, 4xxxx, 16pedaço; Energy values as 32bit, ocupa 2 registros consecutivos)

Protocol Notes: Modbus RTU, register starts at 40001 (Schneider padrão). Some software uses 0-based addressing (40000), pay attention to offset. For float /32bit unsigned integer, palavra alta primeiro. Energy registers come with multiplier register; readings must be multiplied by multiplier factor.

Firmware version: V3.050 (common firmware for PM700 series)

Modbus Address(4xxxx)Data TypeNomeDescrição
40001UINT16V1 Phase VoltageTensão de fase, multiplier register 40013
40002UINT16V2 Phase Voltage
40003UINT16V3 Phase Voltage
40004UINT16V12 Line Voltage
40005UINT16V23 Line Voltage
40006UINT16V31 Line Voltage
40007UINT16I1 Phase A CurrentAtual, multiplier register 40014
40008UINT16I2 Phase B Current
40009UINT16I3 Phase C Current
40010UINT16Frequency Hz
40011UINT16Total Active Power kWPower multiplier 40015
40012UINT16Total Reactive Power kvar
40013UINT16Voltage Multiplier (10^n)por exemplo. value=2 → ×100
40014UINT16Current Multiplier (10^n)
40015UINT16Power Multiplier (10^n)
40016UINT16Total Power FactorRange 0~1000, divide by 1000
4,002,040,021UINT32Total Active Energy kWh40020=High word,40021=Low word; multiplier 40108
4,002,240,023UINT32Total Reactive Energy kvarh
4,002,440,025UINT32Total Apparent Energy kVAh
40030UINT16Phase A THDCurrent total harmonic distortion
40031UINT16Phase B THD
40032UINT16Phase C THD
40040UINT16DI StatusBit0=DI1,Bit1=DI2
40041UINT16DO StatusBit0=DO1
40045UINT16Alarm Status WordAlarm mask
40108UINT16Energy Multiplier (10^n)Energy reading ×10^n, Importante!

Energy Calculation Example: 40020=0012, 40021=ABCD; 40108=2 → 0x0012ABCD ×10² = 1254860 ×100 = 125486000 Wh = 125486 kWh

Harmonics: 1~15th harmonic magnitudes, registers start at 40050, per-phase harmonic amplitude.

Communication Basic Parameters (PM750MG)

Protocolo: Modbus RTU

Taxa de transmissão: 2400/9600/19200

Paridade: Nenhum / Chance / Até; Stop bit:1

Slave address: 1~247

RS485 Terminals: UM, B; 120Ω termination resistor at bus end

  1. PM750MG vs METSEPM5330 Function & Wiring Migration Comparison Table
ItemPM750MG (Old Meter)METSEPM5330 (Replacement Meter)Notas de migração
Tamanho do recorte92×92mm92×92mmRecorte de painel idêntico, direct mounting
Fonte de energiaAC115~415V / DC125~250VAC100~415V / DC110~250VPower circuit can be reused directly
Entrada de Tensão10~480V line voltage10~480V line voltagePT secondary wiring unchanged; support 3P3L/3P4L
Entrada atualCT secondary 0.005~6ACT secondary 0.005~6ACT S1/S2 wiring unchanged, CT ratio must be reconfigured on new meter
DE2DE (24CCV)2DE (24CCV)External DI wiring can be kept
FAZER1-channel static transistor output2-channel relay DO⚠️Major difference! PM750MG uses transistor DO; PM5330 is dry contact relay. Original DO pulse/alarm circuit needs redesign, higher load capacity.
Medição HarmônicaUp to 15th harmonicUp to 31st harmonicPM5330 enhanced power quality capability
Alarm Groups15 grupos35 gruposAlarm logic can be migrated, register addresses for alarms are fully different
ComunicaçãoModbus RTU RS485Modbus RTU RS485Physical A/B wiring unchanged. Register mapping is fully incompatible! PLC/SCADA program must be rewritten, old register addresses cannot be reused.
Energy TariffSingle tariff4 tarifasSupport time-of-use metering
PrecisãoActive energy Class 0.5SActive energy Class 0.5SSame accuracy class
Registro de dadosMáx. & Min valuesMáx. & Mínimo + Event logPM5330 supports event logging

Retrofit Risk Checklist (Mandatory for Site Replacement)

  1. DO circuit modification: PM750MG transistor output cannot drive heavy load. PM5330 uses relay. If original DO sends pulse to acquisition module, verify dry-contact pulse compatibility with acquisition device.
  2. Host software program reconstruction: Register address, data arrangement and multiplier logic are all different. All tags for PLC / KingView / ForceControl / SCADA must be reconfigured; old program cannot be copied directly.
  3. Parameter re-entry: Relação de TC, Proporção de PT, system type (3P3L/3P4L), limite de alarme, Modbus address and baud rate all require manual setup. Parameters from PM750MG cannot be imported into PM5330.
  4. Real-time clock: PM750MG internal battery loses parameters on power loss; PM5330 retains parameters after power loss, only clock resets.

III. Terminal Wiring Comparison

PM750MG Terminal Layout

  1. L1 L2 L3 N Voltage Input
  2. CT1 CT2 CT3 Current Input
  3. Terminais de energia
  4. DI1 DI2 COM
  5. DO+ DO(Transistor)
  6. RS485 A B

METSEPM5330 Terminal Layout

  1. L1 L2 L3 N Voltage
  2. CT1 CT2 CT3 Current
  3. Poder
  4. DI1 DI2 COM
  5. DO1, DO2 (Relé, independent dry contact)
  6. RS485 A B

Tensão, atual, DI and RS485 cables may remain untouched; DO wiring must be rewired.

  1. On-site Replacement Procedure
  2. Power off and confirm safety; record original PM750MG parameters (CT/PT ratio, system type, alarm settings, parâmetros de comunicação).
  3. Remove old meter, keep voltage, TC, DI and RS485 cables.
  4. Install METSEPM5330, connect voltage, TC, DI and RS485; rework DO wiring separately.
  5. Power up, configure CT/PT ratio, system wiring type, Modbus address, baud rate and alarm thresholds.
  6. Verify real-time measurements: tensão, atual, poder; confirm CT polarity is correct.
  7. Modify PLC / SCADA Modbus program, debug communication.
  8. Compare accumulated energy readings, run continuous test to verify metering accuracy.

Schneider PowerLogic PM700 Series Full Model List (Todos descontinuados)

Series basics: 92×92mm panel mounting, True RMS measurement, THD, min/max logging. Definição de sufixo

MG: With RS485 Modbus RTU communication

CA: North American ANSI version (rarely used in China; Chinese projects prefer models without CA suffix)

P: 2-channel solid-state pulse output

Lista completa de modelos

  1. PM700 Base model, sem comunicação, sem saída de pulso
  2. PM700CA North American base version
  3. PM700MG Base measurement + Modbus RS485
  4. PM700MGCA NA version + Modbus
  5. PM700P Base model + 2 solid-state pulse outputs, sem comunicação
  6. PM700PCA NA version with pulse output
  7. PM700PMG Base + saída de pulso + Modbus RS485
  8. PM700PMGCA NA version, pulso + Modbus
  9. PM710 Base measurement + Modbus RS485, no DI/DO
  10. PM710CA NA PM710
  11. PM710MG Mainstream domestic PM710 (Modbus)
  12. PM710MGCA NA PM710MG
  13. PM750 Top tier, Modbus RS485, 2DI+1DO, função de alarme
  14. PM750MG Most common domestic model (modelo de destino, Modbus version)
  15. PM750CA NA PM750
  16. PM750MGCA NA PM750MG

Comparison of 4 Modelos principais (Common for China Projects)

ModeloConfiguração principalAplicativo
PM700Basic electrical +THD/min-max, No comms, no pulseLocal display only, no SCADA connection
PM700PBasic electrical +THD, 2 pulse outputs, No commsEnergy pulse acquisition, no network
PM710MGBasic electrical +THD, Modbus RS485, No DI/DORemote power acquisition, no status points needed
PM750MGFull electrical +THD+15th harmonic, Modbus RS485, 2DI+1DO+threshold alarmsMonitoramento de energia, remote status acquisition, saída de alarme (largest installed base in China)

Descontinuação & Replacement Summary

APAC discontinuation date: 2015-04-30; Americas:2015-08-30. No new original production, only surplus / second-hand spare parts.

PM700 / PM700P / PM710 → METSEPM51xx (PM5100 series)

PM750 / PM750MG → METSEPM53xx (METSEPM5330 RS485; METSEPM5340 Ethernet TCP)

Observações Suplementares

  1. This series does NOT have PM720/PM730/PM740. Many documents are misleading. PM700 series only has four base platforms: PM700, PM700P, PM710, PM750.
  2. CA suffix = North American ANSI variant, differs in wiring logic & classificação de tensão. Avoid CA-suffix spares for China retrofits.
  3. All models share identical 92×92mm cutout and panel appearance; only internal I/O and communication hardware differ.