Siemens 3TF4322-0XM AC Contactor

Tipo de produto: 3-pole AC contactor, discontinued. Recommended replacement: 3RT6026-1AN20 (domestic 3RT6 series) Parâmetros principais: 22UM / 400V at AC-3 duty, suitable for 11kW motors; coil AC230V 50/60Hz; auxiliary contacts 2NO + 2NC Positioning: Tamanho 1, general-purpose industrial type, used for motor starting/stopping, equipment control and power distribution switching Full Model Interpretation (Including Complete Order Number) ...

  • Detalhes do produto

Tipo de produto: 3-pole AC contactor, discontinued. Recommended replacement: 3RT6026-1AN20 (domestic 3RT6 series)

Parâmetros principais: 22UM / 400V at AC-3 duty, suitable for 11kW motors; coil AC230V 50/60Hz; auxiliary contacts 2NO + 2NC

Posicionamento: Tamanho 1, general-purpose industrial type, used for motor starting/stopping, equipment control and power distribution switching

  1. Full Model Interpretation (Including Complete Order Number)

Complete order number: 3TF4322-0XM0. Segment meanings are as follows:

Segmento de modeloSignificadoDescrição detalhada
3TFSeries CodeSiemens AC contactor series (distinguished from 3TH auxiliary contactors and older 3TB series)
43Tamanho / Classificação atualTamanho 1, rated current 22A at AC-3 400V, suitable for 3-phase motors up to 11kW
22Configuração de contato auxiliar2 Normalmente aberto (NÃO) + 2 Normalmente fechado (NC), standard built-in auxiliary contacts, expandable
0XCoil Type0X = AC coil (1X = DC coil); 0XM indicates AC230V series
M0Tensão da bobinaAC230V 50/60Hz. Full voltage codes: M=230V, F=115V, G=42V, Q=400V
StatusProduct LifecycleDescontinuado. Siemens official recommendation: upgrade to 3RT6 / 3RT5 series
  1. Core Technical Specifications (Authoritative Data)
Categoria de parâmetroEspecificaçãoObservações / Aplicativo
Main Circuit Parameters
Número de poloneses3-pólo3-phase AC circuit, no neutral pole
Tensão operacional nominalAC 690V (isolamento); CA 400V (typical)Standard industrial voltage range
AC-3 Rated Current22UMAt 400V, for 11kW 3-phase induction motors
AC-4 Rated Current11UMFor severe duty such as direct starting and reversing of squirrel-cage motors
Quebrando CapacidadeAC-3 400V: 150o; AC-3 660V: 35oMeets industrial short-circuit breaking requirements
Parâmetros da bobina
Tensão da bobinaAC230V 50/60HzStandard 0XM0 configuration, coil power approx. 12VA
Coil TypeAC electromagnetic coilStable pull-in, strong anti-interference
Mecânico / Vida Elétrica
Vida Mecânica≥ 12,000,000 operaçõesNo-load frequent operation, suitable for high-cycle applications
Vida Elétrica≥ 1,000,000 operações (AC-3)Long-term reliable operation at 22A / 400V
Ambiente & Proteção
Temperatura operacional-25°C ~ +55°CWide temperature range for outdoor, workshop and harsh environments
Ingress ProtectionIP20Finger-safe, suitable for panel mounting
MontagemTH35 standard railQuick installation, compatible with standard distribution boards
Approval Standards
ConformidadeCEI 60947-4-1, GB 14048.4Globally recognized certifications, safe and reliable
  1. Funções principais & Design Advantages
  2. Double-break Arc Extinction System: Main contacts feature double-break structure, strong arc quenching, reliable breaking, extended contact life
  3. Modular Accessory Compatibility: Supports add-on auxiliary contact blocks, shunt trips, undervoltage trips, mechanical interlocks, etc..
  4. Screw Terminals: Reliable screw connection for main circuit, suitable for high-current wiring; auxiliary terminals available in spring or screw type
  5. Wide-range Coil Design: Universal for 50/60Hz, adaptable to global grids, reduces spare part variety
  6. Mechanical Position Indication: Clear ON/OFF status for on-site inspection and safe operation
  7. Aplicações Típicas

Controle Motor: Starting, stopping, forward/reverse control of 3-phase induction motors (≤11kW), por exemplo. bombas, fãs, máquinas-ferramentas

Máquinas Industriais: Main circuit control for packaging, textile, injection molding, conveyors and other equipment

Power Distribution: Branch circuit switching in distribution boards and power boxes, local/remote control

Automated Lines: Integrated with PLCs and relays for automatic control in continuous production lines

  1. Replacement Solutions (Chave)

5.1 Siemens Original Replacement (Recomendado)

Modelo originalModelo de substituiçãoPrincipais diferençasCompatibilidade
3TF4322-0XM03RT6026-1AN20Same size, AC-3 22A, AC230V coil, 2NÃO+2NC; accessories not interchangeable, full replacement requiredPerfect drop-in replacement, identical mounting, improved performance
3RT5026-1AN20Same current rating, longer mechanical life, heavy-duty ratedDomestic 3RT5 series, replaces legacy 3TF

5.2 Alternativas entre marcas

MarcaModelo de substituiçãoMatching Key ParametersAplicativo
ABBAF16-30-013-pólo, 22A AC-3, AC230V coilGeneral industrial, econômico
SchneiderLC1D25M73-pólo, 25A AC-3, AC230V coil, 2NÃO+1NCSlightly larger dimensions, verify mounting space
CHINTCJX1-22/223-pólo, 22A AC-3, AC230V coil, 2NÃO+2NCDomestic alternative, significant cost advantage
  1. Instalação & Diretrizes de Manutenção

6.1 Especificações de instalação

Mount vertically on TH35 rail, maintain ≥10mm clearance to adjacent devices for heat dissipation

For 22A rated current, main circuit recommended copper cable ≥ 4mm², tightening torque approx. 2.5N·m

Route coil wiring away from main high-voltage circuits to avoid EMI; auxiliary terminal cable ≥ 1.5mm²

6.2 Recomendações de manutenção

Regular inspection (every 6 meses): contact erosion, terminal tightness, coil insulation

Contact maintenance: replace main contacts if worn below 1mm; clean or replace auxiliary contacts if poor connection

Limpeza: Use compressed air to remove dust, prevent insulation degradation

Solução de problemas: Coil fails to pull in → check voltage and wiring; contact burning → check load current and arc system

  1. Resumo & Upgrade Suggestions
  2. Status: 3TF4322-0XM is discontinued by Siemens. 3RT6026-1AN20 is the preferred direct replacement with better performance and reliability.
  3. Selection Key: Strictly match number of poles, corrente nominal, coil voltage and auxiliary contact configuration to ensure system compatibility.
  4. Upgrade Direction: For extended life or smart functions, select 3RT6 models with expanded auxiliary contacts and remote diagnostics for modern industrial control.

Siemens 3RT6 Series (Domestic SIRIUS) Contactor Model List

Key Overview: The 3RT6 series is Siemens’ official replacement for the legacy 3TF series. Classified by frame size (S00 / S0 / S000 / S1 / S2 / S3), it covers 7-110A AC-3 current, suitable for 3-phase motors up to 55kW, available in 3-pole / 4-pólo, AC / DC coils, with extensive accessory support. Below is a list of commonly used full order numbers, sorted by frame size for general industrial use.

  1. Model Format & Core Parameter Explanation

1.1 Full Order Number Format

3RT6xxx-xxxxx (Exemplo: 3RT6026-1AN20)

SegmentSignificadoCommon Codes
3RT6Series CodeDomestic SIRIUS AC contactor, replaces 3TF series
016 / 017 / 025 / 026Tamanho / Atual016=S00(9UM); 017=S0(17UM); 025=S000(25UM); 026=S000(25UM); 034=S1(38UM)
1Main Contact Configuration1=3NO (3-phase NO); 2=3NC (3-phase NC, rare)
UM / B / F / M / G / PTensão da bobinaA=AC24V; B=DC24V; F=AC115V; M=AC230V; G=AC42V; Q=AC400V
20 / 21 / 22 / 40Contatos Auxiliares20=1NO+1NC; 21=1NO; 22=1NC; 40=2NO+2NC (larger frames)

1.2 Core Parameter Quick Reference

Frame SizeAC-3 Current (400V)Motor RatingBuilt-in Aux. ContatosAplicativo
S007–9A≤4kW1NÃO / 1NCSmall fans, bombas, solenoid valves
S012–17A≤5.5–7.5kW1NÃO+1NCSmall-to-medium machine tools, transportadores
S00022–25A≤11kW2NÃO+2NC11kW motors, general industrial circuits (replaces 3TF43)
S132–38A≤18.5kWNone (add-on required)Medium motors, air compressors, bombas
S250-63A≤30kWNone (add-on required)Heavy equipment, main power distribution
S380–110A≤55kWNone (add-on required)Motores grandes, new energy applications
  1. 3RT6 Series Popular Models (3-pólo, 3NO Main Contacts)

2.1 Frame S00 (7-9UM, ≤4kW)

Full Order No.Tensão da bobinaAC-3 CurrentAux. ContatosAplicativo3TF Replacement
3RT6016-1AN21AC230V9UM1NÃOSmall loads, solenoids3TF3000-0XM0
3RT6016-1AN22AC230V9UM1NCSmall loads, solenoids3TF3001-0XM0
3RT6016-1BB41DC24V9UM1NÃOPLC control, low-voltage DC systems3TF3000-0BB4
3RT6016-1BF40DC110V9UM1NO/1NCIndustrial DC control3TF3001-0BF4
3RT6016-1QF00AC400V9UM1NÃOHigh-voltage control circuits3TF3000-0QF0

2.2 Frame S0 (12-17UM, ≤5.5-7.5kW)

Full Order No.Tensão da bobinaAC-3 CurrentAux. ContatosAplicativo3TF Replacement
3RT6017-1AN20AC230V17UM1NÃO+1NCSmall-to-medium motors, fãs3TF3300-0XM0
3RT6017-1AN21AC230V17UM1NÃOSmall-to-medium motors, fãs3TF3301-0XM0
3RT6017-1BB40DC24V17UM1NÃO+1NCPLC control, Sistemas CC3TF3300-0BB4
3RT6017-1AF00AC115V17UM1NÃO+1NCIndustrial control, máquinas-ferramentas3TF3300-0AF0

2.3 Frame S000 (22-25UM, ≤11kW, Key Replacement for 3TF43)

Full Order No.Tensão da bobinaAC-3 CurrentAux. ContatosAplicativoKey Replacement Note
3RT6026-1AN20AC230V25UM2NÃO+2NC11kW motors, general industrial circuitsDirect replacement for 3TF4322-0XM0, same size, upgraded performance
3RT6026-1AN21AC230V25UM1NÃO11kW motors, general industrial circuitsReplaces 3TF4301-0XM0
3RT6026-1BB40DC24V25UM2NÃO+2NC11kW motors, DC control systemsReplaces 3TF4322-0BB4
3RT6026-1QF00AC400V25UM2NÃO+2NCHigh-voltage industrial circuitsReplaces 3TF4322-0QF0
3RT6025-1AC20CA24V25UM2NÃO+2NCLow-voltage control, small equipment3TF4322-0AC2

2.4 Frame S1 (32-38UM, ≤18.5kW)

Full Order No.Tensão da bobinaAC-3 CurrentAux. ContatosAplicativo
3RT6034-1AN20AC230V38UM2NÃO+2NC18.5kW motors, air compressors
3RT6034-1BB40DC24V38UM2NÃO+2NC18.5kW motors, Sistemas CC
3RT6034-1AF00AC115V38UM2NÃO+2NCIndustrial control, heavy equipment

2.5 Frame S2 (50-63UM, ≤30kW)

Full Order No.Tensão da bobinaAC-3 CurrentAux. ContatosAplicativo
3RT6045-1AN20AC230V63UM2NÃO+2NC30kW motors, bombas, main power distribution
3RT6045-1BB40DC24V63UM2NÃO+2NC30kW motors, DC control systems
3RT6046-1AN20AC230V80UM2NÃO+2NC45kW motors, heavy equipment

2.6 Frame S3 (80-110UM, ≤55kW)

Full Order No.Tensão da bobinaAC-3 CurrentAux. ContatosAplicativo
3RT6054-1AN20AC230V110UM2NÃO+2NC55kW motors, new energy, large industrial equipment
3RT6055-1BB40DC24V110UM2NÃO+2NC55kW motors, high-voltage DC systems
  1. Popular 4-pole Models (3P+N, with Neutral Protection)
Full Order No.PolonesesTensão da bobinaAC-3 CurrentAux. ContatosAplicativo
3RT6026-1AN233P+N (4P)AC230V25UM2NÃO+2NC11kW motors, loads with neutral
3RT6034-1AN233P+N (4P)AC230V38UM2NÃO+2NC18.5kW motors, loads with neutral
3RT6045-1AN233P+N (4P)AC230V63UM2NÃO+2NC30kW motors, loads with neutral
  1. Key Selection & Notas de substituição

4.1 Direct 3TF-to-3RT6 Replacement Table (Essencial)

Legacy 3TF ModelRecommended 3RT6 ReplacementKey MatchesDiferença
3TF3000-0XM03RT6016-1AN219UM, AC230V, 1NÃOSame size, improved electrical life
3TF3300-0XM03RT6017-1AN2017UM, AC230V, 1NÃO+1NCSame size, longer mechanical life
3TF4322-0XM03RT6026-1AN2025UM, AC230V, 2NÃO+2NCPerfect drop-in, compatible mounting, maior capacidade de interrupção
3TF4400-0XM03RT6034-1AN2038UM, AC230V, 2NÃO+2NCUpgraded size for higher-power motors

4.2 Critical Selection Rules

  1. Coil voltage must match: AC coils use M/A/F/Q; DC coils use B/F to avoid burnout.
  2. Auxiliary contacts as needed: S00/S0 have integrated contacts; S1 and above require 3RH series add-on blocks.
  3. Breaking class: Standard duty = S class (≤150kA@400V); heavy-duty / high short-circuit = K/H class.
  4. Expansão de acessórios: Suporta viagem de derivação, disparo por subtensão, surge suppressors; accessories compatible with 3RT5/6 series.
  5. List Usage Instructions
  6. This list covers general industrial models. For special applications (explosion-proof, high protection), refer to Siemens’ official full catalog.
  7. Ao substituir, strictly match poles, atual, coil voltage and auxiliary contacts to ensure mounting and system compatibility.
  8. For 4-pole versions, higher breaking class or special accessories, provide additional requirements for refined model selection.