6ES7: Automação SIMATIC S7 série
3: S7-300 PLC platform
17: CPU317, high-performance CPU
2: Dual-interface version
UM: DP interface variant (no Profinet port, differs from 2EK14 PN/DP model)
K: Hardware revision code
14: Firmware version V2.7
0AB0: Product packaging code, standard German original model
Designação completa: CPU317-2DP, S7-300 Central Processing Unit, 1MB work memory, dual DP interfaces, MMC micro memory card mandatory
- Principais especificações técnicas
- Memória
Work memory: 1MB (programa + dados)
Retentive memory: 256KB
Programas, project files and firmware are fully stored on MMC card. CPU cannot start without MMC card.
- Execution Performance
Bit instruction: 25ns; Word instruction: 30ns; Fixed-point instruction: 40ns; Floating-point instruction: 160ns
- Interfaces de comunicação (2 Independent DP Ports)
Port1: MPI / PROFIBUS-DP, máx.. 12Mbps, configurable as DP master/slave
Port2: Independent PROFIBUS-DP, mestre/escravo, dual DP bus (this model has no Ethernet Profinet port)
- Capacidade de E/S
Máx.. E/S digitais: 65536 pontos (Process Image area: 8192 Bytes)
Máx.. canais analógicos: 4096 canais
Máx.. racks de expansão: 3 prateleiras (main rack + 3 racks de expansão)
Supports FM function modules and CP communication modules
- Elétrica & Dados Mecânicos
Fonte de energia: CC24V, consumo de energia aprox.. 3.5C
Dimensões: 40mm×125mm×130mm, peso aprox.. 0.406kg
Temperatura operacional: 0~60℃ (standard S7-300 range)
- Software de programação: STEP7 V5.x, Portal TIA (Classic Mode)
- Ciclo de vida do produto
Officially entered phase-out stage (PM400) de 2023-10-01. New project orders are no longer accepted; spare parts remain available. Circulating units on market are mainly stock items or used/refurbished modules.
Comparison within series:
6ES7317-2AJ10-0AB0: 512KB work memory, older generation; 2AK14 is upgraded version with doubled memory and improved performance. Direct replacement with AJ10 is invalid if program size exceeds 512KB.
6ES7317-2EK14-0AB0: CPU317-2PN/DP with Profinet port, 1MB work memory. Hardware base compatible with AK14, but different communication interfaces, não diretamente intercambiável.
- Cenários típicos de aplicação
Main controller for production lines, distributed I/O systems over multi-DP buses
Máquinas-ferramentas, metalurgia, papel, embalagem, borracha & plastic and other medium-to-large automation equipment
Multi-drive DP bus control with dual DP network segmentation (one bus for field I/O, one bus for inverters)
PCS7 DCS slave stations, legacy production line retrofit projects
- Seleção de modelo & Soluções de substituição
5.1 Direct replacement on same platform (retrofit of legacy projects, minimal modification)
Mesmo modelo: 6ES7317-2AK14-0AB0 (spare procurement. Attention required for MMC migration and firmware version matching)
⚠️Nota: MMC card cannot be simply unplugged and inserted into new CPU; program and hardware configuration must be re-downloaded. Verify firmware version before replacement to avoid unexpected shutdown.
5.2 Cross-platform upgrade (Recomendado para novos projetos)
S7-300 discontinued, recommended upgrade to S7-1500 series:
CPU1511C-1PN / CPU1513C-1PN; existing DP bus can be retained via ET200SP IM155-6DP interface module for legacy DP slaves.
5.3 Alternativa doméstica
CLP doméstico (Inovação, Xinje, Co-Trust etc.). Program and DP communication configuration must be completely rewritten. STEP7 project cannot be directly migrated. Suitable for full line renovation.
- Instalação & Diretrizes de Manutenção
- Mandatory MMC requirement: Minimum 4MB, 8MB recommended. PLC fails to run if MMC is damaged or missing. All programs reside on MMC; no onboard storage in CPU.
- Montagem: Montagem em trilho DIN, S7-300 backplane bus. PS307 power supply module is mandatory.
- Aterramento: Single-end grounding for DP cable shield to reduce EMC interference. Terminating resistors configured separately for each DP bus.
- LEDs de status: SF (system fault), namorado (bus fault), RUN/STOP. For DP bus faults, check terminating resistors, wiring and DP address conflicts first.
- Solução de problemas comuns
- SF ON, BF flashing: DP cable breakage, faltando resistor de terminação, slave station fault, DP address conflict.
- No RUN after power-up, STOP LED steady ON: MMC missing/damaged, firmware corruption, erro de programa.
- Falha no download do programa: Firmware mismatch in STEP7, wrong CPU order number selected in hardware configuration.
- Parameter loss after power cycle: Incorrect retentive area setup, MMC card not fully saved.
- Foreign Trade Information
Código HS: 85371011 (Programmable Logic Controller PLC)
Export Control: ECCN EAR99H, non-military item, normal industrial export.
- Inspection Checklist for Second-hand Units
- Verificação visual: No burn marks, no oxidation on backplane bus contacts, no water ingress or corrosion.
- Teste de inicialização: Insert functional MMC card; CPU enters RUN mode normally without SF/BF alarms.
- Firmware reading: Read firmware V2.7 online via STEP7, cross-check with label order number.
- Teste de comunicação: Test MPI/DP ports separately to verify both DP channels are functional.
- Serial number verification: Read internal serial number to confirm non-relabeled refurbished module.
STEP7 Hardware Configuration Template|6ES7317-2AK14-0AB0 (CPU317-2DP, V2.7)
Applicable software: STEP7 V5.4 / V5.5 / V5.7; TIA Portal Classic Mode can import this hardware configuration
Prateleira: UR rack (S7-300 rail, Prateleira 0)
- Rack Slot Allocation (HW Config)
| Slot | Nome do módulo | Número do pedido. | Observações |
| 1 | PS307 Power Supply | 6ES7307-1EA01-0AA0 (24V 5A) | Replaceable with 1KA01 (2UM), select according to load |
| 2 | CPU317-2DP | 6ES7317-2AK14-0AB0, V2.7 | Dual DP ports: X1=MPI/DP; X2=independent DP |
| 3~11 | Signal Module / FM / CP | Conforme necessário | Máx.. 8 modules on main rack; IM365 / IM360+IM361 for expansion racks |
⚠️Importante: This model has no Profinet Ethernet port, only two PROFIBUS-DP interfaces
- Core CPU Properties (Double-click CPU to open properties)
2.1 Em geral
Número do pedido: 6ES7317-2AK14-0AB0
Firmware version: V2.7
Work memory: 1MB
Load memory: MMC dependent (8MB recommended, 6ES7953-8LG30)
2.2 Memória
Retentive Settings
Memory bits M: MB0~MB15 set as retentive by default
Timers, Counters: Retention can be ticked
Blocos de banco de dados: Tick “Retentive” in DB properties, data saved to MMC after power loss
Imagem do processo
Input PI: 8192 Bytes
Output PQ: 8192 Bytes
Partitioned process image available (OB1/OB35 partition refresh, suitable for high-speed DP bus)
2.3 Ciclo / Relógio
Cycle monitoring watchdog: Default 500ms, maximum 6000ms
Tempo mínimo de ciclo: Default 0ms
Clock memory byte: MB10 recommended (bit0~bit7:10Hz,5Hz,2.5Hz,2Hz,1Hz,0.5Hz,0.2Hz,0.1Hz)
2.4 Interrupt OB Blocks
Cyclic interrupt OB35: Default 100ms, adjustable 1~60000ms (100/200ms commonly used for DP control)
Hardware interrupt OB40, Diagnostic interrupt OB82, Rack fault OB86, DP slave fault OB87 enabled on demand
2.5 Proteção
Nível de proteção: 1(sem proteção)/2(read protection)/3(read-write protection)
Password: Configurable on site, activated after hardware configuration download
Modo: Protection level editable under STOP mode
- Dual DP Interface Configuration (Crítico: Two independent DP subnets)
✅Port X1: MPI / PROFIBUS-DP (Port1)
- Tipo de interface: MPI or DP (mutually exclusive)
- Bus parameters:
Taxa de transmissão: 187.5k / 500k / 1.5M / 12M (DP max.12Mbps)
Endereço da estação: 2 recomendado (MPI default 2; DP master customizable 1~126)
Highest station address HSA:126
- Modo: Mestre DP, can also be set as DP Slave
Propósito: MPI programming download / Subnet 1 for distributed I/O and drives
✅Port X2: Independent PROFIBUS-DP (Port2, Somente DP, no MPI)
- Create a new separate PROFIBUS subnet (physically isolated from X1)
- Bus parameters: Baud rate matched to slaves on this subnet, max.12Mbps
- Endereço da estação DP: Must not overlap addresses in X1 subnet, por exemplo. 3
- Modo: Mestre DP (mais comum), supports DPV0/DPV1
Propósito: Subnet 2 for inverters and DP instruments. Load separation on two buses to reduce bus interference.
General bus rule: Terminating resistor ON at both ends of bus, OFF at intermediate nodes; single-end shielding earthing.
- Address Map Template (Default Range)
Input I: 0 ~ 8191 Byte
Output Q: 0 ~ 8191 Byte
Peripheral Input PI: 0 ~ 8191 Byte
Peripheral Output PQ: 0 ~ 8191 Byte
Memory bit M: 0~8191 Byte
Temporizador T: 0~2048
Contador C: 0~2048
Local data L: Max.32768Byte per priority class, max.2048Byte per FB block
- Recommended OB Block Template for New Projects
OB1: Main cycle
OB10: Time-of-day interrupt (conforme necessário)
OB35: Cyclic interrupt (100EM)
OB82: Diagnostic interrupt (module fault alarm)
OB86: Rack/DP slave loss interrupt (mandatory for DP projects)
OB87: DP communication fault interrupt
OB121: Erro de programa; OB122: Peripheral access error (retained to prevent CPU stop)
- Download & MMC Precautions
- MMC card must be inserted before downloading hardware configuration; download impossible without MMC.
- Compatibilidade de firmware: Hardware library in STEP7 must contain CPU317-2DP V2.7; older hardware library cannot locate this CPU.
- CPU hardware replacement: Configuração de hardware + user program must be re-downloaded. MMC cannot be transplanted directly.
- Dual DP master: Slaves configured separately on each DP subnet; cross-subnet direct addressing unavailable.
- Erros comuns de configuração
- Wrong model selection: Accidentally select 6ES7317-2EK14 (PN port version), causes compile error in hardware.
- Two DP ports assigned to same subnet: Bus conflict, BF LED flashing.
- Watchdog time set too short: DP bus failure triggers OB80 timeout and CPU stop.
- Insufficient process image size: I/Q address overflow with large-scale distributed I/O.
- Export Template Operation Guide
- Complete above settings in HW Config
- Menu: Station → Save and Compile
- Export as .cfg or export station in SIMATIC Manager for project archiving
- Backup: Export hardware configuration separately for reuse on similar production lines
Contator,disjuntor,sensor,Codificador,CLP,Conversor




















NH42-63-318x560.png)