DSP DIN rail AC-DC fonte de energia, DSP30-24, rated output 24VDC / 30W class, Montagem em trilho DIN35, Class II double insulation, no protective earth terminal required
- Especificações elétricas principais
Entrada
AC: 90~264VAC, 47~63 Hz (wide input voltage for global use)
DC input compatible: 120~370VDC
Built-in PFC, compliant with EN61000-3-2
Cold-start inrush current: 25A@115VAC /50A@230VAC
Saída
Tensão nominal: 24CCV, adjustable range 24~28VDC via potentiometer
Corrente nominal: 1.3UM, rated power 31.2W
Voltage regulation accuracy: ±1%; ondulação & barulho: 50mV (20MHz bandwidth)
Funções de proteção: Proteção contra sobrecorrente (110~160%, fold-back current limiting, proteção contra curto-circuito), overvoltage protection 30~36Vdc, overtemperature protection
Hold-up time: 25ms @115VAC input
Eficiência: Typical 83%~87%
- Mecânico & Ambiental
Montagem: Trilho DIN padrão de 35 mm
Dimensões: W53mm × H95.5mm × D55.6mm
Peso: Aprox.. 200g
Resfriamento: Convecção natural, sem ventilador
Temperatura operacional: -25℃ ~ +71℃; derating starts above 61℃ (2.5%/℃)
Temperatura de armazenamento: -25~+85℃; humidity 20~90%RH (sem condensação)
- Indicator LEDs & Definição de terminal
eu: AC Line; N: CA Neutro
+: 24V Output Positive; -: Output Negative
Vout ADJ: Output voltage trim potentiometer
LED verde: DC OK (Output normal)
Red LED: DC LO (Subtensão / Falta)
- Certificações & Segurança
Safety standards: EN60950-1, UL60950-1, UL1310 Class2 output, CE/UKCA
EMC: EN55032 Class A; Immunity to EN61000-4 series
Tensão suportável de isolamento: 3kV CA
- Model Status & Substituições
DSP30-24 legacy model: NRND (Not Recommended for New Design); upgraded model DSP30-24/277A2, supports wider input 90~304VAC, direct rail replacement, verify pin definition before use
- Aplicações Típicas
CLP, sensores, válvulas solenóides, small control cabinets, automação predial, 24V industrial low-voltage power supply, ideal for compact cabinet installation.
- Solução de problemas comuns
- LED verde apagado: Check AC input L/N, internal fuse, and minimum input voltage
- Red LED steady on: Output overload or short circuit; disconnect load to test power supply recovery
- Output voltage too high/low: Adjust Vout ADJ potentiometer
- Voltage drop under high temperature: Exceed derating temperature; reduce load or improve cabinet ventilation
- Alternativas domésticas compatíveis
Meanwell: DR-30-24 (30C, Trilho DIN)
Delta: DRP-24V30W
Mornsun: LI30-24B24
DSP30-24 (DSP30-24VDC) Casos de aplicação
Principais vantagens: Slim depth (only 56mm), Class II double insulation without PE, fanless natural cooling, wide input voltage, well suited for wall-mounted small electrical boxes and slim control cabinets; rated 24V 1.3A, recommended total load power ≤25W for derating margin
Caso 1: Sistema de gerenciamento predial (BMS) / Controle de HVAC (OEM Primary Application)
Cargas: Small DDC controllers, temperatura & transmissores de umidade, differential pressure sensors, electric damper actuators, room panels
System Description: Slim wall-mounted low-voltage cabinet, DSP30-24 DIN-rail mounted locally to supply HVAC field I/O modules and sensors. Class II design eliminates PE wiring and simplifies cabling.
Notas de seleção: Total current of multiple sensors + small dampers <1A; full power available if cabinet temperature ≤61℃.
Sites típicos: Prédios de escritórios, shoppings, hospital air handling units, fresh air unit local control cabinets.
Caso 2: Access Control & Segurança / Fire Alarm Systems
Cargas: Access controller, door contacts, leitores de cartão, fire alarm input modules, sounder beacons, zone modules
System Description: Wall-mounted security/fire control cabinet, AC220V feeds DSP30-24, 24VDC output powers access host and alarm modules. Wide 90~264VAC input provides tolerance against grid voltage fluctuation. Built-in short/overcurrent protection prevents host damage from field wiring short-circuit.
Observação: Not for fire main backup power loops, used for auxiliary monitoring and access control subsystems only.
Caso 3: Small Industrial Automation Cabinets (Standalone Stations)
Cargas: Micro PLC (Siemens S7-200SMART, Mitsubishi FX3U compact CPU), sensores de proximidade, sensores fotoelétricos, relay modules, pequenas válvulas solenóides
System Description: Local control cabinet for assembly line stations, inspection benches, pequenos transportadores. One PLC + 4~8 sensors + 2~3 small solenoid valves.
Cuidado: Solenoid valves draw high inrush current, reserve margin for surge current during load calculation; recommended total steady-state load ≤25W.
Adequado para: Sorting stations, inspection equipment, small packaging machine local controls.
Caso 4: Monitoramento Remoto & IoT Data Acquisition Cabinets
Cargas: UTR, data acquisition modules, 4G/5G gateways, pressure/level transmitters, wireless sensors
System Description: Remote acquisition cabinets for water, aquecer, óleo & gas sites or equipment rooms. Wide input range and -25℃ cold-start capability for non-constant-temperature environments.
Características: Fanless natural convection, no wearing parts, maintenance-free for unattended sites.
Caso 5: Small Intelligent Lighting Control Systems
Cargas: DALI lighting gateway, dimmer modules, 24V lighting bus sensors
System Description: Wall-mounted control cabinets for shopping malls and conference rooms, power supply for lighting bus controllers. Low profile fits slim lighting distribution boxes.
Caso 6: Teste & Medição / Laboratory Small Tooling
Cargas: Test fixture I/O boards, signal conditioning modules, sensor signal transmitters
System Description: Simple production test benches and small laboratory measurement cabinets. Stable 24V DC with low ripple, ideal for transmitter powering.
Seleção & Limitações do aplicativo (Engineering Key Points)
- Max continuous output: 31.2W /1.3A, engineering design recommended derate to 80% (≤25W)
- Derating required when ambient temperature>61℃; further reduce load for high cabinet temperature
- Design sem ventilador; reserve ventilation gaps on left/right, do not stack tightly beside circuit breakers
- NRND legacy model; use DSP30-24/277A2 for new designs; DSP30-24 only for spare replacement on existing equipment
- Class II double insulation, no PE wire required, simplifies wiring for many wall-mounted low-voltage cabinets, but not applicable for safety loops beyond extra-low voltage safety requirements
Typical Wiring Topology Reference
AC L/N → DSP30-24 → 24V+ /24V→ Parallel loads: PLC/DDC + Sensores + Relay modules; recommend fuse and surge absorber on output side to protect inductive loads such as solenoid valves.
DSP30-24 Engineering Selection Checklist
Applicable for: TDK-Lambda DSP30-24 (24VDC 31.2W, Trilho DIN, Classe II, resfriamento natural)
Propósito: New project evaluation / field retrofit / spare part verification; legacy NRND model, use DSP30-24/277A2 for new projects
✅ 1. Load Power & Current Verification (Essencial)
Avaliado: 24V, 1.3UM, 31.2C; recomendado 80% derating limit: 25W /1.04A
- Sum steady-state loads
Sum rated current of all 24V devices: CLP, DDC, sensores, transmitters, relés, portais, etc..
Cargas indutivas (válvulas solenóides, small actuators): inrush current must be considered, not only steady-state value
Total steady-state current ≤1.04A (recomendado); short peak up to 1.3A, not continuous
- Load type restrictions
✅ Suitable: Transmitters, proximity/photoelectric switches, small I/O, UTR, access controllers, DALI gateways
⚠️ Use caution: Válvulas solenóides de alta potência, large actuators, heating loads, motores
❌ Proibido: Direct battery float charging (no charge management), high-power LED constant-current boards
- Output side protection selection
Recommended series fuse at output: 2Um fusível de ação lenta (24V side)
Cargas indutivas (solenóide / damper actuators): Freewheeling diode or RC snubber across coil to suppress back EMF and prevent power supply damage
Long cable runs: Add 24V-rated TVS for surge protection
✅ 2. Input Side Verification
- AC input voltage: 90~264VAC, 47~63 Hz; compatible with DC 120~370VDC
Sites with large voltage fluctuation (old factories): Confirm minimum field voltage ≥90VAC
- Fiação de entrada: L Line, N Neutral; Classe II, PE earth not required for power supply
Observação: Cabinet shell should connect to protective earth for EMC, power supply itself does not require PE
- Input inrush current: 25A@115VAC; 50A@230VAC
When multiple power supplies switch on simultaneously in one distribution box, select MCB carefully to avoid tripping at switch-on
✅ 3. Temperatura ambiente & Derating Verification (Common Pitfall)
Faixa de temperatura operacional: -25℃ ~ +71℃
Derating rule: Derating starts above 61℃ at 2.5%/℃
Exemplo: Cabinet temperature 66℃, 5℃ above 61℃ → 12.5% redução de potência, max available power=31.2×(1-0.125)=27.3W
Engineering recommendation: Reserve extra margin if cabinet temperature>55℃, ideally keep ≤60℃
- Installation ventilation requirements
Minimum gap top/bottom ≥10mm; left/right ≥5mm clearance
❌ Do not mount tightly next to heat-generating components such as breakers and contactors
❌ Do not enclose inside fully sealed airtight boxes
- Temperatura de armazenamento: -25~+85℃, desligar
✅ 4. Verificação de instalação mecânica
- Montagem: Trilho DIN padrão de 35 mm, instalação vertical (terminals upward)
Horizontal / upside-down mounting not recommended; worsens heat dissipation and accelerates derating
- Dimensões: W53 × H95.5 × D55.6 mm; preferred for slim cabinets
- Vibração & choque: Suitable for general industrial and building automation; add rail lock for heavy machinery with high vibration
✅ 5. Protection Function Verification (Fault Modes)
Built-in protections: Fold-back current limiting / proteção contra curto-circuito, proteção contra sobretensão, overtemperature protection
Protection behavior: Hiccup mode on some versions; auto-recovery after fault removal
- Sobrecorrente: 110~160% rated current, fold-back limiting
- Proteção contra sobretensão: Trigger at 30~36VDC
- Proteção contra superaquecimento: Shutdown on overtemperature, auto retry after cooling
Observação: Repeated short-circuit / thermal cycling shortens service life; output fuse should not be omitted
✅ 6. Status Indicators Verification
DC OK (Verde): Output healthy
DC LO (Vermelho): Subtensão / sobrecarga / falha de curto-circuito
Vout ADJ potentiometer: Output adjustable 24~28VDC
Dica de comissionamento: Do not turn voltage up to 28V upper limit under no-load; re-measure voltage with load connected to avoid overvoltage damage to transmitters
✅ 7. EMC, Isolamento & Verificação de segurança
- Isolation rating: Class II double insulation, input-output isolation withstand 3kV AC
- EMC: EN55032 Class A; immunity meets EN61000-4 (ESD, burst, surto)
⚠️ Class A: Para ambientes industriais; not recommended for residential environments due to EMI non-compliance risk
- Certificações: UL/CE/UKCA; safety standard EN60950-1
- Cabeamento: Route 24V DC cables away from 220V AC power cables to reduce coupling interference
✅ 8. Model Lifecycle Verification (Critical Engineering Reminder)
DSP30-24: NRND Not Recommended for New Design
For repair & replacement on existing equipment: DSP30-24 acceptable
Novos projetos: Upgrade to DSP30-24/277A2, input 90~304VAC, direct DIN rail replacement, verify terminal definition
Alternative domestic models: DR-30-24, LI30-24B24
✅ 9. Site Commissioning Procedure (Power-up Sequence)
- Desconecte todas as cargas, power supply alone, measure no-load output voltage, trim Vout ADJ to 24V
- Connect loads gradually, monitor output voltage, temperature rise and LED status
- Perform short-circuit test (short duration), confirm hiccup protection activates and auto-recovers after fault removal
- Run full load for 30min, check housing temperature rise for abnormal heating
- Check voltage drop on long wiring runs; slightly increase output voltage to compensate for cable drop if wire gauge is thin or distance is long
📋 Quick Tick List (Copy directly to Excel)
| Verification Item | Exigência | Observações |
| Total steady-state load power | ≤25W (80% desclassificação) | Include inrush for inductive loads |
| Cabinet ambient temperature | Full power ≤61℃; derate above 61℃ | Measure cabinet internal temp, not room ambient |
| Faixa de tensão de entrada | 90~264VAC | Record minimum site voltage |
| Installation ventilation clearance | Top/bottom ≥10mm, left/right ≥5mm | Do not mount adjacent to heat sources |
| Output protection components | 2Um fusível de ação lenta, snubber for inductive loads | |
| Orientação de montagem | DIN rail vertical mount, terminals upward | Upside-down impairs heat dissipation |
| Project type | Existing maintenance / New design | DSP30-24 not recommended for new projects |