Conversamos: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Sobre Contato |

Schneider Electric GV2-ME21C - Contator,disjuntor,inversor solar,medidor elétrico,baterias solares

NotíciasNotícias comerciais

Schneider Electric GV2-ME21C

Schneider Electric GV2-ME21C is a 3-pole thermal-magnetic motor protection circuit breaker belonging to the TeSys GV2M series. Its core parameters cover electrical, proteção, mechanical and environmental dimensions. Below is the structured and complete technical parameter sheet:

  1. Parâmetros Elétricos Básicos
Parameter ItemValueStandard/Remarks
Tensão operacional nominal (Ué)690V e (CEI 60947-2); 600V e (UL 508)Suitable for three-phase industrial circuits
Tensão nominal de isolamento (interface do usuário)690V eBenchmark for insulation safety
Tensão nominal suportável ao impulso (Uimp)6kVSurge resistance capability
Thermal Overload Setting Current (Ir)17-23UM10-level adjustable, suitable for motors of corresponding power
Corrente operacional nominal (Ith)23UMUpper limit of long-term current carrying capacity
Número do pólo3-póloProtection for the main circuit of three-phase motors
Utilization CategoryAC-3 (CEI 60947-4-1); Category A (CEI 60947-2)Suitable for motor starting, stopping and operation
Control MethodPush-button type (handle operation)Convenient for closing, opening and trip testing
  1. Protection and Breaking Capacity
Parameter ItemValueApplicable Conditions
Ultimate Short-Circuit Breaking Capacity (UTI)3kA@690V AC; 15kA@400/415V AC; 50kA@230/240V AC; 6kA@440V AC; 4kA@500V AC50/60Hz, compatível com IEC 60947-2
Service Short-Circuit Breaking Capacity (CIs)75% Icu@690V AC; 50% Icu@440V ACCan continue to be used after breaking
Magnetic Trip Current327-390UM (aprox.. 15-17 times of Ir)Threshold for instantaneous short-circuit protection
Phase Loss ProtectionAvailableReliable tripping in case of three-phase unbalance
Proteção contra sobrecarga térmica10-level ambient compensationSuitable for working conditions from -20℃ to +60℃
  1. Mechanical and Installation Parameters
Parameter ItemValueStandard/Remarks
Mounting Method35mm standard DIN rail (EM 60715) / screw mountingDIN rail mounting is preferred; screw hole spacing is approx. 45milímetros
Mounting PositionHorizontal/VerticalFlatness error ≤ 0.5mm/m
Tipo de terminalScrew-clamp typeSuitable for 2.5-4mm² copper core wires, torque 1.5-2.5N·m
Dimensões Gerais (H×W×D)89mm×44.5mm×78.2mmCompact design, saving cabinet space
PesoApprox. 0.26kgLightweight, easy to install
Electrical Service Life100,000 operaçõesDurability of closing and opening cycles
Mechanical Service Life200,000 operaçõesReliability of the operating mechanism
  1. Environmental and Protection Parameters
Parameter ItemValueStandard/Remarks
Ingress Protection Rating (IP)IP20 (main unit)CEI 60529, protection against finger touch
Mechanical Impact Resistance Rating (IK)IK04Resistance to mechanical impact
Temperatura operacional-20℃~+60℃Wide temperature range for industrial applications
Temperatura de armazenamento-40℃~+85℃No condensation or corrosive gas
CertificationsCEI, UL, CSA, CCC, EAC, Green Premium (RoHS/REACH)Compliant with multiple global regional standards
  1. Potência do motor aplicável (Referência)
Voltage LevelPotência do motor aplicável
400/415V e9KW
500V e11KW
690V e18.5KW
  1. Supplementary Core Features
  2. The handle can be locked in the OFF position to prevent accidental closing and improve maintenance safety.
  3. Auxiliary contact modules such as GV2-AE11 (1NO+1NC) can be added for signal feedback or control circuit expansion.
  4. The terminals are suitable for multi-strand flexible wires (cold-pressed terminals are required) to avoid heating caused by loose wiring.