Original Factory Order No.: 1SBL176001R2110
- Definiția defalcării modelului
AF16Z 30 10 21
- AF16Z: AF series; Z = Low-power electronic wide-range coil (direct PLC drive capable); Dimensiunea cadrului 16 clasă
- 30: Contacte principale: 3 Deschis normal (3NU), no main Normally Closed contacts
- 10: Built-in auxiliary contacts: 1 Deschis normal (1NU), 0 În mod normal închis
- 21: Coil code → Control voltage: 24~60 V AC 50/60Hz / 20~60 V DC
⚠️ Difference between AF…Z and standard AF: Extremely low coil power consumption, supports direct driving by DC24V PLC outputs, resistant to voltage dips (compliant with SEMI F47).
- Core Electrical Ratings
Maximum main circuit voltage: 690 V și
AC-1 (sarcină rezistivă), ≤40°C ambient: 30 O
AC-3 (3-motor de fază, 400 V): 18 O, potrivit pentru 7.5 motor kW
AC-3 (690 V): 10.5 O, max. 9 kW
Montare: Montare pe șină DIN, conexiune terminală cu șurub
Dimensiuni de gabarit: W 45 mm × H 86 mm × D 77 mm
Temperatura de functionare: -40~+70 °C (without thermal overload relay); -25~+60 °C (with thermal overload relay)
- Key Coil Characteristics
Wide-range AC/DC universal: AC 24~60 V / DC 20~60 V
Suprimarea supratensiunii încorporată; no external RC snubber or diode required
Low holding power consumption, ideal for continuous energized operation
Withstands short-term voltage fluctuations and voltage drops
- Identificarea terminalului
Circuitul principal: 1L1-2T1, 3L2-4T2, 5L3-6T3
Contact auxiliar: 14NU (Deschis normal)
- Common Alternatives & Distinctions
- AF16Z-30-10-11: Same voltage range, equipped with standard AF coil (non low-power Z coil); cannot be directly driven by low-current PLC outputs, not interchangeable.
- AX16-30-10: AX economy series, without electronic wide-range coil, fixed control voltage; cannot replace AF16Z.
- For 1NO + 1Contacte auxiliare NC: Select model AF16Z-30-11-21.
- Aplicații tipice
Upstream of variable frequency drives, fani & pompe de apa, HVAC equipment, semiconductor machinery, PLC DC output direct load control, industrial sites requiring high tolerance to voltage fluctuations.
ABB AF16Z-30-10-21 Contactor Installation Technical Document
Comanda nr.: 1SBL176001R2110
- General Safety Instructions
⚠️ All installation, wiring and maintenance work must be carried out with all power disconnected; lockout-tagout procedure is mandatory. Work shall only be performed by qualified electricians.
- Clasa de protectie: IP20. For cabinet installation only. Do not install in open air, wet environments, locations with heavy dust or corrosive gas exposure.
- Standarde aplicabile: IEC/EN 60947-1, IEC/EN 60947-4-1; UL/CSA certified.
- AF16Z is equipped with a low-power electronic wide-range coil with integrated surge suppression circuit. No external RC snubber or diode connection is required.
- Informații de bază despre produs
2.1 Definiția modelului
AF16Z: AF series, dimensiunea cadrului 16, Z = low-power electronic coil
30: 3 contactele principale deschise în mod normal
10: Încorporat 1 contact auxiliar normal deschis
21: Coil voltage range AC 24~60 V 50/60Hz / DC 20~60 V
2.2 Dimensiuni generale
Lăţime 45 mm × Height 86 mm × Depth 77 mm
2.3 Rating Summary Table
| Articol | Parametru |
| AC-1 resistive load (40 째C) | 30 O |
| AC-3 motor load (400 V) | 18 O, compatibil cu 7.5 kW 3-phase motor |
| Maximum operating voltage | 690 V și |
| Temperatura de functionare (without thermal relay) | -40 째C ~ +70 째C |
| Temperatura de functionare (with thermal overload relay) | -25 째C ~ +60 째C |
- Specificații de instalare mecanică
3.1 Metode de montare
Two mounting options available:
- Montare pe șină DIN (Recomandat)
Rail standard: TS35 (35×7.5 mm / 35×15 mm)
Operațiunea: Hook the bottom latch onto the rail, press down until an audible click confirms locking. For removal, use a flat screwdriver to pry the bottom latch and lift upwards.
- Base Plate Screw Mounting
Fasten diagonally using 2 × M4 screws; refer to outline drawing for mounting hole spacing.
3.2 Orientarea montajului & Clearance
- Montare verticală (terminals top & fund) preferat. 90° horizontal side mounting is permitted; upside-down installation is forbidden.
- Multiple units may be mounted side-by-side without current derating. Maintain ≥15 mm vertical clearance for ventilation; keep away from heat-generating components such as resistors and inverters.
- Avoid installation in high-vibration locations. Vibration acceleration >0.5g requires vibration damping measures.
- Electrical Wiring Specifications
4.1 Terminal Marking Definition
Upper main circuit: L1, L2, L3 (Power Inlet)
Lower main circuit: T1, T2, T3 (Load Outlet)
Non-UL applications allow power feed from top or bottom; UL certified installations require power input from upper L terminals.
Coil terminals A1, A2: Control signal input (AC/DC non-polarized)
Contact auxiliar 13-14: Built-in normally open contact (1NU)
4.2 Specificația cablului & Lungime de stripare
Lungimea standard de dezilare a firelor: 10 mm
Main circuit conductors: Solid/stranded copper cable 1~6 mm²; ferrules recommended for flexible cables
Controla / auxiliary circuit conductors: 0.75~2.5 mm²
4.3 Cuplul de strângere (Obligatoriu)
Borne ale circuitului principal: 1.5 N·m
Coil A1/A2 & auxiliary contact terminals: 1.2 N·m
Insufficient torque causes terminal overheating; excessive torque leads to thread stripping.
Recommended tools: PZ2 Pozidriv screwdriver / 5.5 mm flat torque screwdriver.
- Critical Coil Application Notes (Core Feature of AF16Z)
- Gama de tensiune: AC24~60 V / DC20~60 V, wide voltage compatibility, direct drive by PLC DC outputs.
- Very low coil holding power consumption, suitable for long-term energized operation; compliant with SEMI F47 voltage sag immunity requirements.
- A1 and A2 are non-polarized; polarity does not matter for DC24V control.
- Do not apply control voltage exceeding 60 V, otherwise the electronic coil module will be destroyed.
- Optional Accessory Installation
- Contacte auxiliare montate lateral (CA4 series)
Snap-fit onto left/right side slots without tools. Maximum 2 sets of side auxiliary contacts can be fitted to AF16.
- Interblocare mecanică
Install for reversing circuit configuration of two AF16Z contactors to prevent simultaneous closing and short circuit between forward and reverse phases.
- Thermal overload relay matching
Compatible with TA25DU series thermal relays, direct snap-fit mounting underneath the contactor.
- Commissioning Procedure After Power-On
- Under power-off condition: Visual inspection for correct wiring, no metallic debris, all terminals tightened to specified torque.
- Manually actuate contactor mechanism to confirm smooth operation without jamming.
- Test control circuit independently: Apply rated control voltage to A1/A2; contactor shall pull in reliably and drop out smoothly upon power removal.
- Verify synchronous switching of auxiliary contact 13-14 with contactor operation.
- Connect main circuit for no-load test run; check for abnormal noise and rapid terminal temperature rise.
- 30-minute loaded operation test; recheck terminal temperature to ensure temperature rise stays within allowable limits.
- Installation Faults & Prohibited Practices
❌ Forbidden operations:
Exposed loose strands on cable terminals
Tightening terminals while energized
Control voltage outside the 20~60 V range
Blocking ventilation channels above and below the contactor
Direct installation in environments with combustible dust or continuous condensation
Common Post-Installation Issues
- Contactor chattering/unstable pull-in: Verify control voltage is above minimum operating level; check voltage drop along control cables.
- Supraîncălzirea terminalului: Retighten terminals to specified torque; confirm conductor cross-section is adequate.
- Failure to pull in when driven by PLC: Confirm unit is AF16Z (bobină de putere redusă); standard AF16 coil cannot be directly driven by PLC transistor outputs.
- Cerințe de întreținere
- Periodic inspection of terminal temperature and abnormal noise.
- Avoid repeated switching above rated breaking capacity.
- Never operate the contactor with arc shield removed. Replace the complete unit when contacts suffer severe ablation.
Mechanical Life Parameters of ABB AF16Z-30-10-21
The AF16Z shares identical mechanical construction with standard AF16. Official technical data:
✅ Mechanical endurance: 10 million operating cycles (10×10⁶ operații)
Test conditions: Tensiunea nominală de control, no-load switching, standard ambient temperature.
Supporting Key Parameters
- Maximum mechanical operating frequency: 3,600 operațiuni pe oră
Continuous high-frequency operation shall not exceed this limit to avoid accelerated mechanical wear.
- Reference electrical endurance (depends on load type, not equal to mechanical life)
AC-3 (400 V motor load): Aproximativ. 1,000,000 cicluri
AC-1 (sarcină rezistivă): Aproximativ. 1,600,000 cicluri
⚠️ Mechanical endurance represents the mechanical operating limit; service life in practical applications is normally determined by electrical erosion of contacts.
Observații suplimentare
- AF16Z only differs by its low-power electronic wide-range coil variant. Armature, linkage and contact mechanical structure are identical to standard AF16; mechanical endurance ratings remain unchanged.
- Actual mechanical endurance will decrease under harsh environments (praf greu, continuous vibration, temperatură ridicată).
- Definition of mechanical endurance: Operating cycles of contactor pull-in/drop-out driven by coil only, with no load connected to main circuit.