Contactor Schneider LC1E1801

Explicația codului modelului: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contact normal închis (1NC) ⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance. Key Specifications Main ...

  • Detalii despre produs

Explicația codului modelului: LC1E = TeSys E series contactor; 18 = rated 18A at 400V under AC-3 duty; 01 = built-in 1 contact normal închis (1NC)

⚠️ The LC1E series has been discontinued (production stopped in July 2020). The standard replacement model is LC1N1801, fully compatible in mounting, terminal layout and performance.

Specificații cheie

Contacte principale: 3P, 3NU

AC-3 (motor duty): 18A @ 400V; AC-1 (sarcină rezistivă): 25O

Motor rating: 7.5kW @ 380/400V; 4kW @ 220V; 9kW @ 440V

Tensiunea de izolație Ui: 690V; Tensiune de rezistență la impuls Uimp: 6kV

Contact auxiliar: 1NC (În mod normal închis)

Montare: DIN rail / base plate screw mounting

Dimensiuni de gabarit: W45mm × H74mm × D80mm, net weight ≈0.3kg

Clasa de protectie: IP20; Temperatura de functionare: -5~+55℃; No derating up to 3000m altitude

Durata de viata mecanica: 10 milioane de operațiuni; Durata de viata electrica AC-3: 1.2 milioane de operațiuni; Frecvența maximă de funcționare: 1800 cicluri/oră

Coil suffix definitions (complete model number)

LC1E1801B5: AC24V, 50Hz

LC1E1801F5: AC110V, 50Hz

LC1E1801M5: AC220V, 50Hz (most common in China)

LC1E1801Q5: AC380V, 50Hz

Sufix 7 = 50/60Hz universal; sufix 6 = 60Hz only

Consumul de energie al bobinei (M5 220V example)

Inrush VA: 95VA; Sealed holding VA: 8.5VA; Coil heat dissipation: 2~3W

Pick-up voltage: 0.85~1.1Uc; Tensiunea de întrerupere: 0.3~0.6Uc

Cuplul de strângere & ecartamentul firului

Torque for main circuit and control circuit terminals: 1.2 N·m

Sârmă solidă: 1.5~6 mm²; Sârmă toronată (cu manta): 1~4mm²

Matching selection reference

Matching thermal overload relay: LRD07 / LRN07 (current range suitable for 18A)

Accesorii: LA1EN auxiliary contact block, LA9D coil surge suppressor, mechanical interlock block

Alternativă internă: CJX2-1801 (similar outline, pay attention to mounting hole and marking differences)

Ghid de depanare

  1. Coil energized but no pull-in: Check if coil voltage is within 0.85~1.1Uc; inspect broken coil wire and loose terminals
  2. Pulled in but main circuit no continuity: Eroziunea principală de contact, contact welding, cabluri libere
  3. Buzzing / chattering: Subtensiune, large harmonic distortion, dust accumulated on core faces
  4. Failed to drop out after power-off: Welded main contacts, core stuck by oil and dirt

Detailed Installation Procedure for Schneider LC1E1801 Contactor

⚠️ Safety precondition: Operated by qualified electricians; cut off all power supply and verify zero voltage before installation. LC1E1801: 3P main contacts with built-in 1NC auxiliary contact. Marcaj terminal: Main circuit L1/L2/L3 (line side, incoming), T1/T2/T3 (partea de sarcină, outgoing); Coil A1, A2; Contact auxiliar: 95, 96 (1NC)

  1. Pregătirea înainte de instalare
  2. Verificați tensiunea bobinei: LC1E1801M5=AC220V, Q5=AC380V, F5=AC110V. Coil rated voltage must match control circuit voltage to avoid coil burnout.
  3. Inspecție vizuală: No shell cracks, intact terminals, armature moves freely without jamming when pressed manually.
  4. Instrumente: 2 șurubelniță Phillips, dispozitiv de dezimbrare, multimetrul, cheie dinamometrică; 35mm standard DIN rail or mounting base plate.
  5. Wire specification

Main circuit solid wire: 1.5~6mm²; Sârmă toronată cu manșon: 1~4mm²

Circuit de control (A1/A2, contacte auxiliare): 0.75~1.5mm²

Cuplul de strângere: 1.2 N·m (avoid over-tightening to prevent thread stripping, or loose connection causing overheating)

  1. Environmental check: Cabinet temperature -5℃~+55℃, keep away from dust, moisture and oil. Mount vertically upright. Do NOT install upside down or horizontally.
  2. Fixing (2 methods: DIN rail / base plate screw mounting)

Metodă 1: 35mm Montare pe șină DIN (preferat)

  1. The contactor has upper hooks and a spring locking clip at the bottom.
  2. Hook the upper notch onto the top edge of the DIN rail first.
  3. Press the bottom of the contactor down until you hear a click, the bottom clip locks onto the rail.
  4. Shake lightly to confirm firm fixation. Îndepărtarea: Use a flat screwdriver to pry down the bottom clip and pull out the contactor.

Metodă 2: Screw mounting on insulated base plate (no rail)

  1. Mark and drill holes on the insulated plate according to the rear mounting holes (for M4 screws).
  2. Insert screws diagonally, pre-tighten, then torque evenly in diagonal sequence; do not force one side to avoid casing deformation.
  3. Accessory Fitting (Opțional: LA1EN auxiliary block, mechanical interlock etc.)
  4. Top auxiliary contact block: Align with the slots on top of contactor, push vertically down until latched.
  5. Thermal relay LRD/LRN: Clip directly underneath the contactor, align positioning slots; the linkage will engage automatically.
  6. Surge suppressor LA9D: Clip beside coil terminals A1/A2, absorbs back EMF to protect PLC output points.
  7. Wiring Sequence (Main circuit → Auxiliary contacts → Coil control circuit)

Standard routing: Line side on top, load side on bottom. L1/L2/L3 on top for three-phase supply; T1/T2/T3 at bottom for load (motor).

  1. Cablajul circuitului principal

Strip insulation 5~6mm, avoid loose copper strands; ferrules are mandatory for stranded wire.

Keep phase sequence L1→T1, L2 → T2, L3→T3 as per drawing.

Torque screws to 1.2N·m; only one conductor per terminal.

  1. Built-in auxiliary contact (95-96, NC)

Terminale 95-96: Conductive when coil de-energized, open when contactor pulls in. Usually used in stop circuit or fault feedback for motor control.

If NO contact is required, add LA1EN auxiliary block.

  1. Coil A1, A2 (circuit de control)

A1 and A2 have no polarity for AC. For AC220V: one to live, one to neutral; for AC380V: connect to two different phases.

Wire in series with start/stop pushbuttons, thermal relay NC contact or PLC outputs.

Route control wires separately from power cables to reduce interference.

Terminal summary:

L1/L2/L3 (Supply In), T1/T2/T3 (Load Out), A1 A2 (Bobina), 95-96 (Built-in 1NC)

  1. Inspecție înainte de pornire
  2. Verificare vizuală: All terminals tightened, no exposed copper, no short circuit risk, no loose strands touching adjacent terminals.
  3. Continuity test with multimeter:

De-energized state: No continuity between L-T; 95-96 auxiliary contact is conductive.

Manually press armature to simulate pull-in: L-T becomes conductive, 95-96 opens.

  1. Double-check coil voltage; separate power supply for main circuit and control circuit.
  2. Punerea în funcțiune
  3. Energize control circuit only, keep main power off: Press start button, contactor should pull-in smoothly without chattering or buzzing; release stop button for reliable drop-out.

Pălăvrăgeală: Tensiune de alimentare scăzută, loose wiring or dirty core surfaces.

  1. After control circuit test passes, energize main circuit and run on load.
  2. Temperature check after 10min running: No obvious overheating at terminals (temperature rise indicates poor connection).
  3. Note de instalare & Prohibitions
  4. Keep minimum clearance ≥10mm between contactor and fuse / MCB for heat dissipation.
  5. Minimum spacing ≥5mm between multiple contactors; increase spacing for high ambient temperature.
  6. Do not plug or remove auxiliary blocks when energized.
  7. Do not trap wire insulation inside terminal clamps; copper must be fully clamped.
  8. LC1E discontinued, spare replacement: LC1N1801, same mounting size and terminal definition.
  9. Common Installation Faults

No pull-in after energized: Wrong A1/A2 voltage, broken control wire or open button circuit

Buzzing when pulled in: Subtensiune, dust or rust on magnetic core faces

Cannot drop out after power cut: Welded main contacts or core jammed by oil

Schneider Easy TeSys E (LC1E / Televizoare EasyPact) Series Full List

Notă importantă: LC1E series fully discontinued in July 2020. Înlocuire directă: LC1N series, identical mounting dimensions and terminal layout.

Model rule: LC1E + current code + auxiliary contact code (10=1NU; 01= 1 NC) + coil suffix

Coil suffix description:

B5=AC24V 50Hz; F5=AC110V 50Hz; M5=AC220V 50Hz; Q5=AC380V 50Hz

B7/F7/M7/Q7=50/60Hz universal; BD=DC24V; 6=60Hz only

  1. 3P LC1E Contactors (AC-3 @400V)
Model de bazăAC-3 CurrentMotor Rating @400VBuilt-in Auxiliary Contact
LC1E06106O2.2kW1NU
LC1E06016O2.2kW1NC
LC1E09109O4kW1NU
LC1E09019O4kW1NC
LC1E121012O5.5kW1NU
LC1E120112O5.5kW1NC
LC1E181018O7.5kW1NU
LC1E180118O7.5kW1NC (your referenced model)
LC1E251025O11kW1NU
LC1E250125O11kW1NC
LC1E321032O15kW1NU
LC1E320132O15kW1NC
LC1E381038O18.5kW1NU
LC1E380138O18.5kW1NC
LC1E401140O18.5kW1NU+1NC
LC1E501150O22kW1NU+1NC
LC1E651165O30kW1NU+1NC
LC1E801180O37kW1NU+1NC
LC1E951195O45kW1NU+1NC
LC1E120120O55kWFără încorporat, add auxiliary block separately
LC1E160160O75kWFără încorporat, add auxiliary block separately
LC1E200200O90kWFără încorporat, add auxiliary block separately
LC1E300300O160kWFără încorporat, add auxiliary block separately

Example complete model: LC1E1801M7 = 18A, 1NC, AC220V 50/60Hz universal

  1. Matching LRE Thermal Overload Relays (plug-on fit for LC1E)

LRE01N~LRE35N (for 06~38A); LRE322N~LRE365N (for 40~300A)

LRE01N: 0.1~0.16A

LRE02N: 0.16~0.25A

LRE03N: 0.25~0.4A

LRE04N: 0.4~0.63A

LRE05N: 0.63~1A

LRE06N: 1~1,6A

LRE07N: 1.6~2,5A

LRE08N: 2.5~4A

LRE09N: 4~6A

LRE10N: 6~10A

LRE12N: 10~16A

LRE14N: 16~24A

LRE16N: 24~36A

LRE21N: 28~36A

LRE22N: 36~48A

LRE322N: 55~70A

LRE323N: 63~80A

LRE353N: 80~104A

LRE355N: 104~135A

LRE365N: 130~165A

  1. E-series Accessories
  2. LA1EN: Top-mounted auxiliary contact block (1NU / 1NC, stackable)
  3. LAEM1: Mechanical interlock module (for two contactor interlocking)
  4. LA9D: Coil surge suppressor (Rețeaua RC / varistor, PLC output protection)
  5. LAEB1N / LAEB3N: Thermal relay independent base (when not mounted under contactor)
  6. LA1EBN: Timed auxiliary contact block (la întârziere / întârziere la oprire)
  7. 2P / 4P LC1E (single phase, iluminat & sarcină rezistivă, AC-1 duty)

LC1E0920: 2Q 9A

LC1E2520: 2P 25A

LC1E0940: 4Q 9A

LC1E2540: 4P 25A

LC1E4040: 4P 40A

4P versions commonly used for HVAC, lighting and heating resistive loads

  1. Cross Reference Table
Old LC1E ModelDirect Replacement LC1N
LC1E0601/0610LC1N0601 / LC1N0610
LC1E0901/0910LC1N0901 / LC1N0910
LC1E1201/1210LC1N1201 / LC1N1210
LC1E1801/1810LC1N1801 / LC1N1810
LC1E2501/2510LC1N2501 / LC1N2510
LC1E3201/3210LC1N3201 / LC1N3210
LC1E3801/3810LC1N3801 / LC1N3810
LC1E40~95LC1N40~95