ABB AX09-30-10-80 Contactor

The AX09-30-10-80 is a general-purpose 3-pole AC contactor of ABB AX series, the official successor to the classic A9 contactor from the former A series. It is designed for controlling low-power loads in general industrial applications, mainly used for direct start and stop of three-phase asynchronous motors, as well as switching of AC distribution circuits, ...

  • Detalii despre produs

The AX09-30-10-80 is a general-purpose 3-contactor AC poli de ABB AX series, the official successor to the classic A9 contactor from the former A series. It is designed for controlling low-power loads in general industrial applications, mainly used for direct start and stop of three-phase asynchronous motors, as well as switching of AC distribution circuits, inductive and resistive loads.

Equipped with a conventional AC coil, this contactor features compact structure and small footprint. It supports mounting on standard 35 mm DIN rails, and offers long mechanical service life, high operating frequency and excellent environmental adaptability. It is widely applied in building HVAC systems, light automation systems, OEM equipment assembly, municipal power distribution and other fields.

  1. Interpretarea Codului Modelului

Model complet: AX09-30-10-80

  1. TOPOR: Cod de serie, representing AX series general-purpose AC contactors (replacement for legacy A series).
  2. 09: Rated current class. Rated operational current is 9 A under utilization category AC-3 at 400 V.
  3. 30: Main contact configuration. 3 normally open main contacts with no normally closed main contacts (the first digit = number of main poles; the second digit = number of normally closed main contacts).
  4. 10: Configurarea contactelor auxiliare. 1 normally open auxiliary contact with no normally closed auxiliary contacts (the first digit = number of normally open auxiliary contacts; the second digit = number of normally closed auxiliary contacts).
  5. 80: Coil code, corresponding to standard AC coil: 220-230 V și 50 Hz / 230-240 V și 60 Hz.
  6. Parametrii tehnici de bază

3.1 Parametrii circuitului principal

ArticolCaietul de sarcini
Polonii & Configurare contact3P, 3 Normally Open main contacts
Curent termic convențional (Ith)24 O (Ambient temperature ≤ 40 ℃)
Curent nominal de funcționare (AC-1)22 O (≤ 690 V și, ≤ 40 ℃); 18 O (≤ 70 ℃)
Curent nominal de funcționare (AC-3)9 O (≤ 440 V și, ≤ 55 ℃); 7 O (≤ 690 V și, ≤ 55 ℃)
Maximum Rated Operational Voltage (Ue)690 V și
Rated Control Power (AC-3)4 kW @ 400 V; 5.5 kW @ 690 V
Capacitate nominală de rupere (AC-3)8 × Ie
Tensiune nominală de rezistență la impuls (Ump)6 kV
Categoria de supratensiuneCategory III
Conexiune la circuitul principalConexiune terminală cu șurub, suitable for solid/stranded copper conductors
Torque for Main Terminals1.2 ~ 1.5 N·m

3.2 Parametrii circuitului de control

ArticolCaietul de sarcini
Tensiune nominală a bobinei (Uc)220~230 V AC 50 Hz; 230~240 V AC 60 Hz
Gama de tensiune de preluare0.85 Uc ~ 1.1 Uc
Interval de tensiune de întrerupere0.2 Uc ~ 0.75 Uc
Tip bobinăConventional AC excitation coil
Standard Auxiliary Contact1 NU, compatible with AC-15 / DC-13 control circuits
Rated Capacity of Auxiliary ContactAC-15: 10 O / 220 V; DC-13: 0.55 O / 220 V
Conexiunea circuitului de controlBorne cu șuruburi

3.3 Mecanic & Parametrii de mediu

ArticolCaietul de sarcini
Dimensiuni generale (L × H × D)44 mm × 74 mm × 74 mm
Greutate netăAproximativ. 0.326 kg
Clasa de protectieIP20 (corpul principal)
Temperatura ambiantă de funcționare-25 ℃ ~ +55 ℃ (Full rating within 55 ℃; current derating required at 70 ℃)
Installation AltitudeNo current derating up to 3000 m
Metoda de montareStandard 35 mm Montare pe șină DIN; vertical screw mounting available
CertificariIEC 60947-4-1, CCC, CE, UL, RoHS

3.4 Durata de viață & Parametri de performanță

ArticolCaietul de sarcini
Viața mecanică10,000,000 cicluri de operare
Viața electrică (Sarcina AC-3)1,000,000 cicluri de operare
Frecvența maximă de operare1200 cycles per hour
Pick-up Time7 ~ 21 Domnișoară
Drop-out Time4 ~ 11 Domnișoară
  1. Modele alternative & Cross-Series Reference

4.1 ABB Equivalent Replacements

  1. Replacement for Discontinued Models: Direct replacement for legacy A series A9-30-10. Fully compatible with original mounting holes and rail dimensions, with upgraded electrical life and overall reliability.
  2. Same Current Rating with Different Coils:

AX09-30-10-81: 24 V și 50/60 bobina Hz

AX09-30-10-84: 110 V și 50 Hz / 110~120 V 60 bobina Hz

AX09-30-01-80: Same main circuit, fitted with 1 Contact auxiliar NC

  1. Higher Current Models in the Same Series: AX12-30-10-80 (12 O), AX18-30-10-80 (18 O). Identical mounting width for direct replacement and capacity upgrade.

4.2 Equivalent Products from Other Brands

Schneider Electric: LC1D09M7C

Siemens: 3RT6015-1AN21

Chint: NXC-09 (220 bobina V)

> Nota: All cross-brand models support 35 mm DIN rail mounting for direct replacement. Please verify auxiliary contact configuration and coil voltage before installation.

  1. Full List of AX Series 3-Pole Contactors (220 V Coil)
ModelCurent nominal (AC-3 @ 400 V)Corresponding Motor Power @ 400 VStandard Auxiliary Contacts
AX09-30-10-809 O4 kW1 NU
AX12-30-10-8012 O5.5 kW1 NU
AX18-30-10-8018 O7.5 kW1 NU
AX25-30-10-8025 O11 kW1 NU
AX32-30-10-8032 O15 kW1 NU
AX40-30-10-8040 O18.5 kW1 NU
AX50-30-11-8050 O22 kW1 NU + 1 NC
AX65-30-11-8065 O30 kW1 NU + 1 NC
AX80-30-11-8080 O37 kW1 NU + 1 NC
AX95-30-11-8095 O45 kW1 NU + 1 NC

Common Accessories

Releu termic de suprasarcina: TA25DU series (de ex. TA25DU-9M). Direct plug-in bottom mounting for motor overload protection.

Blocuri de contact auxiliare: CA5X series front-mounted modules (CA5X-10E, CA5X-01E, CA5X-22E), extensibil până la 4 pairs of auxiliary contacts.

Suprimator de supratensiune: RV5X series, absorbs switching overvoltage of coils to protect PLC control circuits.

Interblocare mecanică: VB5X series, provides mechanical interlock for forward/reverse operation of two contactors.

Terminal Shroud: Improves protection level and prevents accidental contact.

  1. Domeniul de aplicare & Operating Limits

6.1 Aplicații tipice

  1. Controlul motorului mic: Direct start/stop of three-phase asynchronous motors such as small fans, pompe de apa, transportoare, roller table motors and mini compressors, suitable for loads up to 4 kW.
  2. Clădire & Sisteme HVAC: Control of terminal units of central air conditioning, fresh air units, fire exhaust fans, water supply & drainage pumps and fire dampers. It acts as a key actuator for power distribution circuits in building automation.
  3. Echipament OEM: Power circuit control for packaging machinery, utilaje textile, mașini-unelte mici, food processing equipment and other automated machinery. The compact size saves cabinet space.
  4. Distribuția energiei & Controlul Iluminării: Remote switching of high-capacity lighting circuits and small distribution feeders; switching of low-capacity capacitor banks in low-voltage reactive power compensation cabinets.
  5. Automation Logic Control: Acts as a power amplifier for PLC outputs to drive solenoid valves, indicator lights and other small actuators.

6.2 Cerințe de mediu

Install indoors inside switchgear or control boxes. Outdoor exposure to rain and direct sunlight is prohibited.

Pollution level shall not exceed Class 3; no highly corrosive gas, explosive gas or conductive dust present.

No severe impact or vibration on mounting surface; vibration acceleration ≤ 20 m/s².

Current derating is required when installation altitude exceeds 3000 m or ambient temperature exceeds 55 ℃, refer to official manual for calculation.

  1. Troubleshooting Matrix
Fenomen de eroareCauza de bazăSoluții
Contactor fails to close with no sound1. Fără alimentare, loose or broken wiring in control circuit1. Cut off power and perform safety check; inspect wiring at terminals A1/A2 and re-measure coil voltage
2. Burnt or broken coil2. Test coil resistance with multimeter; replace coil or complete unit if open circuit occurs
3. Armature mechanical jam or foreign obstruction3. Manually operate armature after power-off, clean dust and foreign matters on core pole faces
4. Supply voltage far below rated value4. Adjust supply voltage to rated range and eliminate line voltage drop
Continuous buzzing noise after closure1. Oil and dust on core pole faces causing poor contact1. Dismantle core after power-off and clean oil & dirt on pole faces
2. Broken or detached shading coil2. Replace core or complete unit if shading coil is damaged
3. Insufficient suction due to low supply voltage3. Increase supply voltage to rated range
Abnormal overheating at main terminals / contacte1. Loose terminal screws leading to high contact resistance1. Retighten terminals to specified torque after power-off
2. Continuous overload with current exceeding rated value2. Measure load current, check model selection and replace with higher-rated model if necessary
3. Contact ablation and poor conduction3. Polish slightly ablated contacts; replace complete unit for severe damage
Abnormal signal from auxiliary contacts, no feedback to PLC1. Ablation or poor contact of auxiliary contacts1. Test on-off performance of auxiliary contacts after power-off and replace faulty blocks
2. Loose or broken cables2. Inspect wiring and PLC input circuit to fix line faults
3. Improper installation of auxiliary contact block3. Reinstall auxiliary contact block and ensure firm connection
Severe coil overheating, burning smell or smoke1. Supply voltage exceeds coil rating1. Opriți imediat alimentarea, verify supply voltage and rule out wrong high-voltage connection
2. Coil inter-turn short circuit2. Măsurați rezistența bobinei; replace coil if inter-turn short circuit is confirmed
3. Long-term operation under undervoltage condition with excessive current3. Maintain supply voltage within rated range and avoid prolonged undervoltage operation
Failure to open or slow release after power cut1. Adhesion caused by oil on core pole faces1. Clean oil on core pole faces and check residual magnetism
2. Welded main contacts2. Inspect main contacts after power-off; replace contacts or complete unit if welding occurs
3. Fatigue failure of return spring3. Replace return spring or complete contactor