ABB CC-U-STDR-1SVR040010R0000 - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

ABB CC-U-STDR-1SVR040010R0000 - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

electric/

ABB CC-U-STDR-1SVR040010R0000

Model Code Explanation Model Segment Description CC Series code for analog signal converters (Conversion Controller) U Universal type, compatible with conversion of various standard signals STD Standard signal input. Supports 0-20mA/4-20mA/0-1V/1-5V/0-10V/±10V, etc. R Equipped with relay output, differentiated from STD models without relay output 1SVR040010R0000 Official order number, unique identification code ABB Brand logo ABB ...

  • Detalii despre produs

Codul modelului Explicația

Segmentul de modelDescriere
CCSeries code for analog signal converters (Conversion Controller)
UUniversal type, compatible with conversion of various standard signals
STDStandard signal input. Supports 0-20mA/4-20mA/0-1V/1-5V/0-10V/±10V, etc.
REquipped with relay output, differentiated from STD models without relay output
1SVR040010R0000Official order number, unique identification code
ABBLogo-ul mărcii

ABB CC-U-STDR-1SVR040010R0000-ABB Technical Manual The CC-U/STDR is a universal analog signal converter of ABB CC series. It features 2-channel threshold relay outputs and triple electrical isolation, designed for industrial signal conversion and control.

  1. Specificatii tehnice principale
CategorieSpecificații
General Information• Product Type: Universal Signal Converter (with relay output)
• Status: Întrerupt, no direct replacement model
• Origin: Germania
• Greutate: 0.142kg
Alimentare electrică• Rated Voltage: 24-48VDC / 24VAC 50/60Hz
• Power Consumption: ≤5W
Input Signal 7 standard signal ranges: 0-20mA/4-20mA/0-1V/1-5V/0-10V/±10V
• Input Impedance: ≤250Ω for current input; ≥1MΩ for voltage input
Semnal de ieșire• 2-channel SPDT relay contacts
• Independently adjustable threshold and hysteresis for each channel
• Contact Rating: AC 250V/5A, DC 30V/5A
Precizie & Performanţă• Repeat Accuracy: ±0,5% FS (Full Scale)
• Response Time: 10Domnișoară
• Temperature Drift: ≤0.05%/°C
Izolație electrică• Triple isolation: Isolation between input, output and power supply
• Isolation Voltage: ≥2.5kV
Parametrii de mediu• Operating Temperature: -20°C ~ +60°C (Temperatura de depozitare: -40°C ~ +80°C)
• Protection Class: IP20 (Panoul frontal)
• Mounting: 35mm Montare pe șină DIN
Dimensiuni• L × W × H: 120mm × 22.5mm × 105mm
• Mounting Depth: 120mm
  1. Lista completă a modelelor (CC-U Series)
ModelComanda nr.Tip de intrareTip ieșireAlimentare electricăObservații
CC-U/STD1SVR040000R1700Standard SignalAnalog Signal24-48VDC/24VACTip de bază, no relay output
CC-U/STD1SVR040001R0400Standard SignalAnalog Signal110-240VAC/100-300VDCHigh voltage power supply type
CC-U/STDR1SVR040010R0000Standard Signal2-channel Relay24-48VDC/24VACThis model with relay output
CC-U/STDR1SVR040011R2500Standard Signal2-channel Relay110-240VAC/100-300VDCHigh voltage power supply type
CC-U/RTD1SVR040002R0000RTD Temperature SensorAnalog Signal24-48VDC/24VACRTD input type
CC-U/RTDR1SVR040003R0000RTD Temperature Sensor2-channel Relay24-48VDC/24VACRTD input + ieșire releu
CC-U/TC1SVR040005R0000TermocupluAnalog Signal110-240VAC/100-300VDCThermocouple input type
CC-U/TC1SVR040006R0000TermocupluAnalog Signal24-48VDC/24VACThermocouple input type
CC-U/I1SVR040007R0000Current SignalAnalog Signal24-48VDC/24VACCurrent signal conversion type
CC-U/V1SVR040008R0000Voltage SignalAnalog Signal24-48VDC/24VACVoltage signal conversion type
  1. Cross-Model & Replacement Reference

4.1 Replacement for Discontinued Products

Model originalStareRecomandare de înlocuireMotivul înlocuirii
CC-U/STDR-1SVR040010R0000Întrerupt, no direct equivalent1. Upgrade to new ABB model: TTH300 Series• TTH300: New-generation ABB signal converter with enhanced functions
2. Third-party replacement: Phoenix Contact MACX MCR-UI-UI-NC• MACX MCR: Standard industrial replacement with wide compatibility
3. Inlocuire functionala: WAGO 750-455• WAGO 750: Modular design with strong expandability

4.2 Cross-Brand Compatibility

Modelul ABBPhoenix ContactWAGOSiemensComparație de funcții
CC-U/STDRMACX MCR-UI-REL-NC750-4553RK1300• Support standard signal input
• 2-channel relay output
• Triple electrical isolation
• Response time ≤10ms
  1. Medii de aplicație & Cazuri industriale

5.1 Scenarii aplicabile

Automatizare industrială: Monitoring and control of analog signals on production lines, including conversion of pressure, temperature and flow signals

Controlul procesului: Standard signal processing for chemical, pharmaceutical and food industries

Managementul Energiei: Conversion of sensor signals in power systems for equipment monitoring and control

Automatizarea clădirilor: Signal processing for HVAC systems to ensure reliable signal management

Tratarea apei: Conversion of liquid level and flow signals for pump control and alarm systems

Metalurgie: Signal isolation and conversion in high-temperature environments to eliminate interference

5.2 Non-Recommended Scenarios

Intrinsically Safe Areas: No explosion-proof certification, not suitable for Zone 0/Zone 1 hazardous locations

High-Speed Signal Processing: 10ms response time, not applicable for microsecond-level control

Outdoor Installation: Clasa de protectie IP20, additional protective measures are required for outdoor use

5.3 Cazuri tipice de aplicare

Caz 1: Temperature Control of Chemical Reactor

Aplicație: Convert millivolt thermocouple signals to standard 4-20mA signals; set dual thresholds for high temperature alarm (85°C) and over-temperature shutdown (95°C)

Configurare: CC-U/STDR + Type K thermocouple adapter, 24Alimentare VDC

Avantaje: Triple isolation eliminates ground loop interference; dual relay outputs realize hierarchical control and improve operational safety

Caz 2: Pressure Monitoring for Building HVAC System

Aplicație: Convert 0-10V signals from pressure sensors to standard 4-20mA signals; set low pressure alarm (0.5bar) and high pressure alarm (3bar)

Configurare: CC-U/STDR, 24VAC power supply

Avantaje: Standardized signals facilitate centralized PLC monitoring; relay outputs directly control fan start/stop and reduce system costs

  1. Sfaturi de selecție & Quick Reference Rules

Selection Rhythm

The CC series includes U (Universal) și E (Economie);

STD for standard signals, R for relay output, check power supply carefully;

24/48V for low voltage, 110/240V for high voltage;

Triple isolation against interference, 10-millisecond response;

This series is discontinued, plan upgrade in advance.

Quick Reference Rules

  1. Identificarea modelului: CC-U/STDR = Universal type + Standard signal + Ieșire releu
  2. Order Number Distinction: 1SVR040010R0000 = 24-48V power supply; 1SVR040011R2500 = 110-240V power supply
  3. Avantajele de bază: Triple isolation, independently adjustable dual relays, 7 selectable input signals
  4. Status Reminder: All legacy CC-U series products are discontinued. Select ABB TTH300 series or third-party alternatives for new projects.
  5. Depanare & Întreţinere
Fenomen de eroareCauze posibileSoluții
Fără semnal de ieșire1. Power supply disconnected or abnormal voltage1. Check 24-48VDC/24VAC power supply
2. Incorrect DIP switch settings2. Reconfigure DIP switches (input type, output mode)
3. Input signal out of range3. Measure input signal and ensure it is within 0-20mA/0-10V range
Relay Fails to Actuate1. Threshold set too high/low1. Readjust threshold potentiometer
2. Excessively large hysteresis value2. Reduce hysteresis value
3. Damaged relay contacts3. Măsurați rezistența de contact; replace unit if contacts are damaged
Fluctuating Output Signal1. Interference on input signal1. Check shield wiring and add filter
2. Excessive power supply ripple2. Connect a 100渭F capacitor in parallel to power terminals
3. Poor contact of potentiometer3. Clean or replace the potentiometer
Loss of Isolation1. Wrong wiring across isolation zones1. Rewire strictly to separate input, output and power circuits
2. Equipment aging2. Replace with new device (select replacement model due to discontinuation)

Prev:

Lasă un răspuns

Lăsaţi un mesaj