Legacy MEC series, 22Cadrul AF, 3-element (3-phase phase-loss protection type). Direct plug-in fit for GMC-9/12/18/22 contactors. Classic LS small-power motor thermal relay. Model de înlocuire: MT-32/3H
✅ Specificații de bază
Clasa de excursie: Clasa 10A (protectie standard a motorului)
Contacte auxiliare: 1a1b (1NU + 1NC)
Funcții de protecție: suprasarcina, rotor blocat, 3-phase phase-loss protection (advantage of 3-element design)
Constructii: banda bimetalica, compensarea temperaturii, mecanism fără deplasare
Tensiunea nominală de izolație Ui: 690V
Modul de resetare: Resetare manuală (with TEST button)
Montaj independent: Optional bracket AZ-22H
📋 Full Current Range List for GTH-22/3
| Cod model | Setarea intervalului de curent |
| GTH-22/3 0.16 | 0.1~0.16A |
| GTH-22/3 0.21 | 0.16~0.25A |
| GTH-22/3 0.33 | 0.25~0.4A |
| GTH-22/3 0.5 | 0.4~0.63A |
| GTH-22/3 0.8 | 0.63~1A |
| GTH-22/3 1.3 | 1~1,6A |
| GTH-22/3 2.1 | 1.6~2,5A |
| GTH-22/3 3.3 | 2.5~4A |
| GTH-22/3 5 | 4~6A |
| GTH-22/3 6.5 | 5~8A |
| GTH-22/3 7.5 | 6~9A |
| GTH-22/3 8.5 | 7~10A |
| GTH-22/3 11 | 9~13A |
| GTH-22/3 15 | 12~18A |
| GTH-22/3 19 | 16~22A |
🔁 Informații de înlocuire
Factory upgraded replacement: MT-32/3H (identical current ratings, direct replacement for GTH-22/3)
Distincţie: GTH-22/2 is 2-element, without phase-loss protection, do not interchange
📌 Wiring Notes
Circuitul principal: 1/2/3 ÎN, 4/5/6 OUT, connected in series between contactor outlet and motor
Contacte auxiliare: 95-96 (NC, wired into contactor coil circuit); 97-98 (NU, pentru alarma de eroare)
Setarea curentă: Align dial pointer with motor full-load current (FLA)
- Definiția terminalului & Standard Start-Stop Wiring for GTH-22/3
Marcaje terminale:
Circuitul principal: 1, 3, 5 (incoming); 2, 4, 6 (outgoing), wired in series after contactor T1/T2/T3 and before motor
Contacte auxiliare:
95-96: NC normal închis (must be wired in contactor coil circuit; opens on overload to stop motor)
97-98: NU Deschis normal (for alarm lamp / PLC fault input)
Front panel buttons: TEST (simulated trip), RESET (resetare); GTH-22/3 is factory set to manual reset only, no auto-reset selector (different from some domestic thermal relays)
Standard Start-Stop Wiring Sequence (380V Motor)
- Circuit breaker → Contactor KM main contacts L1/L2/L3
- KM output T1/T2/T3 → GTH-22/3 terminals【1, 3, 5】
- GTH-22/3 terminals【2, 4, 6】→ Motor 3-phase terminals
- Circuit de control: Power supply → Stop button NC → 95 → 96 → Start button NO → KM coil A1/A2; KM auxiliary NO for latching
- Circuit de alarma: 97-98 in series with alarm lamp / releu intermediar, powered from control supply
Instalare plug-in: Snap directly onto the bottom of GMC-9/12/18/22 contactors. DIN rail independent mounting requires bracket AZ-22H.
✅ Offline Test Method (Oprire)
Use multimeter continuity mode:
Stare normală: 95-96 conducts; 97-98 deschide
Apăsați butonul TEST: 95-96 se deschide, 97-98 se inchide; release TEST, RESET button must be pressed to restore
- Tabel de depanare (GTH-22/3 3-element phase-loss protected type)
Precauție: GTH-22/3 is Class 10A. It protects against overload, locked rotor and phase loss ONLY. It cannot provide short-circuit protection. Short-circuit protection shall be implemented by fuse or circuit breaker.
| Simptom | Cauza de bază | Inspecţie & Remediu |
| Suprasarcina motorului / rotor blocat, thermal relay does not trip or protect | 1. Setting current too high2. Heating element burnt or internal solder joint open3. Mecanismul blocat, bimetallic strip deformed4. Wrong frame size (current range oversized) | 1. Align setting dial with motor nameplate rated current (FLA; +5%~10% allowed for frequent start)2. Measure continuity of main circuit phases 1-2, 3-4, 5-6 cu multimetru; replace if open3. Activate TEST button to verify contact switching; replace if TEST fails4. Confirm model is GTH-22/3 (3-element with phase-loss protection), not GTH-22/2 |
| Motor runs at normal load, nuisance tripping, trips immediately on startup | 1. Setting current too low2. Loose terminal connection, supraîncălzire (terminal heat triggers premature bimetallic action)3. High cabinet ambient temperature, mounted too close to hot contactor4. Long motor starting time (sarcină de inerție mare)5. 3-phase supply phase loss (GTH-22/3 trips on phase loss) | 1. Recheck motor rated current and adjust setting upwards2. Opriți, retighten all main circuit screws; inspect conductors for oxidation or discoloration3. Keep clear of heat sources, îmbunătățirea ventilației; increase setting by 5% if ambient >40℃4. For long-start loads, consider Class20 thermal relay5. Measure 3-phase supply voltage, check for missing phase or broken cable |
| După ce se împiedică, RESET button cannot reset the relay | 1. Internal trip mechanism jammed or damaged2. Bimetallic strip not cooled down (2~5 min cooling required; hot state prevents reset)3. Auxiliary contacts welded together | 1. Wait for cooling then retry reset; replace if still unable to reset after cooling2. Măsură 95-96 continuitate; replace if remains open after reset |
| Control circuit dead, contactor cannot pull in | 1. Thermal relay tripped, 95-96 open2. Loose or broken wiring on 95/963. Auxiliary contacts eroded and high resistance | 1. Reset relay first, then test continuity of 95-962. Re-terminate control wiring; replace relay if contacts are heavily burnt |
| Random tripping after running for a period, restarts after cooling | 1. Hidden motor overload, bearing seizure, excessive load2. Cablu subdimensionat, high voltage drop, terminal overheating3. Unbalanced 3-phase current | 1. Measure 3-phase running current with clamp meter, compare against setting value2. Inspect motor bearings, impeller and gearbox for binding3. If current imbalance >10%, investigate supply voltage and motor winding |
III. Special Notes for GTH-22/3
- 3-element (/3) ≠ 2-element (/2):GTH-22/3 has phase-loss protection; GTH-22/2 does not, cannot substitute
- Phase-loss protection principle: If one phase is lost, the other two phases draw elevated current, the two corresponding heating elements heat and bend the bimetallic strips to trigger trip. It is thermal accumulation, not instantaneous voltage detection.
- Conductor sizing: Main circuit conductors must be sized for rated current; thin wiring causes false tripping from self-heating.
- Avoid frequent TEST operation, which accelerates internal mechanism wear.
- Replacement model MT-32/3H shares identical terminal assignment and wiring logic, direct swap.
- Quick On-site Troubleshooting Sequence
- Isolate power → Visual inspection: urme de arsuri, burnt odor, overheated terminals
- Multimeter test: main circuit phase continuity, auxiliary contact normal state
- Activate TEST to confirm trip action and reset function
- Porniți, clamp meter test 3-phase running current, cross-check setting
- Measure 3-phase voltage, check phase loss and imbalance
- Rule out motor and mechanical load faults before confirming thermal relay failure
Overload Protection Principle of Bimetallic Thermal Releu de suprasarcină (GTH-22/3 type)
Principiul de bază: Current thermal effect + bimetallic strip thermal deformation, simulating motor thermal characteristics for delayed overload protection. It cannot provide instantaneous short-circuit protection.
- Componenta de bază: Banda Bimetalica
Two metal strips with different thermal expansion coefficients are clad together:
Active layer: higher expansion rate
Passive layer: lower expansion rate
At ambient temperature: plat, mechanism latched, 95-96 NC contact closed.
- Action Sequence on Overload
- Motor current flows through heating element, higher current generates more heat;
- Heat transfers to bimetallic strip;
- Differential expansion causes the strip to bend toward the low-expansion side;
- Sustained overcurrent accumulates bending displacement until trip threshold is reached;
- Mechanical latch releases: 95-96 Contactul NC se deschide, cutting contactor coil supply and stopping motor; 97-98 NO contact closes for fault signal.
Caracteristică: Caracteristica timp invers
Larger overload current → faster heating and shorter trip time. Mild overload requires long duration to trip, matching motor allowable short-time overload. For Class10A: trips within 4~10s at 10× setting current.
- Additional Phase-loss Protection Principle of GTH-22/3 (3-element)
Basic 2-element relays only monitor two phases.
GTH-22/3 has independent heating elements and bimetallic strips for all three phases:
When one supply phase is lost, the remaining two phases carry excess current, both heating elements bend and trigger accelerated trip.
Phase-loss protection is still thermal accumulation, not instantaneous voltage detection.
- Built-in Temperature Compensation (GTH series)
Internal compensation bimetallic strip offsets ambient temperature influence, preventing false tripping in hot cabinet or cold environment when current is normal.
- Reset Principle
După ce se împiedică, the bimetallic strip must cool and spring back to original shape.
GTH-22/3 is manual reset: after full cooling, press RESET to re-latch the mechanism and restore contact status.
- Limitări cheie (Field Critical)
✅ Protected conditions: suprasarcina sustinuta, rotor blocat, pierdere de fază, continuous excess current
Not protected: scurt-circuit (short-circuit current is too high; the relay will burn before the strip bends. Short-circuit protection via breaker/fuse)
Not protected: instantaneous inrush current (starting current is bypassed by inverse time delay)
LS (Legacy GTH + New MT Series) Thermal Relay ↔ Contactor Compatibility Chart
Note: Direct plug-in fit. Independent DIN rail mounting requires bracket (THE / UZ series). /3 = 3-element with phase-loss protection; /2 = 2-element without phase-loss protection.
- Legacy GTH Series (including GTH-22/3)
| Thermal Relay Model | Direct Plug-in Contactor | Observații |
| GTH-22/2, GTH-22/3 | GMC-9, GMC-12, GMC-18, GMC-22 | Max setting 22A; bracket AZ-22H for standalone mounting |
| GTH-40/2, GTH-40/3 | GMC-32, GMC-40 | Max setting 34A |
| GTH-85/2, GTH-85/3 | GMC-50, GMC-65, GMC-75, GMC-85 | Max setting 74A |
| GTH-100/2, GTH-100/3 | GMC-100, GMC-125 | Max setting 107A |
| GTH-150/2, GTH-150/3 | GMC-150 | Max setting 130A |
| GTH-220/2, GTH-220/3 | GMC-180, GMC-220 | Max setting 200A |
| GTH-400/2, GTH-400/3 | GMC-300, GMC-400 | Max setting 320A |
- New MT Series (GTH Replacement, Metasol)
| Thermal Relay Model | Contactor compatibil | Replaces Legacy | Standalone Bracket |
| MT-32/3H | MC-9b, MC-12b, MC-18b, MC-22b, MC-32a, MC-40a | GTH-22/3, GTH-40/3 | UZ-32 |
| MT-63/3H | MC-50a, MC-65a | GTH-85 | UZ-63 |
| MT-95/3H | MC-75a, MC-85a, MC-100a | GTH-100 | UZ-95 |
| MT-125/3H | MC-125a | GTH-150 | UZ-125 |
| MT-200/3H | MC-150a, MC-185a, MC-220a | GTH-220 | UZ-200 |
III. Common Pitfalls for GTH-22/3
- GTH-22/3 only plugs into GMC-9/12/18/22, cannot directly fit GMC32 and above contactors.
- Current rating = adjustable range, not contactor rating. Contactor rated current must be ≥ motor rated current.
- Calea de upgrade: GTH-22/3 → MT-32/3H. Same terminal definition and contact logic, but new contactors are MC series instead of old GMC.
- Bracket incompatibility: AZ-22H for old GTH; UZ-32 for new MT-32, cannot interchange.
- Regula de selecție rapidă
Motor rated current ≤22A: Old scheme GMC-9~~22 + GTH-22/3; New scheme MC-9b~~22b + MT-32/3H
Setting Current Adjustment Procedure for LS GTH-22/3 Thermal Relay
- Setting Principle
Setting Current = Motor Nameplate Full-Load Current (FLA)
Continuous-duty standard motor: set exactly to nameplate FLA
Ventilator / pump general loads: set to nameplate value
Pornire frecventă, heavy-start or long acceleration loads: +5% ~ +10% of FLA, do not exceed 1.1×
Intermittent short-cycle motor: can reduce slightly, minimum ≥0.9× FLA
Nota: The dial scale of GTH-22/3 is adjustable range, not fixed value. The value aligned by the pointer is the setpoint.
- Adjustment Steps (GTH-22/3)
- Power off for safety (always power off before adjustment to avoid live terminal exposure)
- Open the front protective cover
- Rotate the central adjustment dial with indicator pointer
- Align pointer to target setting current
- Refit cover
- Porniți, test run, verify 3-phase current with clamp meter
Exemplu:
Motor nameplate FLA = 5.2A → Select GTH-22/3 5 (4~6A range), align pointer to 5.2.
III. On-site Verification (Critic)
După ajustare, run motor at full load and measure 3-phase current with clamp meter:
Measured stable current ≈ setting value: normal
Continuous running current far below setting: protection is loose, overload may not trip
Frequent tripping near rated current: check setting, suprasarcina motorului, hot terminals or high ambient temperature
- Concepții greșite comune
- Set by contactor rated current: wrong, always reference motor nameplate
- Turn dial to maximum end: removes effective overload protection
- Increase setting heavily to accommodate starting inrush: inverse time characteristic is designed to withstand starting surge, no large over-set required
- Adjust setting to fix 3-phase imbalance: imbalance must be traced to supply, cable or motor winding, not thermal relay setting
- Temperature Compensation Impact
GTH has built-in temperature compensation. If cabinet ambient temperature is persistently above 40℃, relay trips easier at same current; o 5% upward setting is acceptable. If ambient <0℃, setting can be reduced slightly.
- Supplementary Notes for GTH-22/3
TEST button only simulates trip, it does not change the current setting value
Adjustment only changes overload trip threshold, phase-loss protection function remains active