ESB25-22N-06
- ESB: ABB modular building installation contactor serie
- 25: Rated operational current AC-1/AC-7a of main contacts = 25A
- 22: Configurarea contactului: 2 Deschis normal (NU) + 2 În mod normal închis (NC) (4-pol)
- N: Silent AC/DC universal coil (no buzzing sound, built-in overvoltage absorption circuit)
- 06: Tensiunea de control al bobinei: AC/DC 230~240V
Original manufacturer part number: 1SAE231111R0622
Domestic order number: 10228794
- Specificații electrice de bază
2.1 Main Circuit Load Ratings (400VAC/230VAC)
| Categoria de utilizare | Rated Current Ie | Single-phase 230V Load Power |
| AC-1/AC-7a (Resistive: Iluminat, Încălzire) | 25O | 5.8kW |
| AC-3/AC-7b (Sarcini inductive: Motoare, Pompe) | NU contacte: 9O / NC contacts: 6O | 1.3kW |
Tensiunea nominală de izolație Ui: 500V
Tensiune nominală de rezistență la impuls Uimp: 6kV
Maximum main circuit voltage: 400V și / 220În DC
2.2 Control Coil
Tensiunea de control: AC/DC 230~240V (universal for AC & DC)
Applicable frequency: 50/60/400Hz
Caracteristici: Silent operation, consum redus de energie, suprimarea supratensiunii încorporată, no additional varistor required
2.3Mecanic & Rezistenta electrica
Rezistenta mecanica: 1,000,000 operațiuni
Electrical endurance for AC-1 resistive loads: 130,000 operațiuni
Electrical endurance for AC-3 motor loads: 500,000 operațiuni
- Dimensiuni mecanice & Instalare
Metoda de montare: Snap-on mounting on standard 35mm DIN rail
Lățimea modulului: 2 module (36mm)
Dimensiuni de gabarit: W36mm × H85mm × D65mm
Net weight: 0.245kg
Clasa de protectie: IP20 (for indoor cabinet use only)
Încetarea: Borne cu șuruburi, tool-free auxiliary contact expansion interface
- Caracteristicile produsului
- Silent Coil: Universal for AC and DC, suitable for noise-sensitive areas such as machine rooms, dormitories and hotels
- Integrated Overvoltage Protection: Built-in absorption circuit on coil to suppress switching surges
- Wide Load Compatibility: Supports lighting, incalzire prin pardoseala, fani, water pumps and small single-phase motors simultaneously
- Compact Modular Design: 2-module width to save cabinet space
- Equipped with 2NO and 2NC contacts, enabling synchronous control of two switch-on circuits and two switch-off circuits for flexible circuit design
- Scenarii tipice de aplicare
Clădiri comerciale: Public lighting, ventilatoare centrale de aer conditionat, floor heating modules
Hotels & apartments: Automatic control of room lighting, fresh air systems and water pumps
Machine & electrical rooms: Thermostatic equipment, load switching in power distribution cabinets
Light industrial applications: Switching of resistive loads ≤25A and single-phase motors ≤1.3kW
- Optional Matching Accessories
- Module de contact auxiliare: EH04-11N (1NU+1NC), EH04-20N (2NU)
- Spacing heat dissipation baffles: ESB-DIS (for multiple units installed side-by-side in high-temperature environments)
- End cover plates: ESB-PLK24, ESB-SPK24
- Reference Alternative Models in the Same Series
24V AC/DC coil: ESB25-22N-01
4NO with 230V coil: ESB25-40N-06
4NC with 230V coil: ESB25-04N-06
Complete Model List of ABB ESB Silent Building Contactors
- Regula de codificare a modelului (ESBXX-XXN-XX)
- ESB: Silent AC/DC universal building contactor (suprimarea supratensiunii încorporată, buzz-free)
- First two XX digits: Rated AC-1 current rating: 16/20/25/40/63/100O
- Middle two XX digits: Main contact configuration (first = NO, second = NC)
11=1NO+1NC, 20=2NU, 02=2NC, 22=2NO+2NC, 40=4NO, 04=4NC
- N: Silent coil identifier
- Ultimele două cifre: Codul tensiunii bobinei (2 commonly used versions in domestic market)
01: AC/DC 24V
06: AC/DC 230~240V (mainstream for civil use; your model ESB25-22N-06 adopts this voltage)
07: AC/DC 400~415V (for industrial three-phase control)
- Basic Specifications by Current Rating
| Prefixul modelului | Rated AC-1 Current | Lățimea modulului | Applicable Loads |
| ESB16 | 16O | 1 modul (18mm) | Small lighting, small electrical appliances |
| ESB20 | 20O | 1 modul (18mm) | General lighting, fani |
| ESB25 | 25O | 2 module (36mm) | Floor heating, pompe de apa, motoare monofazate |
| ESB40 | 40O | 3 module (54mm) | High-power heating, three-phase lighting |
| ESB63 | 63O | 3 module (54mm) | Commercial central air conditioning, high-power loads |
| ESB100 | 100O | 6 module (108mm) | Main control for large buildings, heavy three-phase loads |
- Full Model List by Current Rating (Domestic common 01/06 Voltaj, including industrial 07 versiune)
3.1 ESB16 (16O, 1 modul)
Contact configurations: 11, 20, 02
ESB16-11N-01 / ESB16-11N-06 / ESB16-11N-07
ESB16-20N-01 / ESB16-20N-06 / ESB16-20N-07
ESB16-02N-01 / ESB16-02N-06 / ESB16-02N-07
3.2 ESB20 (20O, 1 modul)
Contact configurations: 11, 20, 02
ESB20-11N-01 / ESB20-11N-06 / ESB20-11N-07
ESB20-20N-01 / ESB20-20N-06 / ESB20-20N-07
ESB20-02N-01 / ESB20-02N-06 / ESB20-02N-07
3.3 ESB25 (25O, 2 module, your model belongs to this series)
Contact configurations: 20, 02, 22, 40, 04
ESB25-20N-01 / ESB25-20N-06 / ESB25-20N-07
ESB25-02N-01 / ESB25-02N-06 / ESB25-02N-07
ESB25-22N-01 / ESB25-22N-06 / ESB25-22N-07 (your model ESB25-22N-06)
ESB25-40N-01 / ESB25-40N-06 / ESB25-40N-07
ESB25-04N-01 / ESB25-04N-06 / ESB25-04N-07
3.4 ESB40 (40O, 3 module)
Contact configurations: 40, 04, 22
ESB40-40N-01 / ESB40-40N-06 / ESB40-40N-07
ESB40-04N-01 / ESB40-04N-06 / ESB40-04N-07
ESB40-22N-01 / ESB40-22N-06 / ESB40-22N-07
3.5 ESB63 (63O, 3 module)
Contact configurations: 40, 04
ESB63-40N-01 / ESB63-40N-06 / ESB63-40N-07
ESB63-04N-01 / ESB63-04N-06 / ESB63-04N-07
3.6 ESB100 (100O, 6 module)
Configurarea contactului: 40
ESB100-40N-01 / ESB100-40N-06 / ESB100-40N-07
- Manual Operation Version EN Series (Opțional, with manual toggle lever)
Same coding rule as ESB, prefixed with EN, de ex. EN20-22N-06, EN25-40N-06, for on-site manual switching and commissioning.
- Matching Accessory Part Numbers
- Module de contact auxiliare: EH04-11N (1NU+1NC), EH04-20N (2NU)
- Side-by-side heat dissipation baffles: ESB-DIS
- End cover plates: ESB-PLK24 (for 1/2-module models), ESB-PLK40/63 (for 3/6-module models)
- Side sealing plates: ESB-SPK24, ESB-SPK40/63
- Cross Reference of Common Domestic Order Numbers (06 version with 230V coil)
ESB16-22N-06: 1SBE111111R0622
ESB20-22N-06: 1SBE121111R0622
ESB25-22N-06: 1SAE231111R0622 (Comanda nr.: 10228794)
ESB25-40N-06: 1SAE231111R0640 (Comanda nr.: 10228796)
ESB40-40N-06: 1SAE341111R0640
ESB63-40N-06: 1SAE351111R0640
Official Mechanical Endurance Parameters of ABB ESB25-22N-06
Mechanical Durability: 1,000,000 operațiuni
Reference Supporting Electrical Endurance (Original Manufacturer Data for Same Model)
- Resistive loads AC-1 / AC-7a (Iluminat, Încălzire)
Deschis normal (NU) contacte: 130,000 operațiuni
În mod normal închis (NC) contacte: 50,000 operațiuni
- Motor loads AC-3 / AC-7b (Fani, Pompe de apă)
Deschis normal (NU) contacte: 500,000 operațiuni
În mod normal închis (NC) contacte: 340,000 operațiuni
Note suplimentare
- All models in ESB25 series (ESB25-20/02/22/40/04N-01/06/07) share a unified mechanical endurance of 1,000,000 operațiuni, unaffected by contact configuration or coil voltage.
- Mechanical endurance refers to pure mechanical actuation cycles with no load, only coil pull-in and drop-out; electrical endurance means the effective service life of contacts under rated load switching.
- Ambient operating temperature range: -25℃ ~ +55℃. Temperatures exceeding 55℃ will shorten electrical endurance, while mechanical endurance is barely affected by minor temperature fluctuations.
Translation Specification Note
- Industrial electrical standard terms comply with IEC international norms (NO/Nc, AC-1/AC-3, DIN rail, Ie, Ui, Uimp etc.)
- Marca, model, part numbers, order codes remain unchanged as original characters
- Tables, hierarchical titles, lists fully retain original document structure for engineering use
- Unit expressions follow international engineering writing habits (O, V, kW, mm, kg)
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare



















NH42-63-318x560.png)