Eaton thermal overload relay XTOG010BC1

The Eaton thermal overload relay XTOG010BC1 is a device specifically designed for motor protection, suitable for industrial control scenarios. The following is a key information summary based on search resources: Core Technical Parameters Current RangeSchneider-MCCB-NSX250F-4P-250AThe rated current adjustment range is 6–10A, suitable for motors matching this current interval. Protection Features Class 10 Protection: ...

  • Detalii despre produs

The Eaton thermal overload relay XTOG010BC1 is a device specifically designed for motor protection, suitable for industrial control scenarios. The following is a key information summary based on search resources:

  1. Parametrii tehnici de bază
  2. Current RangeSchneider-MCCB-NSX250F-4P-250A

The rated current adjustment range is 6–10A, suitable for motors matching this current interval.

  1. Protection Features

Clasă 10 Protection: In case of overload (de ex., motor stalling), it can quickly trigger tripping within 10 seconds to effectively prevent motor damage. Pret intreruptoare Schneider

Phase Loss Protection: Built-in phase fault detection function, compliant with IEC/EN 60947 standardele.

Environmental Compensation: Adopts a bimetallic thermal tripping mechanism, which can automatically compensate for environmental temperature changes (-25°C to 55°C) to avoid misoperation.

  1. Specificații electrice

Tensiune de izolație: 690V AC, certified by UL and CSA, suitable for the North American market.

Contacte auxiliare: Standard configuration includes 1 deschis în mod normal (NU) şi 1 în mod normal închis (NC) contact for signal feedback in the control circuit.

  1. Metoda de instalareÎntrerupătoarele de circuit CC din seria NB1-63DC de la Chint Preţ

Plug-in Design: Can be directly installed with Eaton XTCE series contactors (such as XTCE007B10, XTCE009B10), saving space and simplifying wiring.

IP20 Protection Level: Prevents foreign objects from entering, potrivite pentru medii industriale.

  1. Scenarii de aplicare

Controlul motorului: Widely used for overload protection of three-phase motors such as fans, pompe de apa, si compresoare, forming a complete motor control circuit in combination with contactors.

Automatizare industrială: Supports integration with PLC or other control systems, enabling remote monitoring and fault alarm through auxiliary contacts.

Pret relee termice de suprasarcina seria Chint NXR

III. Installation and Usage Key Points

  1. Type Selection and Matching

Select the corresponding specification of thermal overload relay according to the motor’s rated current, ensuring the current adjustment range covers 1.1–1.25 times the motor’s full-load current.

Must match the frame size of the contactor (de ex., XTOG010BC1 is suitable for XTCE 007B to XTCE015B series contactors).

Pret protector de supratensiune CHINT

  1. Wiring and Settings

Circuitul principal: Connect the three-phase main contacts of the relay in series with the motor’s power supply line.

Circuit de control: Auxiliary contacts need to be connected to the contactor coil circuit to cut off the motor power after tripping.

Current Setting: Adjust the current scale to the motor’s rated value via the front knob. It is recommended to set it at the lower-middle range of the adjustment range to improve sensitivity.

  1. Reset Modes

Manual Reset: After tripping, manually press the reset button, suitable for scenarios requiring manual fault confirmation.

Automatic Reset: Automatically restores when the temperature drops, suitable for systems allowing automatic restart.

  1. Market and Alternative Solutions
  2. Starea aprovizionării

As of 2025, XTOG010BC1 is still in stock with spot supply, priced at approximately 44–48 USD.

  1. Modele alternative

XTOD010BC1 in Eaton’s D-Line series may be an upgraded model, covering a wider current range (6–95A) and标配 auxiliary contacts. It is recommended to confirm through official channels.

  1. Certifications and Compliance

Complies with standards such as UL, CSA, IEC/EN 60947, suitable for North American and international markets.

  1. Probleme comune și întreținere
  2. Troubleshooting for Misoperation

Environmental Temperature: If the ambient temperature exceeds 55°C, it may cause the bimetallic strip to act prematurely. Strengthen heat dissipation or use with derating.

Current Setting: Check if the setting value is lower than the motor’s actual load. It is recommended to measure the motor current with an ammeter.

  1. Contact Maintenance

Regularly clean the surface of auxiliary contacts to prevent poor contact due to oxidation. Use contact cleaners if necessary.

  1. Fault Code Reference

In case of communication anomalies with other devices (de ex., PLC), refer to fault troubleshooting methods for similar industrial devices (de ex., check wiring and communication protocol compatibility).

  1. Obtaining Technical Support

Official Resources: Eaton’s official website provides product manuals and technical documents, but specific materials need to be obtained by searching the model or contacting customer service.

Distributor Services: Contact Whatsapp: 0086-13811255435 for technical consultation and after-sales service. Some support online selection tools.