Honeywell DC120L10001000 Limit Controller

Numele complet: Honeywell UDC120L10001000, a UDC1200 Micro-Pro 1/16 DIN Limit Controller. It is not a conventional PID temperature controller. It is designed for safety over-limit protection with latching alarm function. Decodarea codului modelului: DC120L 10001000 DC120L: UDC1200 series Limit Controller (differentiated from DC1201/1202 conventional PID controllers) 1: Main Output 1, SPDT Relay 0: No auxiliary ...

  • Detalii despre produs

Numele complet: Honeywell UDC120L10001000, a UDC1200 Micro-Pro 1/16 DIN Limit Controller. It is not a conventional PID temperature controller. It is designed for safety over-limit protection with latching alarm function.

  1. Decodarea codului modelului: DC120L 10001000

DC120L: UDC1200 series Limit Controller (differentiated from DC1201/1202 conventional PID controllers)

1: Main Output 1, SPDT Relay

0: No auxiliary output

0: Nicio comunicare

1: Universal Power Supply 90–264VAC (50/60Hz)

0: No second output

0: No optional extras

0: No additional alarm

  1. Specificații de bază
ArticolParametru
Dimensiunea de ansamblu48×48×110 mm (1/16 DIN)
Decupaj panou45×45 mm
Alimentare electrică90~264V AC, 50/60Hz, Power Consumption ≤4W
IntrareUniversal Input: Thermocouple K/J/R/S/B/E/N/T; Pt100 RTD; 4-20mA linear signal
Precizie0.1% of full scale ±1 LSD
Main OutputSPDT Relay, Contact Rating 3A@240VAC
Sampling Period250Domnișoară
AfişaDual 4-digit LED, simultaneous PV/SP display + status LED
GreutateMax. 210g
CertificariCE, RoHS
  1. Funcții cheie (Main Differences Between Limit Controller & Normal PID Controller)
  2. Over-limit Latching Protection: When the measured value exceeds the set limit value, the relay actuates and latches. Manual reset is required for recovery. Applied for over-temperature safety cut-off of ovens, furnaces and heat treatment equipment (safety temperature limiter).
  3. Universal sensor input supporting thermocouples, RTDs and analog signals.
  4. Sensor break detection: TC/RTD break triggers alarm output.
  5. Password-protected parameters to prevent unauthorized modification of limit values on site.
  6. No PID automatic regulation. Only upper / lower limit safety protection (cannot be used for continuous temperature regulation).
  7. Scenarii tipice de aplicare

Over-temperature safety protection loops for industrial ovens, heat treatment furnaces, aging test chambers, environmental chambers, boiler auxiliaries, plastic extruders and food baking equipment. Often used together with conventional PID temperature controllers (PID controller handles regulation; DC120L serves as independent safety temperature limiting).

  1. Instalare & Ghid de cablare
  2. Panel snap-in mounting, max panel thickness 6mm; keep heat dissipation gaps front and rear.
  3. Relay contacts are dry contacts with external load power supply. Do NOT connect high voltage to instrument internal terminals.
  4. Route sensor cables separately away from power cables to reduce interference.
  5. Unlock via password before commissioning to modify temperature limits. Manual key reset is required after latch activation.
  6. Alternativă / Optional Models
  7. Aceeași serie: Other DC120L suffix versions (DC120L10011000 with RS485 communication)
  8. Alternative interne: Yudian AI series limit controllers, Hongrun NHR-1100 (funcții similare, latch logic needs verification)
  9. Legacy Honeywell replacement: DC1000 series limit type (gradually phased out)
  10. Depanare comună

Sensor error displayed: Check TC/RTD polarity, wire breakage and cold junction compensation.

No latch after over-limit: Confirm function mode is set to Limit latch mode instead of ordinary alarm mode.

Relay fails to actuate: Verify contact load rating, terminal wiring and instrument power supply.

Parameters cannot be modified: Instrument password locked, enter unlock password.

  1. HS Code Reference (For Foreign Trade)

9032890090 Other automatic regulating or controlling instruments and apparatus

Tabel de comparație: Honeywell DC120L (UDC120L10001000) vs UDC1202 PID Temperature Controller

Element de comparațieDC120L (Limit Controller)UDC1202 (PID Process Controller)
Poziționarea de bazăSafety over-limit protection instrument (independent safety temperature limiting)Process temperature automatic regulation instrument (main temperature control)
Algoritm de controlNo PID algorithm, only limit logic; Over-limit Latch functionPID/PD/On-off / Three-position stepping valve control; Auto-tune supported
Latch Function✅ Standard: Relay latches after over-limit actuation, manual reset mandatory for release (safety cut-off)❌ Ordinary alarm without latch; output recovers automatically once temperature drops
Funcția de ieșireOutput for safety cut-off only, no continuous regulationMain output for continuous temperature control: Releu / SSR / 4-20mA analog output
Dimensiunea de ansamblu48×48 mm, 1/16 DIN, panel cutout 45×45mm48×48 mm, 1/16 DIN, panel cutout 45×45mm (fully interchangeable for panel mounting)
Universal Input✅ Thermocouple, Pt100, 4-20mA linear signal✅ Thermocouple, Pt100, 4-20mA linear signal
Alimentare electrică90~264VAC wide range90~264VAC wide range
Precizie0.1% of full scale ±1 LSD0.1% of full scale ±1 LSD
Utilizare tipicăOver-temperature safety protection for ovens, heat treatment furnaces and test chambers, independent safety loop (safety redundancy)Closed-loop regulation of normal process temperature to maintain setpoint
Combination ApplicationUsed with PID controller: UDC1202 for main temperature control, DC120L as secondary independent safety protectionSole unit for automatic temperature control; not responsible for safety temperature limiting
Manual / Moda autoNo manual/auto control mode, only limit value settingAutomatic PID regulation, manual output, manual/auto switch available
Alarm TypesOnly over-limit safety latch alarmUpper limit, limita inferioară, deviation, band alarms and more configurable alarm types
Communication OptionRS485 Modbus optional (this DC120L10001000 unit has no communication)RS485 Modbus optional
Puncte cheie ale selecțieiApplications requiring independent temperature limit loop and latching trip per safety specificationsConventional temperature control scenarios requiring automatic constant temperature closed-loop regulation
Observații importanteCannot replace PID controller for temperature regulation, safety protection onlyCannot replace safety limit instrument; non-latching alarm fails safety requirements for some equipment

Selection Recommendation Summary

  1. Equipment requiring safety redundancy, hard over-temperature cut-off and fault latching: Dual-instrument scheme: UDC1202 (main temperature control) + DC120L (independent temperature limit) (widely used for heat treatment, ovens and aging chambers)
  2. Only conventional constant temperature control required with no mandatory safety latch requirement: Select UDC1202 directly
  3. Only over-temperature protection required without automatic temperature control: Select DC120L alone

Honeywell DC120L10001000 (UDC120L Limit Controller) Technical Document

Product Full Name: Honeywell UDC1200 Micro-Pro DC120L Limit Controller

Document Type: Fișa cu date / Technical Specification Manual (English Engineering Version)

Model aplicabil: DC120L10001000 (Ieșire releu, No Communication, 90~264VAC Power Supply)

Poziționarea produsului: Independent safety limit instrument, no PID regulation, over-limit latching trip, applied for equipment over-temperature safety protection

  1. Model Code Definition DC120L 1 0 0 1 0 0 0
Segment de codDescriereConfiguration of This Model
DC120LUDC1200 series Limit ControllerLimit type, no PID algorithm
1st digit 1Main Output Type1=SPDT Relay Output
2nd digit 0Ieșire auxiliară0=No auxiliary output
3rd digit 0Communication Option0=No RS485 Modbus communication
4th digit 1Power Supply Specification1=Universal AC 90~264VAC, 50/60Hz
5th digit 0Second Output0=No second output
6th digit 0Funcție opțională0=No optional extras
7th digit 0Alarm Option0=No additional alarm output
  1. Electric & Specificatii mecanice
ArticolValoareObservații
Dimensiunea de ansamblu48mm × 48mm × 110mm1/16 DIN panel mount
Decupaj panou45mm × 45mmMax panel thickness 6mm
Alimentare electrică90~264V AC, 50/60HzWide-range universal AC supply
Consumul de energie≤4WConsum redus de energie
Greutate≤210g
Sampling Period250Domnișoară (4 ori pe secundă)
Precizia măsurătorilor0.1% of full scale ±1 LSDCold junction compensation ±1℃ for thermocouples
Impedanta de intrare>10MΩ (TC/RTD); 5Oh (4-20mA)
Main OutputSPDT Relay, 3A@240VACDry passive contacts
CertificariCE, RoHSIndustrial certifications
Sensor Break DetectionTC / RTD / 4-20mA break diagnosis supportedBreakage triggers limit action

Universal Input Types (Supported Sensors)

Termocuplu: K, J, R, S, B, E, N, T

RTD: Pt100 (DIN43760 0.00385)

Linear Analog: 4~20mA, 0~20mA, 0~10V, 1~5V

  1. Core Function Description
  2. Limit Latch Protection【Core Feature】

When measured PV exceeds setpoint SP, relay actuates and latches in trip state. No automatic recovery upon temperature drop; manual key reset required. Meets hard cut-off safety requirements for ovens and heat treatment furnaces.

Configurable for high limit or low limit mode.

  1. Sensor Break Diagnosis

Breakage of thermocouple, RTD or 4-20mA signal triggers limit output action to prevent runaway caused by sensor failure.

  1. Parameter Password Lock

Parameter menu protected by password to prevent unauthorized modification of safety limit values. Password unlock required to edit SP, input type and latch mode.

  1. Dual 4-digit LED Display

Upper screen: PV real-time measured value; Lower screen: SP set limit value. Status LED indicates output/alarm/latch status.

  1. No PID Automatic Control

This instrument has no PID regulation function and cannot act as primary temperature controller. It serves only for independent safety over-limit protection, forming dual-loop safety temperature control system when paired with UDC1202 PID controller.

  1. Definiția cablajului terminalului (DC120L Basic Version)

Notă importantă: Relay contacts are passive dry contacts. Do NOT connect load power supply to instrument internal power terminals.

  1. L, N: Instrument power supply, 90~264VAC
  2. Sensor input terminals: Termocuplu / Pt100 / 4-20mA
  3. Main output relay: COM comun, NU deschis în mod normal, NC normal închis

Typical wiring: Use NC normally closed contact. Contact closes under normal temperature; opens upon over-temperature latch to cut heating circuit.

Wiring Recommendation: Use shielded twisted pair for sensor cables, routed separately from power cables to reduce interference.

  1. Specificații de instalare
  2. Panel snap mounting, max panel thickness 6mm; reserve heat dissipation gap for side-by-side multi-unit installation.
  3. Temperatura ambiantă de funcționare: 0~50℃; ambient humidity: 20~80%RH, no condensation and corrosive gas.
  4. Keep away from high-power contactors, frequency converters and strong electromagnetic interference sources.
  5. Legare la pământ: Instrument chassis grounding; single-end grounding for shield layer.
  6. Operațiunea & Configuration Overview

6.1 Enter Parameter Menu

Press 【UP】+【SETUP】 simultaneously, introduceți parola (common password:10/20) to unlock and enter configuration mode.

6.2 Key Configurable Parameters

Input type code (sensor model selection)

Full scale upper/lower range

Limit SP (safety protection threshold)

Limit mode: high limit latch / low limit latch

Latch enable/disable

Action logic for sensor break

Password setting & parameter locking

6.3 Latch Reset

After over-limit latch trip, perform manual reset via keys on operator interface to restore relay contacts to normal state.

  1. Scenarii tipice de aplicare

Independent over-temperature safety protection loops for industrial ovens, hot air furnaces, heat treatment furnaces, aging test chambers, environmental chambers, plastic extruders and food baking equipment.

Standard scheme: UDC1202 (PID main temperature control) + DC120L (independent temperature limit protection) dual-instrument redundant control complying with equipment safety standards.

  1. Tabel de diagnosticare a erorilor
Fenomen de eroareDirecția de depanare
Sensor error displayedCheck sensor wiring polarity and breakage; verify input code matches sensor; verificați împământarea scutului
No latch after over-limitConfirm Latch function enabled in parameters; confirm limit mode instead of ordinary alarm mode
Relay fails to actuateCheck contact load rating; verify COM/NO/NC relay wiring; confirm instrument power supply
Parameters cannot be modifiedInstrument password locked, input unlock password; confirm not in read-only mode
Reading driftSeparați cablurile senzorilor de cablurile de alimentare; verificați împământarea; verify cold junction compensation for TC
  1. Alternative Model Information

Same Honeywell series: DC120L10011000 (version with RS485 communication)

Alternative interne: Yudian AI series limit controllers, Hongrun NHR-1100 (latch logic requires verification)

Înlocuire moștenire: DC1000 series limit controller (întreruptă)

  1. HS Code for Foreign Trade

Cod HS: 9032890090 Other automatic regulating or controlling instruments and apparatus

  1. Safety Notes
  2. This instrument is a safety limit protection device, cannot be used alone for process temperature control.
  3. External contactor is recommended for safety circuit. Relay contact capacity is limited and cannot directly drive high-power heating loads.
  4. Periodic over-temperature test on safety circuit is required to verify latch trip function.
  5. Disconnect power before instrument disassembly and wiring, comply with local electrical safety regulations.

Prev:

Lasă un răspuns