Telemecanique XMLB010A2S11 Presostat electromecanic

Marca: Senzori Telemecanique (formerly Schneider OsiSense XM series, now part of YAGEO) Tip: Diaphragm type, adjustable differential pressure switch with dual setpoints, local scale indicator, 1 contact de schimbare (1CO) ✅ Pressure Specifications Rising pressure setting range: 0.7~10 bar Falling pressure reset range: 0.13~9.15 bar Minimum differential: 0.57 bar; maximum differential: 7.5 bar Instantaneous overload pressure: ...

  • Detalii despre produs

Marca: Telemecanique Senzori (formerly Schneider OsiSense XM series, now part of YAGEO)

Tip: Diaphragm type, adjustable differential pressure switch with dual setpoints, local scale indicator, 1 contact de schimbare (1CO)

✅ Pressure Specifications

Rising pressure setting range: 0.7~10 bar

Falling pressure reset range: 0.13~9.15 bar

Minimum differential: 0.57 bar; maximum differential: 7.5 bar

Instantaneous overload pressure: 22.5 bar; continuous maximum working pressure: 12.5 bar

Presiune de spargere: 45 bar

Sensing element: Diafragmă; wetted materials: FPM/FKM fluoroelastomer + zinc alloy

Compatible media: Aer comprimat, clean water, ulei hidraulic; temperatura medie: 0~70 ℃

✅ Process & Conexiune electrică

Conexiune la proces: Filet interior G1/4 (ISO228)

Electrical entry: Pg13.5 cable gland, cable OD 9–13 mm; terminale cu șuruburi, wire size 0.5~2.5 mm²

Contact: 1CO (13-14-11-12) silver contact, snap-action

Evaluarea contactului: AC-15 120V/3A; 240V/1.5A; DC-13 250V/0.1A

Tensiunea de izolație Ui: 500V(IEC); tensiune de rezistență la impuls Uimp: 6 kV

Clasa de protectie: IP66

Repetabilitate: ±2%; maximum switching frequency: 120 cicluri/min

Durata de viata mecanica: 5 milioane de cicluri

Temperatura mediului ambiant: -25~70 ℃; temperatura de depozitare: -40~70 ℃

✅ Dimensions & Greutate

Lăţime 35 mm × Height 113 mm × Adâncime 75 mm; Greutate netă 0.705 kg; mounting in any orientation

✅ Approvals & Standarde

CE, UL508, CSA, IEC60947-5-1; marine classification approval; origin: Republica Cehă / Maroc; garanție: 18 luni

✅ Aplicații tipice

Compresoare de aer, hydraulic power packs, pompe de alimentare cu apă, lubrication systems, HVAC, general industrial pressure start/stop, high/low pressure interlock protection

✅ Cross-Series Replacement Reference

XMLB shares the same platform with XMLA/XMLC/XMLD. Please distinguish pressure ranges (0.25/10/16/25 bar), contact quantity and indicator versions. Legacy models XM2JM, XMJ can be replaced with XMLB.

Telemecanique XMLB010A2S11 Pressure Switch Installation Manual

Applicable series: XMLA / XMLB / XMLC / XMLD same-platform electromechanical pressure switches. Model: XMLB010A2S11, 10 bar range, adjustable differential, 1CO changeover contact, Filet interior G1/4, Pg13.5 gland, IP66

⚠️ Precautionary Safety Warnings (Read First)

  1. Do NOT disassemble, wire or adjust under pressure or live power. Depressurize the system and isolate control power before any work.
  2. Approved media: Aer comprimat, clean water, standard hydraulic oil. Strong corrosive media or high-temperature media are prohibited (max medium temperature 70 ℃).
  3. Pressure must not exceed instantaneous overload 22.5 bar or burst pressure 45 bar. Overpressure will permanently damage the diaphragm and void protection function.
  4. Contacts are designed for control circuits only. Do not switch main motor power directly. AC-15 120V 3A / 240V 1.5A, DC-13 250V 0.1A.
  5. IP66 rated. For outdoor installation, avoid direct sunlight and continuous heavy spray. Tighten the cable gland fully for sealing.
  6. Punerea în funcțiune, calibration and maintenance must be performed by qualified pneumatic/hydraulic and low-voltage electrical personnel.
  7. Inspecție de despachetare

Verificați modelul: XMLB010A2S11

Check housing and thread for cracks or damage; confirm scale plate intact, gland and sealing washer supplied

Accesorii: Doar unitate, fitted with Pg13.5 cable gland; no adapter included

Verificați plăcuța de identificare: 0.7~10 bar range, 1CO contact, G1/4 ISO228 internal process thread

  1. Instalare mecanică

2.1 Cerințe de montare

Orientarea montajului: Any position (XMLB has no mandatory upright requirement). Prioritize easy visibility of the scale.

Keep away from high heat sources and heavy vibration (excessive vibration causes false tripping and shortens service life).

It is recommended to fit an isolation valve + drain valve at the tapping point for future calibration and replacement without full system shutdown.

Tapping point: Take pressure from the side wall of pipe runs. Avoid high points (air accumulation) and low points (sediment build-up).

2.2 Thread Connection (G1/4 Internal BSP)

  1. Clean male thread, remove burrs and metal debris to prevent particles entering the diaphragm chamber.
  2. Etanșare: Use PTFE tape only on the male thread. Do not push tape residue into the switch internal thread as debris may jam the diaphragm.
  3. Tightening: Use a spanner on the bottom hexagonal process base only. Never clamp the plastic housing — this will damage the internal mechanism.
  4. Torque moderately until leak-tight; do not force over-tightening.

Accesoriu optional: G1/4 to NPT1/4 adapter for NPT piping systems.

2.3 Piping Recommendations

Keep impulse tubing short and large bore to reduce response lag. Long tubing may cause slow response and chattering.

Install a pre-filter for media with solids to protect the FKM fluoroelastomer diaphragm.

Drain water-filled systems in cold environments to prevent freezing; ice expansion ruptures the diaphragm.

  1. Cablaje electrice

3.1 Specificația cablului

Diametrul exterior al cablului: 9~13 mm (matches Pg13.5 gland)

Secțiunea conductorului: 0.5~2,5 mm² (AWG20~AWG14); ferrules are recommended for stranded conductors.

3.2 Definiția terminalului (1contact uscat cu CO)

TerminalDefiniţieDescriere
11COMComun
12NCÎn mod normal închis: Conducts below set pressure, opens at trip pressure
14NUÎn mod normal deschis: Closes at trip pressure, opens at low pressure

Marcare 13: Some versions mark 13 alongside 14 for the same NO circuit; follow housing marking.

3.3 Procedura de cablare

  1. Izolați puterea, remove top cover screws and open the lid.
  2. Loosen Pg13.5 gland nut, feed cable through and strip to suitable length.
  3. Insert wires into terminals and tighten screws securely to avoid loose connections.
  4. Route cables clear of the internal spring adjustment assembly. Refit cover and tighten screws evenly.
  5. Tighten gland and compress rubber seal to maintain IP66 integrity. Poor gland sealing causes water ingress and failure.

Notă de cablare: This is a passive dry contact. No supply voltage is carried by the switch. PLC or relay control power must be supplied externally.

  1. Pressure Setting & Calibrare (XMLB dual setpoint: trip point + diferenţial)

XMLB operation: Two adjustment screws: high setpoint (trip pressure) and differential (histerezis). The low reset point is not independently adjusted.

Specification range for this model:

Rising trip pressure: 0.7~10 bar

Falling reset pressure: 0.13~9.15 bar

Minimum differential 0.57 bar, maximum differential 7.5 bar

Calibration Steps

  1. Fully depressurize the line.
  2. Open the front scale cover to access the two adjustment screws with graduated scale.
  3. Connect a reference pressure gauge (accuracy ≥0.5 class). The built-in scale is only for rough setting.
  4. Raise pressure slowly while monitoring the reference gauge:

Main adjustment screw: Sets trip pressure. At this pressure, contact state reverses (NU se inchide, NC se deschide).

Differential screw: Sets the pressure gap between trip and reset. Larger differential means greater pressure drop before reset.

  1. Cycle pressure up and down 2–3 times to confirm stable trip and reset points with no drift.
  2. Refit protective cover after setting to prevent accidental adjustment. Record values and apply identification label.

✅ Typical example (pornirea-oprirea pompei):

Start at 3 bar, stop at 5 bar → differential = 2 bar. Pump stops at 5 bar, restarts at 3 bar.

Nota: The built-in scale is approximate. Safety interlock applications must be calibrated against a certified reference gauge; accuracy ±2%.

  1. Commissioning Check
  2. Confirm no leakage, secure wiring and intact housing sealing.
  3. Ramp pressure slowly through working range and verify contact switching matches settings.
  4. Complete multiple cycles to confirm no chattering or rapid cycling.
  5. Verify contact load stays within rated limits; fit fuse protection for control circuits.
  6. Înregistra: trip pressure, reset pressure, media, ambient temperature and calibration date.
  7. Întreţinere
  8. Inspecție de rutină: Scurgere, deteriorarea cablului, gland water ingress and housing corrosion.
  9. Calibration interval: 6–12 months for standard air compressor / water pump service; quarterly calibration for safety interlock duty.
  10. Curatenie: Wipe housing externally only. Do NOT disassemble the process chamber. Diaphragm removal destroys sealing and accuracy.
  11. Long-term shutdown: Depressurize and drain the chamber. Drain water circuits to prevent corrosion and freezing.
  12. Durata de viata mecanica: 5 milioane de cicluri. Replace at end of life.
  13. Tabel de depanare a erorilor
SimptomCauza probabilăRemediu
Switch does not actuate at set pressureDiaphragm jammed by debris; differential set too large; cabluri rupteDepressurize, inspect or replace unit; reset differential; verifica cablurile
Rapid cycling / chatteringDifferential set too small; pressure pulsation in pipingIncrease differential; fit snubber or accumulator
Trip pressure drifts out of toleranceSoc de suprapresiune; diaphragm aging; vibrații excesiveReplace switch; add vibration dampening and surge protection
Pătrunderea apei / internal corrosionLoose gland, missing cover gasketReseal assembly; replace unit if sealing parts are damaged
Leakage at threadPTFE tape misapplied; cracked base from over-tighteningRe-seal thread; replace unit if base is cracked

Telemecanique XMLB Series Electromechanical Pressure Switch – Fault Troubleshooting Guide

For XMLB010A2S11, diaphragm type, adjustable differential, contact uscat. Always depressurize and isolate power before troubleshooting; test contacts with multimeter continuity mode.

Simptom de eroareCauza de bazăEtape de inspecțieAcțiune corectivă
No switching when pressure reaches setpoint1. Tapping port / impulse line blocked by sludge, scale or debris2. Diaphragm jammed or ruptured3. Setpoint higher than system working pressure4. Internal adjustment thread stripped or spring seized5. Failed microswitch1. Depressurize and inspect tapping port2. Use reference gauge to confirm actual system pressure3. Test COM-NO / COM-NC continuity with multimeter1. Clear impulse line and add inlet filter2. Reduce trip setpoint and lock screw3. Replace complete unit if diaphragm or internal mechanism is damaged (diaphragm chamber not serviceable on site)
Switch fails to reset below reset pressure, contact stays latched1. Excessive differential setting2. Contact sudat / stuck (inductive load without surge suppression)3. Jammed mechanical linkage or fatigued spring4. Trapped pressure in piping, no pressure relief1. Test continuity after full depressurization2. Check differential scale and verify relief valve operation1. Reduce differential within published range2. Replace switch; add intermediate relay and RC snubber for inductive loads3. Clear piping to enable free pressure relief
Rapid cycling / chattering1. Diferenţial (histerezis) set too low2. Pulsating pressure from pump / compressor3. Insufficient accumulator volume or failed bladder4. Tapping point located in turbulent flow zone1. Observe pressure gauge for small fluctuations2. Check current differential setting1. Increase differential (XMLB max differential 7.5 bar)2. Fit pressure snubber or buffer tank on impulse line3. Relocate tapping point to straight pipe side wall
Trip pressure inconsistent, drifting between cycles1. Spring fatigue from repeated pressure shock2. Permanent diaphragm deformation by overpressure3. Extreme temperature or continuous vibration4. Relying only on built-in scale without reference gauge calibration1. Compare trip/reset points over multiple cycles against certified gauge2. Check history of exceeding 22.5 bar instantaneous overload1. Recalibrate and log values with reference gauge2. Add vibration bracket and heat shielding3. Replace unit if drift persists
Intermittent signal loss, unstable contact1. Loose terminals or oxidized conductors2. Burned / carbonized microswitch contacts3. Water ingress and terminal corrosion from loose gland4. Internal wiring loose due to vibration1. Izolați puterea, open cover and retighten terminals2. Cycle and test continuity repeatedly1. Strângeți din nou bornele, clean or replace oxidized conductors2. Tighten Pg13.5 gland and check seal for IP663. Replace unit if contacts are burned
Media leakage from switch body1. PTFE tape trapped inside the thread and scoring diaphragm2. Diaphragm aging / incompatibility with process fluid3. Freeze damage, overtemperature or overpressure4. Cracked base from spanner on plastic housing1. Identify leak location: thread joint or housing seam2. Verify process pressure and temperature are within ratings1. Re-seal correctly, apply tape only on male thread2. Select wetted material variant compatible with media3. Replace unit if base or diaphragm is damaged
Water ingress and internal rusting1. Missing or loose gland seal2. Aged cover gasket, unevenly tightened cover screws3. Outdoor installation with direct spray / UV exposure1. Open cover and inspect for standing water or oxidation1. Replace gasket, tighten cover screws evenly and compress gland seal2. Fit weather shield for outdoor use
Repeated contact burnout on power-up1. Direct switching of motors / contactoare, exceeding contact ratingXMLB contact rating: AC-15 240V 1.5A, not for high-power loads2. Unsuppressed inductive arcing1. Check load current and separate control circuit from power circuit1. Use pressure switch to drive an intermediate relay only; relay switches the load2. Fit RC snubber across inductive coils

✅ Standard Troubleshooting Sequence

  1. Process check: Confirm pressure, media and temperature are within rating; verify isolation and relief valves are open and impulse line clear
  2. Mechanical check: Scurgere, vibratie, mounting and tapping location
  3. Setpoint check: Verify trip and differential with certified reference gauge
  4. Electrical check: Izolați puterea, test dry contact continuity, check wiring and sealing
  5. Final decision: Replace complete unit if diaphragm, spring or microswitch fails. No spare internal parts are available for XMLB.

✅ Preventive Guidelines

  1. Install pre-filter for dirty media to protect diaphragm
  2. Quarterly calibration for safety interlock circuits; 6–12 months for standard compressor / water pump service
  3. Never apply spanner force to plastic housing; only grip the hexagonal base
  4. Use intermediate relay isolation for inductive loads to extend contact life
  5. Confirm wetted material compatibility: Standard XMLB uses FKM fluoroelastomer; special versions required for aggressive media

Telemecanique Nautilus / OsiSense XM Electromechanical Pressure Switch Series Overview

Nota: XMLA / XMLB / XMLC / XMLD are current main diaphragm / piston pressure and vacuum switches. Legacy XM series (XMJ, XMG, XM2JM, XMP, FYG) are discontinued and only for cross-reference. Conexiune standard: G1/4 internal ISO228 thread, passive dry contact, control circuit duty, IP66

Model coding rule (XMLB010A2S11 example):

XML [Serie] [Gamă] [Wetted Material] [Contact / Mecanism] [Electrical Entry] [Versiune]

S11 = Pg13.5 cable gland, terminale cu șuruburi (XMLB010A2S11); S12=M20 gland; C11=DIN43650 connector

Comparație de serie

SerieContacteDiferenţialCaracteristica cheieUtilizare tipică
XMLA1COFixed differentialSingle setpoint, fixed hysteresis, rentabilCompresoare de aer, simple alarm, single threshold protection
XMLB1COAdjustable differentialO singură schimbare, adjustable trip+reset, scale plate (modelul dvs)Pump start-stop, compressor pressure regulation, lubrifiere & sisteme hidraulice
XMLC2COAdjustable differentialTwo independent changeover contacts, dual adjustable setpointsSeparate low-pressure warning + high-pressure shutdown, interblocare, pump/fan sequencing
XMLD2COFixed differentialDual independent switch elements, each with fixed hysteresisTwo independent fixed pressure thresholds, safety interlock
XMLAM / XMLBMVidFix / ReglabilNegative pressure vacuum switch, -1…0 barVacuum handling, suction lines
  1. XMLA (Fixed Differential, 1CO) Lista de modele
ModelGamă (bar)Observații
XMLA002A2S110.25~2.5Low pressure air / apă
XMLA004A2S110.4~4Aprovizionare cu apă, HVAC
XMLA010A2S110.7~10General air compressor
XMLA020A2S111.2~20Hidraulic, medium pressure pneumatic
XMLA035A2S112.1~35Medium pressure hydraulic
XMLA070D2S114.5~70High pressure hydraulic
XMLA160D2S119~160High pressure hydraulic
XMLA300D2S1116~300Heavy-duty hydraulic
XMLA500D2S1130~500Ultra-high pressure hydraulic
XMLAM01V2S11-1~0Vacuum switch
  1. XMLB (Adjustable Differential, 1CO, including XMLB010A2S11)
ModelGamă (bar)Observații
XMLB002A2S110.25~2.5Low pressure
XMLB004A2S110.4~4HVAC & aprovizionare cu apă
XMLB010A2S110.7~10Modelul tău, popular for compressors & pompe
XMLB020A2S111.2~20Medium pressure pneumatic / hydraulic
XMLB035B2S112.1~35Hydraulic power units
XMLB070D2S114.5~70High pressure hydraulic
XMLB160D2S119~160High pressure hydraulic
XMLB300D2S1116~300Heavy-duty hydraulic
XMLB500D2S1130~500Ultra-high pressure hydraulic
XMLBM02V2S11-1~0Adjustable vacuum switch
  1. XMLC (Adjustable Differential, 2CO Dual Contacts)
ModelGamă (bar)Observații
XMLC004B2S110.4~4Dual signal output
XMLC010B2S110.7~1010 bar dual contact, scăzut / high pressure alarm
XMLC020B2S111.2~20Medium pressure dual output
XMLC035B2S112.1~35Hydraulic dual interlock
XMLC070D2S114.5~70High pressure dual contact
XMLC160D2S119~160High pressure hydraulic
XMLC300D2S1116~300Heavy-duty hydraulic
XMLC500D2S1130~500Ultra-high pressure hydraulic
  1. XMLD (Fixed Differential, 2CO Dual Stage)
ModelGamă (bar)Observații
XMLD004B2S110.4~4Dual stage fixed hysteresis
XMLD010B2S110.7~1010 bar dual stage protection
XMLD020B2S111.2~20Medium pressure dual stage
XMLD035B2S112.1~35Hydraulic safety interlock
XMLD070D2S114.5~70High pressure dual stage
  1. Discontinued Legacy Models (Cross-reference only, nu pentru proiecte noi)

XMJ: Old single setpoint pressure switch, replaced by XMLA

XMG: Old adjustable differential switch, replaced by XMLB

XM2JM: Simple fixed differential auxiliary sensor

XMP / FYG: Old dual setpoint switch, replaced by XMLC

Most legacy XM series discontinued in 2002; stock only available in spare parts market. Prefer XMLB/XMLC for replacement.

  1. Electrical Suffix Cross Reference (Interchangeable for same range)

S11: Pg13.5 cable gland, terminale cu șuruburi (XMLB010A2S11 standard)

S12: Presetupă M20×1,5, terminale cu șuruburi

C11: DIN43650 square connector (solenoid valve style)

S13: Special extended housing version

  1. Wetted Material Code Definition

O: fluoroelastomer FKM (general: aer, clean water, ulei hidraulic, standard)

B: NBR nitrile rubber (ulei mineral, not for hot water)

D: Oţel inoxidabil + FKM (ulei hidraulic, elevated temperature hydraulic)

V: Vacuum grade sealing

  1. Ghid de selecție rapidă
  2. Single trip point, fixed hysteresis → XMLA
  3. Adjustable start-stop differential (pompa / compresor) → XMLB (XMLB010A2S11)
  4. Two independent alarm signals (low warning + high shutdown) → XMLC
  5. Two independent thresholds, no differential adjustment required → XMLD
  6. Negative vacuum pressure → XMLAM / XMLBM

Prev:

Următorul:

Lasă un răspuns