Modul de intrare analogică OMRON CJ1W-AD04U

OMRON CJ Series 4-Channel Isolated Universal Analog Input Module (Unitate specială I/O) Stare: Întrerupt. Available via spare parts and second-hand markets. Compatible with CJ1/CJ2/NJ-series PLCs. Independent signal type configuration for each of the 4 canale, inter-channel isolation. Supports mixed acquisition of temperature sensors, 4~20mA and voltage signals, widely used in industrial process measurement. ✅ Model ...

  • Detalii despre produs

OMRON CJ Series 4-Channel Isolated Universal Analog Modul de intrare (Unitate specială I/O)

Stare: Întrerupt. Available via spare parts and second-hand markets. Compatible with CJ1/CJ2/NJ-series PLCs. Independent signal type configuration for each of the 4 canale, inter-channel isolation. Supports mixed acquisition of temperature sensors, 4~20mA and voltage signals, widely used in industrial process measurement.

✅ Model Explanation

CJ1W: Prefix for CJ-series Special I/O Units

AD: Intrare analogică

04: 4 canale

U: Universal multi-type input

CJ1W-AD04U: Screw terminal type; CJ1W-AD04U-SL: Terminal cu arc (fără unelte) versiune

📌 Core Specifications

ArticolParametru
Numărul de canale4CH, input type configurable independently per channel
Supported InputsPlatinum RTD: Pt100, Pt1000, JPt100 (3-sârmă)
Termocuplu: K, J, T, L, R, S, B
Actual: 4~20mA, 0~20mA
Voltaj: 1~5V, 0~5V, 0~10V
Rezoluţie1/12000 (Tensiune/curent, approx.14-bit)
Conversion Cycle250ms for all 4 canale
Precizie (25℃)Tensiune/curent: ±0,3% FS
Platinum RTD: The greater of ±0.3%PV or ±0.8℃
Termocuplu: The greater of ±0.3%PV or ±1.5℃
IzolareChannel-to-channel isolation; opto+transformer isolation between channels and PLC bus; Withstand voltage AC500V
Alimentare electricăDC5V, Max 320mA (Powered via PLC backplane)
Dimensiuni31(W) ×90(H) ×65(D) mm; ≤150g
TerminaleRemovable 18-pin terminal block
Unit NumberRotary switch on front: 00~95, must not overlap with other Special I/O Units

✨ Features

  1. Universal Mixed Input: 4 channels can be set to different types, de ex. CH1=Pt100, CH2=4~20mA, CH3=K-type thermocouple
  2. Built-in Cold Junction Compensation for direct thermocouple use; 3-wire Pt100 measurement, max single wire resistance ≤20Ω
  3. High/low limit alarm per channel, alarm delay 0~60s and hysteresis setting; open-circuit/error detection
  4. Zero/Span calibration available during operation
  5. Automatic value scaling; temperature values stored in CPU multiplied by 10 (de ex. 256.0℃ → stored as 2560)
  6. Data exchange: Allocation Relay Area (measured values + alarm flags), DM Parameter Area (gamă, alarma, channel type)

🛠 Installation & Ghid de cablare

  1. Mount on CJ CPU base or expansion base; it is a Special I/O Unit. Unit number and channel types must be configured in PLC software.
  2. 3-wire Pt100: A/B/b three wires with equal length; B and b must NOT be shorted outside the module terminals.
  3. Intrare curentă: Module integrates built-in 250Ω sampling resistor, connect in series directly into the loop.
  4. Max input rating: Voltage ±15V; Current 30mA. Do NOT exceed range.
  5. Warm up for 30 mins after power on to reach rated accuracy.

⚠️ Depanare (Defecte comune)

  1. ERR Red LED: Duplicate unit number, insufficient backplane 5V supply, terminale libere, incorrect parameter download
  2. Fluctuating temperature reading: Cold junction interference for thermocouple, unbalanced resistance of 3 Pt100 wires, ground loop interference
  3. Abnormal 4~20mA reading: Incomplete closed loop, missing external transmitter power supply
  4. Open-circuit alarm: Broken sensor cable or poor contact

🔁 Referință de selecție alternativă

Same-series upgraded model: CJ1W-PH41U (Faster sampling, wider signal types; also discontinued)

New project recommendation for NX series: NX-AD4204 / NX-TC3404 (Separate or universal temperature & intrare analogică)

Simple alternative if only 4~20mA/voltage required: CJ1W-AD041 (Analog only, no thermocouple/RTD support)

📎 Supporting Document

Manual No.: W466-E1-02 (CJ1W-AD04U Operation Manual)

Compatible PLCs for CJ1W-AD04U (CJ-series Universal Analog Special I/O Unit)

This module is a CJ bus Special I/O Unit, mounted directly on CJ backplane. Restrictions apply for NJ/CP1H. Not compatible with CS series.

✅ Native Direct Compatibility (CJ1 CPUs, mount directly on CJ rack)

CJ1M: CJ1M-CPU11 / CPU12 / CPU13 (Including ETN Ethernet versions)

CJ1G: CJ1G-CPU42H / 43H /44H /45H; CJ1G-CPU42P/43P/44P/45P (Tip de control al buclei)

CJ1H: CJ1H-CPU65H / 66H/67H

✅ Native Direct Compatibility (CPU-uri CJ2, mount directly on CJ rack)

CJ2M: CJ2M-CPU11 /12 /13 /14 /15 /31 /32 /33 /34

CJ2H: CJ2H-CPU64 /65 /66 /67 (Inclusiv modele -EIP Ethernet)

✅ Seria NJ (Controler de mașină, utilizabil cu avertismente)

NJ501, NJ301 și alte controlere NJ: Poate folosi CJ1W-AD04U cu rack CJ

Nota: Încă tratată ca unitate specială I/O în sistemul NJ. Software-ul de configurare este Sysmac Studio, diferit de CX-Programmer pentru CJ. Unele instrucțiuni native CJ Special I/O nu sunt acceptate.

✅ CP1H (Este necesar un adaptor, nu se poate conecta direct)

CPU CP1H nu are backplane CJ nativ. Trebuie să utilizați CP1W-EXT01 (Adaptor pentru unitate CJ). Maxim 2 Unități speciale I/O CJ (AD04U aparține acestei categorii). CP1E/CP1L nu este acceptat.

❌ Incompatibil

  1. Seria CS1 (CS1G/CS1H): Autobuz de tip backplane diferit, nu poate fi folosit direct
  2. CP1E, CP1L, CPM, CQM1, C200H: Niciun suport pentru modulele speciale I/O CJ1W
  3. PLC din seria NX: NX folosește module NX-AD dedicate, nu se poate monta pe backplane NX

📌 Note importante de utilizare

  1. Locația de montare: Rack CPU sau rack de expansiune CJ. Comutatorul rotativ de pe partea frontală a modulului stabilește numărul unității (00~95). Nu există numere duplicate ale unităților speciale I/O.
  2. Software: CX-Programmer pentru CJ1/CJ2; Sysmac Studio pentru NJ
  3. Consumul de energie: DC5V, 320mA. Calculați capacitatea de putere a panoului posterior în timpul selecției.
  4. Max per sistem: Până la 40 Unități speciale I/O CJ (Limitat de sursa de alimentare și capacitatea procesorului)
  5. Pași pentru a configura CJ1W-AD04U în CX-Programmer (CJ1M / CJ2M / CJ2H / CJ1G)

Condiție prealabilă: Setați numărul unității rotative hardware (00~95). Nu există duplicate între unitățile speciale I/O. Înregistrați acest număr pentru configurarea software-ului.

  1. Proiect nou & Selectați modelul CPU
  2. Deschideți CX-Programmer → Proiect nou
  3. Tip de dispozitiv: CJ1M / CJ2M / CJ2H / CJ1G, selectați procesorul corespunzător
  4. OK pentru a intra în spațiul de lucru al proiectului
  5. Tabelul I/O și Configurarea unității (Pasul de bază)
  6. Faceți dublu clic [Setări tabel I/O și unitate] în arborele de proiect pentru a deschide vizualizarea rack
  7. Faceți clic dreapta pe slotul de rack gol → [Adăugați o unitate]
  8. Categorie: I/O analogic general → CJ1W-AD04U, Bine
  9. Selectați unitatea AD04U, faceți clic dreapta [Unit Settings] to open module parameter window

⚠️ Unit number must match hardware rotary switch! Exemplu: hardware set to 0, software unit number =0

  1. Channel Parameter Configuration (Intrare universală, independent per channel)

Each channel can independently select sensor type: Pt100/Pt1000/JPt100 / K/J/T/L/R/S/B thermocouple /4~~20mA /0~~10V etc.

Channel Enable: Check to activate unused channels; disable unused channels otherwise alarms easily triggered

Tip de intrare: Dropdown to select sensor/range

Temperature Unit: ℃ / ℉ (for temperature inputs)

Alarm Settings: Limită superioară/inferioară, alarm delay 0~60s, histerezis; enable open-wire detection

Zero/Span Calibration: Optional online calibration

Averaging Processing: Reduce signal fluctuation (opțional)

Register Allocation Rule:

Unit No. N:

CIO: Starts at `CIO 2000 + 100×N`

CH1 Measured Value: `2000+100N`

CH2 Measured Value: `2001`

CH3 Measured Value: `2002`

CH4 Measured Value: `2003`

Alarm flags and status bits in subsequent bits

DM Parameter Area: `D20000 + 100×N` stores channel type, range parameters

Exemplu: Unit No.=0

CH1 Value → CIO2000; CH2→CIO2001; CH3→CIO2002; CH4→CIO2003

  1. Download and Online Verification
  2. After parameter setup, [Transfer to PLC] (Download I/O table + special unit parameters together)
  3. Switch PLC to Monitor mode and watch CIO channel readings
  4. No ERR red light = basic configuration OK. ERR red light causes: mismatched unit number, insufficient backplane 5V, parametri incorecți

Notă importantă: AD04U is a Special I/O Unit. Parameters download into PLC memory and auto-load to module on power-up. No initialization instructions required in user program.

  1. Restrictions for CP1H + CP1W-EXT01 + CJ1W-AD04U

Hardware architecture: CP1H CPU + CP1W-EXT01 Adapter + CJ Backplane + CJ1W-AD04U

✅ Permis

  1. Maxim 2 Unități speciale I/O CJ (AD04U counts as Special I/O; combination: 1×AD04U + another CJ Special I/O)
  2. Only supports CJ Special I/O Units / Unități de magistrală CPU; I/O de bază CJ (CJ1W-ID/OD) nu poate fi montat
  3. Configurația CX-Programmer este aproape identică cu configurația CJ: Adăugați AD04U în tabelul I/O și setați numărul unității

❌ Limitări dure

  1. Cantitate maximă: 2 unitati, nu poate adăuga al treilea. Sunt permise două AD04Us, dar bugetul actual al backplane-ului de 5V trebuie validat (320mA pentru AD04U)
  2. Lungimea extensiei: Doar un segment al bazei CJ după EXT01; Fără o altă bază de expansiune CJ sau cablu de expansiune în cascadă
  3. Instrucțiuni CJ Special I/O parțial avansate indisponibile; funcțiile de bază de achiziție și alarmă ale AD04U funcționează normal
  4. Capacitatea programului CP1H și spațiul de adrese CIO limitat; evitați numerele mari de unități, recomandat 0, 1
  5. Alimentare electrică: 5Puterea V pentru rack CJ după EXT01 trebuie să aibă o capacitate suficientă. Două AD04Us atrag un total de 640mA, rezervă ≥30% marjă contabilă pentru consumul de bază
  6. CP1E / CP1L nu poate folosi EXT01, doar CP1H (Modele XA/X)
  7. Adresa: Regulile de compensare ale CIO și DM la fel ca și CJ, dar zona CP1H CIO limitată, număr de unitate ≤15 recomandat

⚠️ Capcane comune

  1. Lipsește terminatorul CJ1W-TER01 la capătul rack-ului EXT01 (livrat cu adaptor, Eroare I/O dacă lipsește)
  2. Numărul de unitate duplicat pe două module → LED roșu ERR
  3. Selecție greșită: Încercați să montați unitatea de bază DI/DO CJ1W-ID211 după EXT01 → Nerecunoscut
  4. Curent insuficient de 5 V pentru backplane: ERR clipește după pornire, fără date de măsurare

Procedura de depanare simplificată pentru CP1H + AD04U

  1. Cablajul hardware: Montați CP1W-EXT01 pe portul lateral CP1H → bază CJ → AD04U, instalați terminatorul CJ1W-TER01 la capătul rackului
  2. Setați numărul unității rotative AD04U la 0 (sau 1)
  3. Nou proiect CP1H în CX-Programmer, deschideți tabelul I/O, adăugați CJ1W-AD04U sub rack de expansiune EXT01, potriviți numărul unității cu hardware-ul
  4. Set 4-channel input types and download I/O table + parametrii
  5. Online monitor CIO area to read temperature/analog signals

Engineering Application Cases of OMRON CJ1W-AD04U (Universal Analog Input Module)

Core advantages: Independent 4-channel setup, inter-channel isolation, mixed acquisition of Pt100/thermocouple/4~~20mA/0~~10V. Ideal for small reactors, sterilizers, heat exchange stations, tratarea apei, ovens and other mixed-sensor process applications.

PLC Host: CJ2M / CJ1M / CJ1G; HMI options: NB/NS Touchscreen, CX-Supervisor SCADA

Cazul 1: Temperatură & Pressure Monitoring for Small Reactor (Typical AD04U Application in Chemical/Pharmaceutical)

Project Requirements

Reactor multi-signal acquisition:

CH1: Pt100 (Vessel temperature 0~~200℃, 3-wire RTD)

CH2: K-type thermocouple (Jacket temperature 0~~400℃)

CH3: Pressure transmitter 4~~20mA (0~~1.0MPa)

CH4: Level transmitter 4~~20mA (0~~2m liquid level)

Funcții: Limit alarm, open-wire detection, real-time HMI display, over-temperature interlock output via DO module.

Hardware Architecture

CJ2M-CPU13 + CJ1W-AD04U (Unitate 0) + CJ1W-OD211 Digital Output + NB Touchscreen

AD04U handles mixed signals across four channels, eliminating separate temperature module and regular AI module to save rack slots.

Puncte cheie de configurare

  1. Add CJ1W-AD04U in CX-Programmer I/O Table; hardware rotary switch 00
  2. Channel setup

CH1: Pt100, open-wire detection enabled; linearization onboard, stored value ×10 (256.0℃→2560)

CH2: K thermocouple, built-in cold junction compensation

CH3: 4~~20mA, range 0~~1MPa

CH4: 4~~20mA, range 0~~2m

  1. Adresa (Unitate 0)

CH1 Temperature: CIO2000; CH2: CIO2001; CH3 Pressure: CIO2002; CH4 Level: CIO2003

  1. Program: SCL scaling, high/low limit comparison; channel open-wire bit triggers alarm, over-temperature triggers DO to cut heating.

Field Debugging Issues

Thermocouple shield cable single-end grounding. Ground loop and temperature fluctuation occur with both ends grounded;

Unequal resistance of three Pt100 wires leads to reading drift, keep three wires same length;

30-minute module warm-up before reaching rated accuracy.

Cazul 2: Food Sterilizer (Steam Sterilization Equipment)

Cerințe

Multi-point temperature measurement inside chamber, monitor cavity temperature and steam pressure for pasteurization / high-temperature sterilization process logging.

CH1: Pt100 Chamber Temperature 0~~135℃

CH2: Pt100 Product Core Temperature

CH3: 4~~20mA Steam Pressure 0~0.4MPa

CH4: Reserved for cooling water K thermocouple

System Features

Sterilization site has heavy electrical interference, inter-channel isolation of AD04U delivers better noise immunity than non-isolated regular AI. Data uploaded to touchscreen to save process curves for food batch traceability.

Expansiune: Add CJ1W-DA021 analog output module for PID temperature control to modulate steam regulating valve.

Cazul 3: Heat Exchange Station (HVAC / District Heating Substation)

Cerințe

Primary supply temp, primary return temp, supply pressure, return pressure

CH1: Pt100 Primary Supply

CH2: Pt100 Primary Return

CH3: 4~~20mA Supply Pressure 0~~1.6MPa

CH4: 4~~20mA Return Pressure 0~~1.6MPa

PLC: CJ1M-CPU12; Remote SCADA, heat calculation, high/low pressure and overtemperature alarm.

Puncte cheie

Sensors distributed over long wiring distances in heating stations. Built-in open-circuit detection alerts maintenance staff immediately on probe failure.

Cazul 4: CP1H+CP1W-EXT01+CJ1W-AD04U Low-cost Water Tank Temperature & Level Monitoring

Hardware

CP1H-X40DT-D + CP1W-EXT01 Adapter + CJ Base + CJ1W-AD04U + CJ1W-TER01 Terminator

Prescripţie: Max 2 Unități speciale I/O CJ; numai 1 AD04U used here

Canale:

CH1: 4~~20mA Liquid Level 0~~5m

CH2: Pt100 Water Temperature

CH3, CH4 Reserved

Aplicație: Water purification / sewage tank, pump start-stop interlock by liquid level, overtemperature alarm.

Nota: No CJ basic DI/DO allowed after EXT01, only Special I/O; calculate 5V backplane consumption (320mA for AD04U).

Cazul 5: Cuptor / Heat Treatment Furnace Monitoring (K Thermocouple Dominant)

CH1/CH2 K thermocouple for multi-point furnace temperature; CH3 4~~20mA fan wind pressure; CH4 0~~10V speed potentiometer.

Suitable for small heat treatment and drying ovens. Supports thermocouple + Voltaj + current within single module, which is the biggest advantage of AD04U. Regular CJ1W-AD041 only handles 4~20mA/voltage and does not support RTD/thermocouple.

General Programming Guidelines for CJ1W-AD04U

  1. Temperatură (Pt100/Thermocouple): Onboard linearization, raw value = actual temperature ×10;

Exemplu: CIO2000=1250 → 125.0℃

  1. 4~20mA Raw Range: 4mA corresponds to 1/12000, 20mA corresponds to full scale; SCL instruction scales engineering value in PLC program
  2. Alarme: Module hardware provides per-channel high/low limit and open-wire bits in subsequent CIO bits, no need to write comparison logic for open-circuit detection.

Ghid de selecție (When to choose AD04U)

✅ Potrivit: Mixed sensor types (Pt100, thermocouple plus 4~~20mA transmitters), inter-channel isolation required, ≤4 points

❌ Nu este potrivit: Pure 4~~20mA acquisition with many points (CJ1W-AD081 recommended); high-speed sampling (CJ1W-PH41U recommended)

Summary of Common Faults in Field Commissioning

  1. ERR Red LED: Duplicate unit number, insufficient backplane 5V power, I/O table parameter not downloaded
  2. Jumpy temperature reading: Shield cable grounded at both ends, sensor cables routed together with power cables
  3. 4~20mA locked at 4mA: Transmitter loop open, 2-wire transmitter wiring error
  4. Pt100 reading drift: Unequal resistance among three wires

Prev: