CJ1W-AD081-V1
- CJ1W: Special I/O module series base for CJ1-series PLCs
- AD: Intrare analogică
- 08: 8 canale de intrare analogice
- 1: Standard hardware revision
- V1: Upgraded functional version (supports wire break detection, dual resolution switching, and digital smoothing filter)
Derivative Model: CJ1W-AD081-V1-SL (spring screwless terminal type)
- Core Hardware Specifications
Parametrii de bază
| Articol | Caietul de sarcini |
| Numărul de canale | 8 independent analog inputs (CH1~CH8) |
| Compatible PLC CPUs | Full lineup of CJ1M / CJ1H / CJ2M / CJ2H CPUs |
| Bus Interface | Dedicated CJ backplane I/O bus; nu este necesară alimentarea externă |
| Backplane Power Consumption | DC 5V ≤ 420mA |
| Isolation Scheme | Optocoupler isolation between internal module circuit and PLC bus; no isolation between individual channels |
| Dimensiuni generale | W31mm × H90mm × D65mm |
| Greutate | ≤ 140g |
| Mediul de operare | 0~55°C, 10%~90% RH non-condensing |
| Terminal Specifications | Model standard: Borne cu șurub M3; SL model: spring quick-disconnect terminals, 18-pin detachable terminal block |
Input Signal Ranges (Hardware DIP switch selectable per channel)
Tensiune de intrare (DIP Switch = OFF)
-10~+10V, 0~10V, 0~5V, 1~5V
Impedanta de intrare: ≥1MΩ, Maximum Withstand Voltage: ±15V
Intrare curentă (DIP Switch = ON, built-in 250Ω sampling resistor)
4~20mA, 0~20mA
Impedanta de intrare: 250Oh, Maximum Withstand Current: ±30mA
Precizia conversiei & Rezoluţie
- Two software-selectable resolution grades
4000-count (12-pic): Economical mode with fast conversion speed
8000-count (13-pic): High-precision mode for precise flow/pressure measurement
- Full-scale Accuracy (Temperatura mediului ambiant: 25°C)
Tensiune de intrare: ±0,2% FS
Intrare curentă: ±0.4% FS
- Full-temperature Range Accuracy (0~55°C)
Voltage Signal: ±0.4% FS
Current Signal: ±0,6% FS
- Viteza de conversie: 1ms pe canal; full scan of 8 channels takes 8ms; high-speed mode: 250μs pe canal
- Built-in Core Functions
- Wire Break Detection (Dedicated for 4~20mA Circuits)
When a current loop is open, the corresponding channel wire break flag turns ON for program-based alarming.
- Digital Smoothing Filter
Average value calculation to suppress sensor jitter and on-site electromagnetic interference.
- Peak / Valley Hold
Captures and locks the maximum and minimum analog values within a cycle, suitable for impact pressure and instantaneous flow acquisition.
- Offset / Gain Calibration
Onboard calibration registers allow on-site correction of sensor zero drift.
- Custom Range Scaling
Upper and lower limits of ±32000 can be configured to directly map 4–20mA signals to engineering values such as 0~1000 or 0~5000.
- Terminal Wiring Definition (18-Pin Terminal Block)
Each channel occupies two terminals: V+ (Signal Positive), COM (Common Negative)
CH1: Pin1(V+), Pin2(COM)
CH2: Pin3(V+), Pin4(COM)
CH3: Pin5(V+), Pin6(COM)
CH4: Pin7(V+), Pin8(COM)
CH5: Pin9(V+), Pin10(COM)
CH6: Pin11(V+), Pin12(COM)
CH7: Pin13(V+), Pin14(COM)
CH8: Pin15(V+), Pin16(COM)
Pin17, Pin18: Shield grounding terminals (Connect all sensor shield cables here for anti-interference performance)
Ghid de cablare
- Voltage signals: Connect only V+ and COM; set DIP switch to OFF
- 2-wire 4~20mA transmitters: Connect V+ to transmitter positive terminal, COM to 24V negative terminal; set DIP switch to ON
- It is recommended to common the COM terminals of multiple sensors. Connect shield layers to pins 17/18 of the module at one end only; double-end grounding is prohibited.
- PLC Memory Allocation (Special I/O Unit)
- Input Relay Area (10 Words): Stores raw A/D conversion values for 8 canale
CH1: Channel Word 0; CH2: Channel Word 1 … CH8: Channel Word 7
- Output Relay Area (10 Words): Function setting registers
Includes resolution switching, filter sampling count, wire break detection enable, upper/lower scaling limit parameters
- Software de configurare: CX-Programmer + CX-Integrator. Channel addresses are automatically assigned after registering the module in the I/O table.
- Typical Industrial Application Scenarios
- Fluid Control: Acquisition of 4–20mA transmitters for pressure, liquid level and flow
- Temperature Control Systems: 0~10V / 1~5V temperature transmitter modules
- Analog Feedback for Inverters & Servo Drives: Collection of 0~10V speed and torque feedback signals
- Centralized multi-point analog signal acquisition for water treatment, chemical and packaging machinery
- Same Series Comparison & Soluții de înlocuire
Comparison of Analog Input Modules in the Same Series
| Model | Channel Count | Caracteristici cheie |
| CJ1W-AD041-V1 | 4 canale | Low-cost solution for small-scale point acquisition |
| CJ1W-AD081-V1 | 8 canale | Standard general-purpose model with largest market stock |
| CJ1W-AD161 | 16 canale | High-density acquisition; without V1 enhanced functions |
Upgrade & Compatible Replacements
- Direct drop-in replacement on the same platform: CJ1W-AD081-V1-SL (terminale cu arc, identical hardware parameters; no program modification required)
- CJ2 Series Compatibility: Direct mounting on CJ2M/CJ2H CPUs with unchanged I/O configuration
- Replacement for legacy CS Series: CS1W-AD081-V1 (Backplanes are incompatible; CPU rack replacement is mandatory)
- New-generation NX Series Alternative (Recomandat pentru proiecte noi): NX-AD4208 (8-canal de intrare analogică, EtherCAT bus)
- Common Fault Troubleshooting Matrix
| Fenomen de eroare | Cauze fundamentale | Resolution Steps |
| All channels show fixed zero value | 1. Module not registered in CX-Integrator; 2. Poor backplane contact; 3. Insufficient 5V backplane power supply | 1. Rebuild and download the I/O table; 2. Remove and re-seat the module firmly; 3. Reduce the number of modules installed on the backplane |
| Single channel value unchanged / stuck at full scale | 1. Incorrect DIP switch setting for voltage/current mode; 2. Open/short circuit in signal wiring; 3. Loss of 24V power supply to transmitter | 1. Verify channel DIP switch configuration; 2. Test circuit continuity with a multimeter; 3. Check power supply to sensors |
| Frequent wire break alarms on 4–20mA channels | 1. Excessive voltage drop along cables; 2. Insufficient load capacity of transmitters; 3. Loose terminal connections | 1. Use thicker signal cables; 2. Shorten cable length; 3. Tighten terminal screws |
| Severe signal drift and fluctuation | 1. Shield ground not connected; 2. Smoothing filter disabled; 3. Analog cables laid in parallel with power cables inside the same trunking | 1. Connect shield wires to module ground terminals; 2. Enable average filter in software; 3. Separate low-signal wiring and high-power wiring |
| Excessive conversion error | 1. Ambient temperature exceeds 55°C; 2. Long-term zero drift; 3. External signals out of rated range | 1. Improve cooling of control cabinet; 2. Perform offset/gain calibration; 3. Confirm matching of transmitter measuring range |
- Usage Restrictions (Strictly Forbidden Operations)
- Do not set DIP switches of voltage-input channels to current mode; this will burn the internal sampling resistor of the module
- Never apply input signals exceeding ±15V (modul de tensiune) or ±30mA (modul curent); A/D chips may suffer permanent breakdown
- Avoid parallel routing of analog signal cables with power cables for inverters and contactors in the same cable trunking; severe electromagnetic interference will cause data distortion
- Double-end grounding of transmitter shield layers is prohibited, as circulating current will introduce power-frequency interference
- Power off the entire PLC system before plugging/unplugging modules; hot swapping will damage backplane bus interfaces
Official Accuracy Specifications of CJ1W-AD081-V1 (Per OMRON Manual Standards)
- Nominal Accuracy at Room Temperature (23±2°C / 25°C, Full-Scale Error)
- Tensiune de intrare (0~5V / 0~10V / -10~+10V / 1~5V)
Overall Accuracy: ±0,2% FS
- Intrare curentă (4~20mA / 0~20mA)
Overall Accuracy: ±0.4% FS
> Nota: FS = Full Scale, referring to relative error across the entire signal range, including integrated zero-point, gain and linearity errors.
- Full-Temperature Range Accuracy (0~55°C Operating Temperature)
Voltage Signals: ±0.4% FS
Current Signals: ±0,6% FS
- Rezoluţie (Distinction Between “Precizie” şi “Rezoluţie”)
Resolution refers to the minimum detectable signal change and is not equivalent to accuracy:
- Low-speed mode (1ms pe canal): 1/4000 (12-pic)
- Mod de mare viteză (250μs pe canal): 1/8000 (13-pic)
Error Calculation Examples
Calculation based on 4~20mA (full span = 16mA) with current accuracy ±0.4%FS:
Maximum Absolute Error = 16mA × 0.4% = ±0.064mA
Calculation based on 0~10V voltage with accuracy ±0.2%FS:
Maximum Absolute Error = 10V × 0.2% = ±0.02V
- Supplementary Remarks
- Factory default calibration is optimized for voltage signals. For 4–20mA current loop applications, perform offset/gain calibration via software to further reduce current measurement errors.
- No galvanic isolation exists between channels. Additional measurement errors may be introduced by multi-sensor common-ground wiring, long cables or heavy electromagnetic interference; such errors are not included in the module’s nominal accuracy rating.
- The specified accuracy excludes external error sources such as sensor intrinsic error, cable voltage drop and grounding interference.
Full Application Scenarios of CJ1W-AD081-V1 (Classified by Industry, Equipment and Collected Signals)
This is a general-purpose 8-channel analog acquisition module compatible with 4~20mA / 0~10V / 1~5V signals, equipped with wire break detection, digital filtering and peak hold functions. It supports CJ1H/CJ1M/CJ2M/CJ2H CPUs and is ideal for multi-point continuous physical quantity collection, closed-loop process control and equipment condition monitoring. No isolation between channels, making it suitable for sensor networks sharing a common ground at the same location.
- Chimic / Tratarea apei / Protecția mediului (Most Common Application Field)
Collected Signals
Mainly 4~20mA 2-wire transmitters: liquid level, presiunea conductei, flow rate, PH/ORP, dissolved oxygen, turbidity, chemical reagent concentration, reactor temperature
Echipamente & Sisteme
- Complete wastewater treatment equipment: Closed-loop dosing control based on biochemical tank liquid level, aeration pressure, influent and effluent flow rates, and chemical tank liquid level
- Pure water / reverse osmosis equipment: Collection of product water flow, pre/post-membrane differential pressure and conductivity transmitter signals
- Chemical reactors / mixing kettles: Interlocked temperature and pressure control based on kettle temperature, internal pressure and raw material feed flow
- Exhaust gas treatment / desulfurization & denitrification: Monitoring of flue gas temperature, differential pressure, reagent flow and acid-base neutralization concentration
Module Advantages
4~20mA wire break detection: Automatic alarm for broken cables or power loss of transmitters
Digital filtering eliminates power-frequency interference from water pumps and fans
8 channels enable simultaneous acquisition of multiple tank and pipeline measuring points to reduce total module quantity
- Mâncare & Băutură / Farmaceutic / Ready Meal Production Lines
Collected Signals
Temperature transmitters (PT100 converted to 4~20mA), tank liquid level, syrup/material flow, filling pressure, vacuum degree
Echipamente
- Sterilizing kettles, cooking pots: Closed-loop multi-point temperature control with interlock shutdown for overtemperature
- Batching and mixing systems: Automatic feeding based on raw material tank level and delivery flow ratio
- Filling and blow molding equipment: Collection of filling pressure and negative vacuum to guarantee filling precision
- Pharmaceutical purified water and mixing tanks: Compliant data logging of liquid level, temperature and differential pressure (GMP traceability)
Matching Strengths
±0.2% FS high precision at room temperature meets process metering requirements; peak hold captures instantaneous pressure fluctuations.
- Ambalare / Imprimare / Cauciuc & Plastics Machinery
Collected Signals
Predominantly 0~10V voltage signals: Servo/inverter speed feedback, tension sensors, mold cavity pressure, melt extrusion pressure
Echipamente
- Vertical / horizontal packaging machines: Film roll tension and heat-seal temperature acquisition for constant-tension closed-loop control
- Injection molding / extrudere: Segmented barrel temperature, melt pressure and hydraulic system oil pressure
- Mașini de imprimat: Roller pressing pressure and ink concentration transmitter signals
- Blow molding and bag-making equipment: Mold temperature and air supply pressure monitoring
Matching Advantages
High-speed 250μs per channel conversion captures rapidly varying tension and pressure; centralized multi-channel acquisition of all analog feedback signals from the whole machine.
- HVAC, Automatizarea clădirilor & Central Air Conditioning
Collected Signals
Temperatură & humidity transmitters (4~20mA), air duct differential pressure, cold/hot water flow, chilled water pressure, CO₂ concentration
Sisteme
Factory central air conditioning, cleanroom air handlers, constant temperature & humidity units for dust-free workshops, fresh air & sisteme de evacuare
Application Purpose
Automatically adjust fan speed and chilled water valve opening based on indoor temperature, humidity and CO₂ concentration for energy-saving coordinated control.
- Energie, Fotovoltaic, Pompa de apa & Fan Stations
Collected Signals
Battery temperature, solar irradiance intensity, pump outlet pressure, water tank liquid level, motor bearing temperature
Scenarii
- PV energy storage cabinets: Multi-point temperature measurement of ambient environment and battery packs
- Constant-pressure water supply pump rooms: Closed-loop variable-frequency constant pressure control via pipeline pressure acquisition
- Air compressor stations: Monitoring and early warning of air tank pressure, exhaust temperature and lubricant oil temperature
- Boiler auxiliary equipment: Feed water flow, furnace negative pressure and flue gas exhaust temperature
- Mașini-unelte, Linii de producție automatizate & Custom Non-Standard Equipment
Collected Signals
Hydraulic oil pressure, cylinder pressure, cutting fluid temperature, 0~10V displacement sensors, vibration transmitters
Echipamente
CNC lathes, linii de asamblare, stamping equipment, automated test fixtures
Funcții de bază
Equipment condition early warning with automatic shutdown for excessively low oil pressure or high temperature; dimensional inspection via displacement signal collection.
- Agricultură, Conservarea apei & Aquaculture
- Aquaculture: Automatic aeration and water exchange interlock based on water dissolved oxygen, water temperature and pond liquid level
- Irrigation & water conservancy: Automatic irrigation control via collection of pipeline flow, pool liquid level and soil humidity transmitter signals
Not Recommended Application Scenarios (Model Selection Pitfall Avoidance)
- Demand for strong isolation between multiple channels: Only the bus side features optocoupler isolation with no inter-channel isolation. For sites with multi-sensor separate grounding or severe interference, prioritize CJ1W-AD041-V2 (channel-isolated model).
- Control cabinets with high voltage and intense electromagnetic fields or dense inverters: External signal isolators must be installed to prevent severe signal drift.
- Mai puțin decât 4 analog measuring points: Select CJ1W-AD041-V1 for lower cost; choose CJ1W-AD161 for high-density 16-point acquisition.
Application Value Corresponding to Core Module Functions
- Wire Break Detection → Prevents circuit faults for 4–20mA transmitters in water treatment and chemical industries
- Digital Average Filter → Anti-interference for on-site water pumps, fans and inverters
- Peak / Valley Hold → Recording of injection melt pressure and instantaneous stamping pressure
- Offset & Gain Calibration → Corrects long-term sensor zero drift to sustain consistent measurement accuracy
- 8-Channel Mixed Signal Compatibility → Supports mixed wiring of voltage and current transmitters on a single module to reduce cabinet module count
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare