Tip de produs: Integrat Senzor de presiune (Comutator de presiune) | Stare: Discontinued by Manufacturer
Omron E8EB series integrated pressure sensor with analog + switching output, positive pressure type, Ieșire NPN.
✅ Specificații de bază
Interval de presiune: 0~1 MPa (0~10 kgf/cm², 0~142 psi)
Alimentare electrică: DC24V
Comutați ieșirea: NPN colector deschis; Max. curent de sarcină 80 mA, Max. voltage DC30V
Linear Analog Output: 1~5 V, Output impedance 20Ω, Min. load resistance 10 kΩ
Timp de răspuns: ≤5 ms
Consumul curent: 20 mA
Port de presiune: RC(PT)1/4
Clasa de protectie: IP54
Temperatura de operare: -10℃~+55℃ (fara glazura); Depozitare: -25℃~70℃
Indicator: LED roșu (lights up when output is ON)
Cablu: Standard 2m lead wire
Media: Dry air, gaz necoroziv (Not suitable for corrosive liquid)
📌 Model Code Explanation (E8EB Series)
E8EB = Series Code
10 = Range 0~1MPa
C = NPN output; Suffix B = PNP (Model E8EB-10B)
01 = 0~0.1MPa; N0 = Vacuum type
🔁 Official Replacement Model: E8F2-B10C
| Articol | E8EB-10C (Model Vechi) | E8F2-B10C (Înlocuire) |
| Interval de presiune | 0~1MPa | 0~1MPa |
| Ieșire | NPN colector deschis + 1~5V linear analog | NPN, dual independent switch outputs + 1~5V linear analog |
| Consumul curent | 20mA | 70mA |
| Curent de sarcină | 80mA | 30mA |
| Ajustare | Potentiometer adjustment, no digital display | Afișaj digital + grafic cu bare, one-touch teaching setup |
| Dimensiuni de montare | Different footprint and mounting holes | Cannot be plug-and-play; bracket and piping need modification |
⚠️ Notă importantă: Direct plug-in replacement is NOT feasible. Capacitate de încărcare, current draw and mounting dimensions differ; PLC wiring logic must be verified.
🧾 Pin Assignment (4-Core Cable)
Maro: DC24V+
Albastru: 0V (GND)
Alb: ON/OFF Switch Output (NPN)
Negru: 1~5V Linear Analog Output
🛠️ Troubleshooting Checklist
- Fără ieșire: Check 24V supply and blue wire ground; confirm pressure exceeds set threshold
- Abnormal analog signal: Load resistance ≥10kΩ; low-resistance loads are prohibited
- LED does not light: Pressure not reaching actuation point, or incorrect hysteresis setting
- Deriva semnalului: Water/oil contamination in air source, out-of-range temperature, or pressure surge exceeding full scale
📎 Supplementary Information
Folosit / second-hand units are still available on the aftermarket; no brand-new original stock
Codul HS de referință: 90262090 (Gas pressure measuring sensor)
Modele alternative: E8F2 series, E8CC series digital pressure sensors
E8EB-10C → E8F2-B10C Retrofit Wiring List (4-core old → 5-core new)
E8EB: 4-miez; E8F2-B10C: 5-miez (dual switch outputs + 1~5V analog), NPN, 0~1MPa, DC24V
Goal: Retain the original circuit: 1 switch signal + 1~5V analog; leave the second output unused and insulated.
- Wire Color Matching Table
| E8EB-10C (Vechi, 4-Miez) | Funcţie | E8F2-B10C (Nou, 5-Miez) | Funcţie | Connection Plan |
| Maro | DC24V+ | Maro | DC24V+ | ✅ Direct connection |
| Albastru | 0V GND | Albastru | 0V GND | ✅ Direct connection |
| Alb | Switch Output OUT1 (NPN) | Alb (OUT1) | Comutați ieșirea 1 (NPN) | ✅ Connect to original PLC input point (keep original pressure signal logic) |
| Negru | 1~5V Analog Signal | Gri | 1~5V Analog Output | ✅ Original black wire → new grey wire |
| — | N/A | Alb (OUT2) | Independent Switch Output 2 (NPN) | ⚠️ Leave unused, wrap with insulation; short-circuit strictly forbidden |
Memento critic: The analog output on E8F2 is the grey wire NOT the white wire, this is the most common wiring mistake. If analog signal is not required, insulate the grey wire separately.
- Procedura de cablare
- Cut off all power; confirm PLC and sensor power circuits are fully de-energized
- Disconnect old sensor terminals and record Brown/Blue/White/Black channel mapping
- Circuitul de alimentare: Brown to Brown, Blue to Blue (Alimentare DC24V)
- Switch signal: Original white wire → E8F2 OUT1 white wire (match original PLC logic)
- Analog signal: Original black (1~5V) → E8F2 grey wire
- E8F2 OUT2 white wire: Seal with heat-shrink tube/insulation tape, keep isolated
- Inspect wiring for short circuits and exposed copper before powering on.
- Parameter Differences & PLC Program Verification Checklist (Obligatoriu)
| Articol | E8EB-10C | E8F2-B10C | Retrofit Risk Point |
| Current Draw | 20mA | 70mA | Recheck 24V power supply capacity; insufficient margin will cause voltage drop |
| Switch Load Capacity | 80mA | 30mA | PLC digital input is fine; if the original circuit drives a relay directly, the relay cannot be reused; reduce curentul de sarcină |
| Thread Port | RC(PT)1/4 | R(PT)1/8 | Must install reducing adapter; cannot thread directly |
| Montare | Original bracket | 28panou mm / E89-F3 bracket | Hole positions do not match; new holes or adapter plate required |
| Metoda de setare | Potentiometer adjustment | Meniu / teaching setup | Pressure setpoints and hysteresis must be reconfigured; old potentiometer values are invalid |
| Output Channels | Single switch | Two independent switches | Program only uses OUT1; disable OUT2 |
- Power-On Commissioning Sequence
- No-load power-on first; confirm E8F2 digital display lights up normally
- Enter menu: Set actuation mode, pressure setpoint and hysteresis to match the original E8EB values
- Pressurize and test: Verify OUT1 triggers PLC input correctly
- Analog test: 0MPa ≈1V, 1MPa≈5V; confirm linear reading on PLC analog channel
- Stabilize signal: Enable anti-chatter filter to prevent false triggering caused by air pressure fluctuation.
- Depanare rapidă
No analog reading: Grey wire disconnected or misconnected to OUT2 white wire
Cannot drive load: Load current exceeds 30mA rating
Nicio acțiune de comutare: Parameters not reconfigured; factory default values differ from old sensor
Scurgeri de aer: Thread mismatch; missing reducing adapter
Full Commissioning Procedure: E8EB-10C Upgrade to E8F2-B10C (Match Original System Logic)
Objective: OUT1 replaces the old E8EB switch point; grey wire 1~5V analog keeps the original PLC analog channel; OUT2 remains unused.
Butoane: SET (Confirm/Enter), Up ▲, Down ▼; Press and hold SET for 2s to enter main menu; short press SET for pressure setting.
Pas 1: Pre-Power Check (Prevent PLC Input Burnout)
- Verificați cablarea: Maro=24V+, Albastru=0V, White=OUT1, Grey=Analog, OUT2 white wire fully insulated
- Load check: E8F2 NPN output max. 30mA. Do not drive relays directly. Add an intermediate relay if the old circuit had a relay load
- Conducte: Install PT1/8 to PT1/4 reducing adapter with thread sealant; test for air leakage before commissioning
- Air source: Use dry compressed air free of excessive water and oil; working pressure cannot exceed 1MPa full scale
- Partea PLC: Analog input impedance ≥10kΩ; low-resistance loads are prohibited.
Pas 2: No-Load Power On & Resetare la zero (Zero Pressure Condition)
- Power the sensor alone, without air pressure applied, wait for display stabilization
- Zero point reset (zero pressure calibration): Press ▲+▼ simultaneously to reset zero reading
Nota: Zero reset must be done at zero pressure; calibration under pressure will lead to permanent drift.
Pas 3: Basic Parameter Setup (Hold SET 2s to enter main menu)
- Unitate (unt): Select MPa (consistent with old sensor; kPa is also acceptable)
- Modul de operare (m-a): Select HYS (Hysteresis Mode, same as E8EB); avoid Window Mode
- Logica de ieșire (ope): NPN, Deschis normal (NU); output ON when pressure exceeds set value
- Anti-chatter Filter: Set to STND (Standard); select longer filtering if air pulsation is severe to avoid signal chattering
- Salva: Hold SET 2s to return to measurement screen.
Only configure OUT1; leave OUT2 parameters unchanged as it remains unused.
Pas 4: Pressure Setpoint Configuration (2 Opțiuni: Manual Input / Teaching Mode; Teaching is Recommended)
Opțiunea A: 2-Point Teaching (Best for replicating old E8EB trigger points)
- Short press SET to enter pressure setting → select OUT1 → select 2-point teaching
- Slowly raise pressure to ON actuation pressure, stabilize and press SET to save the ON point
- Slowly reduce pressure to OFF release pressure, stabilize and press SET to save hysteresis OFF point
- Hold SET to save and exit.
Exemplu: Original E8EB turns ON at 0.5MPa and OFF at 0.4MPa; teach these two pressure values directly on site.
Opțiunea B: Manual Value Entry (If original setpoints are known)
- Short press SET → enter OUT1 ON value → adjust value with ▲▼
- Press SET to switch to OUT1 OFF value → set hysteresis (OFF < PE)
- Press SET again to jump to OUT2; skip without modification
- Hold SET to save and exit.
Recommended hysteresis: Keep consistent with original setting to avoid frequent cycling; factory default hysteresis = 3%FS (30kPa for 0~1MPa range).
Pas 5: Switch Output Test (OUT1, PLC Digital Input)
- Gradually increase pressure; check E8F2 OUT1 indicator + PLC input: ON when pressure ≥ setpoint
- Gradually reduce pressure; input turns OFF when pressure drops below OFF threshold
- Repeat 3 times to confirm:
No flickering or intermittent signal
Trigger action fully consistent with the old sensor
No premature or delayed switching
Depanare: Frequent chattering → increase filter time and hysteresis; no action → reverse NO/NC output logic.
Pas 6: 1~5V Analog Channel Calibration (Grey Wire, Pas critic)
Gamă: 0~1MPa = 1V ~ 5V
0MPa: Theoretical output ≈1.0V
0.5MPa: Theoretical output ≈3.0V
1.0MPa: Theoretical output ≈5.0V
Etape de punere în funcțiune:
- Zero pressure: Confirm PLC analog reading ≈1V
- Pressurize to 0.5MPa and cross-check reading
- Full scale 1MPa: Verify output ≈5.0V
⚠️ Notă importantă: E8F2 analog output is pre-calibrated for linearity. No re-calibration on PLC side is required. If deviation occurs, redo zero reset first and check load resistance.
Pas 7: Full System On-Line Test (Automatic Machine Cycle)
- Switch equipment to automatic mode; verify pressure interlock and alarm logic work correctly
- Run continuously for 5~10 minutes; confirm output stays stable under pressure fluctuation
- Record actuation pressure, hysteresis and filter parameters in engineering change records
- Add pressure buffer/throttle on the air inlet if pressure surge occurs to prevent overpressure damage.
Pas 8: Tabel de depanare a erorilor
| Simptom | Cauza de bază | Remediu |
| OUT1 never switches ON | ON setpoint too high; NO/NC logic reversed | Recheck set value; modify ope output mode |
| Switch signal flickers continuously | Air source pulsation; timp de filtrare prea scurt | Extend response filter; increase hysteresis value |
| Analog signal stuck fixed at 1V | Grey wire broken/disconnected; load resistance too low | Inspect grey wire; ensure PLC input resistance ≥10kΩ |
| Zero reading drifts constantly | Zero reset performed under pressure; air contains water/oil | Re-zero at zero pressure; install air filter for moisture removal |
| Output stays permanently ON after power-up | OFF value set higher than ON value (parameter reversed) | Ensure OFF pressure < ON pressure |
| PLC input channel burned out | Load current exceeds 30mA rating | Remove direct relay drive; add intermediate relay |
Full Model List of OMRON General-Purpose Gas Pressure Sensors (Pneumatic / Compresor / Vid, Dry Air Only)
Nota: All models are Gauge Pressure. Ieșire: NPN/PNP switch + 1~5V analog. Split into Discontinued Legacy Models + Official Replacement Models, suitable for spare part replacement, BOM & foreign trade.
Definiția sufixului: C=NPN; B=PNP; A01=0~100kPa; B10=0~1MPa; AN0=Vacuum 0~-101kPa.
- E8EB Series (Fără afișaj, reglaj potențiometru, DISCONTINUED)
4-core lead wire, RC1/4 thread, single switch + 1~5V analog; 20mA current draw, max. load 80mA.
| Model | Interval de presiune | Ieșire |
| E8EB-01C | 0~100kPa (0.1MPa) | NPN |
| E8EB-01B | 0~100kPa (0.1MPa) | PNP |
| E8EB-10C | 0~1MPa | NPN (Main Model in This Retrofit) |
| E8EB-10B | 0~1MPa | PNP |
| E8EB-N0C2B | 0~-100kPa Vacuum | NPN |
| E8EB-N0B2B | 0~-100kPa Vacuum | PNP |
- E8F2 Series (Afișaj digital, official replacement for E8EB/E8CC, DISCONTINUED)
5-cablu miez, PT1/8 thread, dual independent switch outputs + 1~5V analog; 70mA power consumption; single channel max. load 30mA; one-touch teaching programming.
| Model | Interval de presiune | Ieșire |
| E8F2-A01C | 0~100kPa | NPN (E8EB-01C Replacement) |
| E8F2-A01B | 0~100kPa | PNP |
| E8F2-B10C | 0~1MPa | NPN (Direct replacement for E8EB-10C) |
| E8F2-B10B | 0~1MPa | PNP |
| E8F2-AN0C | 0~-101kPa Vacuum | NPN |
| E8F2-AN0B | 0~-101kPa Vacuum | PNP |
- E8CC Series (Slim digital type, predecessor of E8EB, DISCONTINUED)
With digital display, single switch + 1~5V analog; Montare pe șină DIN; replaced by E8F2.
| Model | Interval de presiune | Ieșire |
| E8CC-A01C | 0~100kPa | NPN |
| E8CC-B10C | 0~1MPa | NPN |
| E8CC-AN0C | 0~-101kPa Vacuum | NPN |
- E8MS / E8M Split Type (Sensor Head + Controlor, DISCONTINUED)
Pure 1~5V analog signal without built-in switch; requires E8M controller for multi-channel pressure acquisition.
| Model | Interval de presiune | Tip |
| E8MS-01 | 0~100kPa | Positive Pressure Probe |
| E8MS-10 | 0~1MPa | Positive Pressure Probe |
| E8MS-N0 | 0~-101kPa Vacuum | Vacuum Probe |
| E8MS-N1 | -101~101kPa Compound Pressure | Compound Pressure Transducer |
| E8M-10 | 0~1MPa | E8M Independent Probe |
| E8M-N0 | 0~-101kPa Vacuum | Vacuum Probe |
| E8M-A1 | 0~1000Pa | Micro Differential Pressure |
- E8AA Series (Stainless Steel Diaphragm Special Model, DISCONTINUED)
Limited use for liquid / slightly corrosive gas applications.
| Model | Interval de presiune |
| E8AA-M05 | 0~500kPa |
| E8AA-M10 | 0~1MPa |
- E8Y / E8Y-L Micro-Pressure Sensors (Differential Pressure for Duct & Ventilator, Not General Pneumatic Type)
Pa-level low pressure (200Pa ~5kPa); some models with 4-20mA output; used for air duct and filter differential pressure monitoring only.
✅ Cross Reference Table (Spare Part Replacement Priority)
| Model Vechi | Înlocuire recomandată | Diferențele cheie |
| E8EB-01C | E8F2-A01C | PT1/8 thread, ieșiri duale, load current reduced to 30mA |
| E8EB-10C | E8F2-B10C | Full retrofit plan covered above |
| E8EB-N0C2B | E8F2-AN0C | Vacuum pressure type |
| E8CC-A01C | E8F2-A01C | Different mounting footprint |
📌 General Notes
- Media: Dry non-corrosive air; Not for liquid or strong corrosive gas
- Analog Output Standard: 1~5V (1V at zero pressure, 5V at full scale)
- Thread Spec: E8EB = RC1/4; E8F2 = R1/8; reducing adapter is mandatory for retrofit
- Alimentare electrică: DC24V
- All listed models are discontinued; only surplus stock & unități second-hand disponibile. New projects shall select the latest OMRON E8F series.