Releu cu stare solidă OMRON G3PA-240B-VD - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

electric/

Releu cu stare solidă OMRON G3PA-240B-VD

The Omron G3PA series single-phase solid state relay (SSR) with integrated heat sink, zero-crossing turn-on, Montare pe șină DIN, directly driven by PLC DC signals. Widely used for non-contact switching control of heating elements, fans and lamp loads. Notă importantă: Acest model este întrerupt. Only stock units are available or alternative models should be selected. Model ...

  • Detalii despre produs

The Omron G3PA series single-phase solid state relay (SSR) with integrated heat sink, zero-crossing turn-on, Montare pe șină DIN, directly driven by PLC DC signals. Widely used for non-contact switching control of heating elements, fans and lamp loads.

Notă importantă: Acest model este întrerupt. Only stock units are available or alternative models should be selected.

  1. Definiția codului modelului

G3PA: Numele seriei, solid state relay with integrated heat sink

2: Monofazat, AC24~240V output specification

40: Rated load current 40A

B: Built-in heat sink

VD: DC5~24V DC input control, opto-triac isolation, zero-crossing turn-on

  1. Specificații electrice de bază

✅ Input Side (Control Terminals +A1, -A2)

Tensiunea de control: DC5~24V, operating range DC4~30V

Maximum input current: 7mA (directly drivable by PLC output point)

Operating voltage ≤DC4V; Reset voltage ≥DC1V

Izolare: Opto-triac isolation

✅ Output Side (Terminale de încărcare 1, 2)

Rated load voltage: AC24~240V, operating range AC19~264V (50/60Hz)

Rated load current: 40A @40℃; derate to 36A for dense side-by-side mounting

Surge withstand current: 440O (60Hz, 1 ciclu)

I²t: 1260 A²s

On-state voltage drop: ≤1.6V RMS

Switching characteristic: Zero-cross turn-on, reduces switching surge

Operate / release time: Within half cycle of load power supply +1ms

✅ Environmental & Mecanic

Temperatura de functionare: -30℃ ~ +80℃ (fara condens)

Montare: DIN rail or screw mounting; screw type terminals

Dimensiuni: W47 × H100 × D100 mm

Dielectric strength between input and output: AC4000V

  1. Scenarii tipice de aplicare

Temperature control: Heating tubes, ceramic heaters, infrared heating (cele mai frecvente)

Iluminat: High power lamp banks, halogen lamps

Motoare: Small single-phase fans (rezistiv / weakly inductive load preferred)

Nota: Inductive loads and loads with large starting inrush current require additional varistor and RC snubber protection.

  1. Ghid de cablare
  2. +A1, -A2: DC control signal, good polarity tolerance. It is recommended to connect PLC positive output to A1.
  3. Terminale 1, 2: Connected in series to AC load circuit, L/N non-polarity.
  4. Circuit amortizor RC + varistor connected in parallel at output terminals for inductive loads.
  5. Derate current and reserve heat dissipation clearance when multiple SSRs are installed side by side on DIN rail.
  6. Replacement Models for Discontinued Product
  7. Upward replacement within same series: G3PA-260B-VD (60O, DC5~24V input). Same pin layout with higher capacity.
  8. New generation alternative: G3PE series G3PE-245B, 45A DC control, Montare pe șină DIN, înlocuire directă.
  9. Domestic compatible SSR: 40A solid state relay, DC5-24V input, AC240V, zero-cross type with integrated heat sink.
  10. Depanare comună
  11. Input LED does not light: Check PLC output voltage and broken wiring; insufficient input current to drive SSR.
  12. LED lights but load does not turn on: Borne de ieșire slăbite, sarcina sparta; internal triac damage.
  13. Load remains energized after control signal removed: SSR short-circuit failure (common for heating loads), usually caused by overheating or surge breakdown.
  14. Declanșări false frecvente: Control cable runs in parallel with power cable causing interference; connect 1000pF anti-interference capacitor at input side.
  15. Note de selecție
  16. Sarcini rezistive: Derate to 0.7 times rated current for selection.
  17. Heating loads have low cold resistance with large starting inrush current, este necesară o marjă de curent suficientă.
  18. Further derate when ambient temperature >40℃ or densely mounted.
  19. Solid state relay has no mechanical contacts, cannot serve as safety disconnect switch. Circuit breaker must be fitted on main circuit.

OMRON G3PA-240B-VD (40A DC to AC Zero-cross SSR) Cazuri tipice de aplicare

Product Recap: Integrated heat sink, Montare pe șină DIN, DC5~24V input, AC24~240V 40A, zero-cross turn-on. Directly driven by PLC, mainly suitable for resistive loads. RC+MOV snubber required for inductive loads.

Caz 1: Temperature Control System – Industrial Heating Tube Control (Most Popular)

Aplicație

Cuptoare, hot presses, plastic dryers, mold temperature machines, food baking lines, single-phase 220V heating tubes, max power ~8kW (220V×40A), PID power regulation by PLC + temperature controller.

Configurarea sistemului

  1. Controla: Transistor output DC24V from temperature controller / PLC connected to A1/A2 of G3PA; zero-cross switching reduces grid harmonic distortion.
  2. Circuitul principal: AC220L → SSR terminal 1; Terminal 2 → heating tube → N.
  3. Protecţie: 3P circuit breaker + fast fuse at upstream; thermocouple over-temperature protection is recommended for heating tubes.
  4. Snubber: RC optional for resistive loads; 470V varistor is recommended for high power applications to absorb grid surge.

Derating Recommendation

Continuous long-term operation: Load current controlled within 28A (0.7×rating); reduce to 24A for side-by-side multi-unit installation.

Avantaje

Contactless operation, no contact erosion even under frequent switching (several times per second), higher PID temperature control accuracy.

Capcană comună

Heating tubes have large cold-state inrush current. Continuous full-current operation tends to break down SSR; do not treat rated 40A as continuous operating current.

Caz 2: High Power Halogen / Infrared Lamp Bank Control

Aplicație

UV curing lamps, infrared heating lamps, industrial inspection light sources, infrared radiation panels for drying lines, 220V AC lamp banks.

Configurarea sistemului

PLC DC24V output drives SSR; lamp load connected in parallel to SSR output terminals.

Halogen lamp has extremely low cold resistance, inrush current at switch-on can reach 8~10 times rated current.

Precauții

  1. Zero-cross G3PA is well suited for lamp loads, turn-on at voltage zero point to reduce inrush.
  2. Heavy derating is mandatory: lamp load at 0.4~0.5 times SSR rating; load ≤20A for this 40A SSR.
  3. NTC surge limiting thermistor in series is recommended.

Avantaje

Comutare silențioasă, fără arc electric sub pornire/oprire frecventă, potrivit pentru sursele de lumină automate ale liniilor de producție.

Caz 3: Fani / Motoare mici monofazate (Sarcina inductivă)

Aplicație

Încălzirea prin conducte de aer se potrivește cu ventilatoare, ventilatoare de răcire de mare putere din cabinet, mici ventilatoare monofazate de transport pentru control continuu pornire-oprire.

Aceasta este sarcina inductivă, Snubber RC + Trebuie instalat varistorul MOV (100Ω/2W +0,1μF/400VAC +470V varistor).

Sistem

PLC controlează SSR pentru pornirea/oprirea ventilatorului; întrerupător de circuit montat în amonte de SSR.

Prescripţie

Nu este potrivit pentru rotirea frecventă înainte/înapoi a motorului; nu se aplică pentru motoarele de mare putere cu supratensiune mare de pornire.

EMF invers generat la oprirea motorului poate deteriora cu ușurință SSR, Snubber RC este esențial.

Caz 4: Bancă de supape solenoid, Unitatea bobinei contactorului AC (Sarcină inductivă mică)

Aplicație

Echipamente de ambalare, linii de producție pneumatice, bobine solenoide multiple AC220V paralele controlate central de PLC.

Configurarea sistemului

Ieșirea SSR acționează mai multe bobine solenoide paralele AC220V; RC+MOV conectat în paralel la bornele SSR.

Note

Bobina solenoidului este inductanță, generează un vârf de tensiune înaltă la oprire; curentul total de sarcină nu poate depăși 40A.

Pot apărea vibrații minore ale solenoidului după oprirea SSR din cauza curentului de scurgere RC. Soluţie: conectați o rezistență de purjare de 10kΩ/5W la bornele de sarcină.

Caz 5: 220Role motorizate V AC pentru linii transportoare / Echipamente de transport mici

Aplicație

Linii de sortare logistică, linii transportoare de ambalare, control start-stop al rolelor motorizate monofazate de 220V.

Puncte cheie

Amortizor RC+MOV obligatoriu pentru sarcina inductivă a motorului; nu este potrivit pentru jogging frecvent cu impact puternic, aplicabil pentru funcționarea pe termen lung cu interval lung de pornire-oprire.

Caz 6: Circuitul de încălzire a camerei de testare a mediului

Aplicație

Temperatura constanta & camera de umiditate, camera de testare a îmbătrânirii, circuit rezistiv de încălzire cu reglare continuă a puterii PID.

Configurarea sistemului

PID DC24V output from temperature controller drives G3PA; multi-section heating zone control with multiple G3PA mounted side by side on DIN rail.

Note cheie

Derate current and reserve heat dissipation clearance for side-by-side installation; ambient temperature around SSR must not exceed 60℃.

Load Selection Summary Table

Tip de încărcareRecommended DeratingRC+MOVObservații
Resistive heating tube0.7×ratingOpțional (MOV recommended)Most compatible, utilizat pe scară largă
Halogen / Infrared lamp0.4~0.5×ratingRecomandatExtreme cold inrush current
Single-phase fan, small motor (inductiv)0.6×ratingObligatoriuHigh risk of back EMF breakdown at turn-off
AC220V solenoid coil0.6×ratingObligatoriuLeakage current may cause minor false actuation

General Usage Prohibitions for G3PA-240B-VD

  1. ❌ Not for large air compressors, high-power single-phase motors (excessive starting surge)
  2. ❌ Cannot act as safety disconnect switch, independent circuit breaker required for main circuit
  3. ❌ Nu este potrivit pentru sarcini inductive de înaltă frecvență de înaltă tensiune; riscul de defectare a unui scurtcircuit triac (SSR blocat, sarcina alimentata continuu, riscul de incendiu la supratemperatură în sistemele de control al temperaturii)
  4. ❌ Este necesară o reducere suplimentară a curentului atunci când temperatura ambientală >60℃

G3PA-240B-VD Lista de erori în funcție de scenariul aplicației

Model: Omron G3PA-240B-VD, 40O intrare DC cu cruce zero SSR; principalele moduri de eroare: scurtcircuit permanent la iesire (cele mai periculoase), incapacitatea de a porni, falsă declanșare intermitentă.

Precauție: Dacă SSR eșuează scurtcircuitat, sarcina rămâne alimentată continuu. Riscul de incendiu la supratemperatură este mare pentru sistemele de încălzire. Pe circuitul principal trebuie montată o protecție independentă la supra-temperatură.

Caz 1: Tub de încălzire / Cuptor, Mașină de temperatură a matriței (Sarcină rezistivă, Cele mai comune)

Defecțiune1: SSR scurtcircuitează după o perioadă de funcționare, încălzirea nu se oprește niciodată

Simptom: Semnalul de control PLC a fost eliminat, nicio intrare la A1/A2, heating tube remains heated; SSR housing very hot.

Cauza de bază:

1) Long-time full current operation without 0.7 derating; insufficient heat dissipation with side-by-side mounting.

2) Aging heating tube with partial short circuit, surge current breaks triac.

3) Grid voltage spike without varistor protection.

Remediu: Control load current ≤28A; install 470V varistor; periodically test insulation of heating tube; add independent over-temperature thermostat for hard cut-off.

Fault2: Large temperature fluctuation under PID control, intermittent heating

Simptom: Temperature controller output normal, heating cuts in and out randomly.

Cauza de bază:

1) Insufficient output current from PLC, voltage drop on cable.

2) Loose SSR terminals, contact resistance generates heat.

3) Oxidized wiring of heating tube, contact slab.

Remediu: Strângeți bornele (torque 0.8~1.0N·m); check driving capacity of PLC transistor output; replace aged heating tube.

Fault3: SSR indicator LED on, but no heating

Cauza de bază: Broken output circuit, burnt heating tube; open-circuit damage of internal triac.

Remediu: Measure resistance of heating tube after power-off; measure AC voltage across SSR output terminals.

Caz 2: Halogen / Infrared Lamp Bank

Defecțiune1: SSR damaged immediately upon lamp switch-on

Simptom: SSR burns out right after lamp activation even if average current is low.

Cauza de bază: Extremely low cold resistance of halogen lamp, inrush current reaches 8~10 times rated; zero-cross turn-on still cannot eliminate huge surge without derating.

Remediu: Limit load current to 0.4~0.5×SSR rating; fit NTC surge suppression thermistor in lamp circuit; prefer lamp-specific SSR.

Fault2: Lamp flickering

Cauza de bază: Fluctuating supply voltage; lamp aging; internal component aging of SSR.

Remediu: Replace aged lamps; verify power supply stability.

Caz 3: Single-phase Fan, Small Motor (Sarcina inductivă)

Defecțiune1: SSR breaks down every time fan stops

Simptom: Fan runs normally, SSR eșuează când semnalul de control se oprește.

Cauza de bază: Inductanța înfășurării motorului generează EMF în spate ridicat la oprire; RC+MOV nu este montat.

Remediu: Instalați snubber RC (100Ω/2W +0,1μF/400VAC în serie) +470V varistor, cablu direct aproape de bornele SSR.

Fault2: Ventilatorul se rotește încet după oprirea SSR

Simptom: Ventilatorul nu se oprește complet după îndepărtarea semnalului PLC, rotație cu viteză mică.

Cauza de bază: Curentul de scurgere introdus de amortizorul RC, tensiune slaba indusa pe infasurarea motorului.

Remediu: Montați o rezistență de purjare de 10kΩ/5W peste bornele motorului; sau utilizați un contactor mecanic pentru o întrerupere completă.

Caz 4: Baterie de bobine de solenoid AC220V (Sarcina inductivă)

Defecțiune1: Solenoidul trage la întâmplare (declanșare falsă)

Simptom: Solenoid zbârnâie ocazional sau acţionează fără semnal de ieşire PLC.

Cauza de bază: Curent de scurgere RC; interferențe electromagnetice atunci când cablul de control este paralel cu cablul de alimentare; fir de control excesiv de lung.

Remediu: Montați o rezistență de purjare de 10 kΩ/5 W peste bornele de sarcină; rutare separată pentru cablurile de comandă și alimentare; montați condensator anti-interferență de 1000pF la intrare.

Fault2: SSR deteriorat după mai multe cicluri de comutare

Cauza de bază: Spike de înaltă tensiune de la oprirea bobinei fără protecție RC+MOV.

Remediu: Instalați RC+MOV; nu conectați solenoizi excesivi în paralel, reduceți curentul total la 0,6 × rating.

Caz 5: Rolă motorizată transportor

Defecțiune1: Pornire-oprire instabilă a rolei, eșec ocazional de pornire

Simptom: Rola uneori nu pornește chiar și atunci când semnalul de control este trimis către SSR.

Cauza de bază: Valoare mare de pornire a motorului; marjă SSR insuficientă; voltage drop on cable.

Remediu: Reduceți capacitatea de încărcare; verificați gabaritul cablului de alimentare; RC+MOV obligatoriu pentru sarcina inductivă.

Fault2: Supraîncălzirea severă a SSR

Cauza de bază: Funcționare cu curent greu de lungă durată; disipare slabă a căldurii pentru mai multe SSR montate unul lângă altul pe șină DIN.

Remediu: Măriți distanța de montare între unitățile SSR; reduce curentul de sarcină; adăugați un ventilator de răcire auxiliar dacă este necesar.

Defecte generale comune (Aplicabil tuturor scenariilor)

  1. LED-ul indicator de intrare la A1/A2 nu se aprinde

Secvență de depanare:

1) Verificați ieșirea PLC, confirmați prezentul DC24V.

2) Cablu de control rupt, polaritate inversată (tolerat într-o oarecare măsură, polaritatea inversă pe termen lung deteriorează LED-ul de intrare).

3) Circuit de intrare ars al SSR.

  1. LED de intrare normal, nicio acțiune de ieșire

Depanare: Alimentare principală disponibilă; terminale de ieșire slăbite; open-circuit damage of internal triac.

  1. Defecțiune aleatorie a SSR la temperatură ambientală ridicată

Cauza de bază: Temperatura ambientală> 60℃, disiparea căldurii se deteriorează, deriva caracteristică a dispozitivului.

Remediu: Îmbunătățiți ventilația cabinetului; reduceți în continuare curentul; montați SSR departe de componentele care generează căldură.

  1. Acționare falsă aleatorie a SSR cauzată de interferență

Simptom: SSR pornește/oprește neregulat în timpul funcționării echipamentului.

Contramăsuri:

1) Canal de cablu separat pentru semnalul de control și cablul de alimentare, evitați rutarea paralelă lungă.

2) Montați releul de izolare pe partea de ieșire a PLC-ului.

3) Conectați condensatorul ceramic de înaltă tensiune de 1000pF la intrare.

Procedura de diagnosticare rapidă a erorilor (Pentru punerea în funcțiune la fața locului)

  1. Deconectați alimentarea principală CA, mențineți alimentarea de control DC24V pornită, verificați dacă LED-ul de intrare SSR urmează semnalul PLC.
  2. Opriți, Măsurați rezistența la bornele de ieșire SSR:

Stare normală (nici un semnal de intrare): Rezistență ridicată, Nivel mega-ohm.

Rezistență aproape de starea conducătoare fără intrare: SSR scurtcircuitat, NU energizați!

  1. Porniți cu sarcină, measure AC voltage across SSR output terminals:

Cu semnal ON: Căderea de tensiune pe SSR ≤1.6V.

Cu semnal OFF: Tensiune la SSR aproape de AC220V.

  1. Verificați temperatura carcasei SSR; îmbunătățește derating-ul sau disiparea căldurii dacă temperatura depășește 70℃.

Reguli de siguranță

  1. Defecțiunea de scurtcircuit este modul de defecțiune tipic al acestui SSR. Pentru aplicațiile de încălzire trebuie prevăzută o protecție mecanică independentă la supratemperatură; nu vă bazați doar pe PLC și SSR.
  2. Nu efectuați teste pe termen lung fără RC+MOV pentru orice sarcină inductivă.
  3. SSR nu trebuie utilizat ca întrerupător de izolare de siguranță; întrerupătorul principal trebuie deschis pentru întreținerea echipamentului.

Prev: