Full Order Code: UNO-PS/2AC/24DC/90W/C2LPS
Phoenix Contact UNO POWER Series 2-Phase Input Sursă de alimentare pe șină DIN
✅ Key Specifications
Intrare: 2-phase AC 400~500 V AC (Wide range: 264–575 V AC)
Ieșire: 24 În DC, curent nominal 3.75 O, 90 W
Adjustable output voltage: 24~28 V DC (via potentiometer)
Output ripple: <50 mVpp
Protecție la supratensiune (OVP): ≤35 V DC
No-load power consumption: <0.7 W
Power factor cosφ: 0.48
Clasa de protectie: IP20
Montare: NS35 DIN rail
Temperatura de functionare: -25℃ ~ +70℃; derating 2.5% per Kelvin above 55℃
Terminale: Screw-type clamping terminals
C2LPS = NEC Class 2 output certification + hazardous area approval (Clasa I, Division 2, T4). The output circuit can be wired per Class 2 requirements without extra isolation or protective sheathing, suitable for powering PLCs, sensors and valve islands in explosion-proof cabinets.
No parallel or series connection allowed
✅ Typical Applications
Control cabinets with 400V two-phase power supply, hazardous locations, construction machinery, HVAC, wind turbine auxiliary control systems; power supply for PLCs, comutatoare de proximitate, solenoid valves and HMIs.
Important distinction: Unlike conventional single-phase 220V UNO power supplies, this model is a high-voltage two-phase input version, which is frequently misselected on site.
✅ Replacement Reference
Single-phase counterpart in the same series: 2902994 (UNO-PS/1AC/24DC/90W/C2LPS), input range 85–264 V AC. Do not interchange the two models.
For higher power with the same structure: UNO 150W & 240W two-phase variants.
✅ Troubleshooting Guide
- DC OK indicator off: First verify two-phase input voltage. The unit will not start under phase loss or input voltage below 264 V și.
- Excessive voltage drop under load: Check for overcurrent or temperature-induced derating.
- Frequent protection trips: Load short circuit or output earth fault. Clasă 2 models feature highly sensitive short-circuit protection.
PHOENIX 2904371 (UNO-PS/2AC/24DC/90W/C2LPS) Manual de instalare
Safety Precondition: Indoor cabinet mounting only, Clasament IP20. C2LPS stands for Class 2 output plus Class I Division 2 certificare pentru zone periculoase. All installation in explosive environments must comply strictly with ISA-12.12.01 standards.
- Prezentare generală a produsului
Comanda nr.: 2904371
Serie: UNO POWER 2-phase DIN rail power supply
Intrare: 2-phase AC 264–575 V (400V two-phase, NOT single-phase 220V)
Ieșire: 24 În DC, 3.75 O / 90 W, adjustable 24–28 V
Montare: NS35 DIN rail (EN60715), horizontal installation
Housing width: 55 mm
- Cerințe de autorizare (Mandatory for Heat Dissipation)
Side-by-side horizontal installation: 0 mm minimum clearance (units may be mounted tightly together)
Vertical stacking: Minimum 30 mm upper and lower clearance for cooling air flow
No upside-down or side mounting; only horizontal installation with terminals facing forward/downward
Do not install adjacent to heat-generating components (contactoare, rezistențe de frânare); high ambient temperature will trigger power derating
Altitude derating: Power rating and insulation voltage must be reduced above 2000 m elevation
- Instalare șină DIN & Îndepărtarea
- Hook the top latch onto the NS35 rail first
- Press down the unit until the latch clicks securely into place
- Îndepărtarea: Insert a flat screwdriver into the bottom latch tab, pry upward to release the lock and pull the unit off the rail
Rezistenta la vibratii: Compliant with industrial cabinet vibration standards; no extra locking screws required once clipped firmly.
- Specificații de cablare (M3 Screw Terminals)
Tip terminal: Screw clamping terminals
Dimensiunea conductorului: Solid wire 0.2–2.5 mm²; stranded wire 0.2–2.5 mm²; AWG24~AWG14
Strip length: 8 mm
Cable temperature rating: ≥75℃ for ambient <55℃; ≥90℃ for 55~70℃ ambient
Cuplul de strângere: 0.5–0.7 Nm (evitați strângerea excesivă pentru a preveni deteriorarea firului)
Definiția terminalului (Critic: Two-phase input, no neutral N!)
Input terminals: L1, L2 (two-phase 400V AC, neutral N is not connected); PE protective earth terminal
Output terminals: +24 V, 0 V (24 În DC)
Adjustment potentiometer: ADJ (24~28 V fine-tuning; factory preset to 24 V)
Indicator: DC OK (green light ON = normal output; OFF = no output or protection active)
⚠️ Critical Warning: This is a 2-phase AC power supply. Never wire it as a single-phase L+N unit; incorrect wiring will cause failure or permanent damage.
- Wiring Sequence (Lockout-Tagout Safety Procedure)
- Confirm upstream circuit is de-energized and apply lockout-tagout
- Connect PE protective earth first (reliable earthing is mandatory)
- Wire the two-phase input lines L1/L2
- Terminate the 24V DC load cables
- Inspect for short circuits and earth insulation; confirm no shorted load circuits
- Apply power and verify the DC OK green LED illuminates; trim the ADJ potentiometer to set target output voltage
- Clasă 2 (C2LPS) wiring rule: Output cabling shall follow NEC Class 2 specifications; no shared trunking with high-voltage power cables without isolation barriers.
- Funcții de protecție & Diagnosticarea defecțiunilor
Protecție la scurtcircuit: Constant current limiting. Clasă 2 versions feature high sensitivity; short-circuit triggers immediate shutdown, auto-recovery after fault removal.
Protectie la suprasarcina: Current exceeding 105% rated value activates current limiting
Protecție la supratensiune (OVP): Output shuts down above 35 În DC
Thermal protection: Over-temperature shutdown; auto-restart after cooling down
Subtensiune / pierdere de fază: No start-up if input voltage drops below 264 V și; DC OK light remains off.
- de mediu & Restricții de instalare
Temperatura de functionare: -25℃ ~ +70℃; 2.5%/K power derating above 55℃
Umiditate: 5%~95% fără condensare
Forbidden applications: Outdoor direct mounting, dusty/corrosive atmospheres, water splash exposure
Explosion-proof installation (Class I Div.2 T4): Cabinet-only mounting; external wiring must not create ignition sources, comply with flameproof/enclosure standards.
- Paralel & Series Connection
❌ This model does NOT support parallel current expansion or series voltage boosting. Select the QUINT series if multi-unit parallel operation is required.
- EMC & Legare la pământ
The PE terminal must connect securely to cabinet protective earth; floating earth is prohibited
Upstream overcurrent protection recommendation: C-curve MCB, 1 A or 2 O (for 400V two-phase circuit)
Clasă 2 output circuits normally do not require additional fuses; dacă este necesar, implement UL1310 Class 2 current-limiting designs.
- Commissioning Checklist
Unit fully clipped onto DIN rail with no play
PE earth connection solid and reliable
L1/L2 two-phase input voltage stays within 264–575 V AC
No short circuit or earth fault on output wiring
DC OK green LED stays steady ON after power-up
Measured output voltage matches the set value
30 mm vertical cooling clearance is maintained top and bottom
III. UNO-PS Full Model List
3.1 UNO-PS / 1AC Single-phase Standard Models (24V Output)
| Comanda nr. | Model complet | Putere | Curent nominal |
| 2902991 | UNO-PS/1AC/24DC/30W | 30 W | 1.25 O |
| 2902992 | UNO-PS/1AC/24DC/60W | 60 W | 2.5 O |
| 2902993 | UNO-PS/1AC/24DC/100W | 100 W | 4.2 O |
| 1088851 | UNO-PS/1AC/24DC/100W/H | 100 W High-altitude version | — |
| 2904376 | UNO-PS/1AC/24DC/150W | 150 W | 6.25 O |
| 2904377 | UNO-PS/1AC/24DC/240W | 240 W | 10 O |
3.2 Other Output Voltages (12V / 15V / 48V)
| Comanda nr. | Model complet | Evaluare de ieșire |
| 2902998 | UNO-PS/1AC/12DC/30W | 12 V / 30 W |
| 2902999 | UNO-PS/1AC/12DC/55W | 12 V / 55 W |
| 2902997 | UNO-PS/1AC/12DC/100W | 12 V / 100 W |
| 2903000 | UNO-PS/1AC/15DC/30W | 15 V / 30 W |
| 2903001 | UNO-PS/1AC/15DC/55W | 15 V / 55 W |
| 2903002 | UNO-PS/1AC/15DC/100W | 15 V / 100 W |
| 2902995 | UNO-PS/1AC/48DC/60W | 48 V / 60 W |
| 2902996 | UNO-PS/1AC/48DC/100W | 48 V / 100 W |
- UNO-PS/2AC Two-phase Standard Models (Non-C2LPS, No Class 2 Protecție împotriva exploziilor)
| Comanda nr. | Model complet | Putere nominală |
| 2904371 | UNO-PS/2AC/24DC/90W/C2LPS | 90 W (C2LPS explosion-proof variant, modelul dvs) |
| 2904376 | UNO-PS/2AC/24DC/150W | 150 W (standard two-phase model) |
| 2904377 | UNO-PS/2AC/24DC/240W | 240 W (standard two-phase model) |
- Regula de denumire a modelului (For Selection Reference)
UNO-PS / 1AC/2AC / 24DC / 90W / C2LPS
- 1AC = Single-phase input; 2AC = Two-phase 400V input (L1+L2, no neutral N)
- 24DC = 24 V DC ieșire
- 90W = Nominal output power
- C2LPS = Class 2 ieșire + Class I Division 2 certificare pentru zone periculoase (only available for the 90W model)
- Note suplimentare
- Only two C2LPS explosion-proof models are available:
Monofazat: 2902994
Two-phase: 2904371 (modelul dvs). No higher-power two-phase C2LPS variants exist.
- No parallel current expansion for the entire UNO series. Use the QUINT series if parallel operation is required.
- All units come with screw terminals (SC). The second-generation UNO models use push-in PT terminals and are not mechanically interchangeable with this housing.
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor






















NH42-63-318x560.png)