  Model Segment Full Designation Description 2981800 Comanda nr. Phoenix Contact global unique part number PSR PSR Phoenix Contact PSR series safety relay (Programmable Safety Relay) SCP SCP Safety function: dedicated for Emergency Stop / Safety Gate monitoring (Safety Control for E-Stop/Door) 24DC 24DC Control voltage: DC24V input ESD ESD Function feature: Emergency Stop Delay ...

  • Detalii despre produs

 

Segmentul de modelFull DesignationDescriere
2981800Comanda nr.Phoenix Contact global unique part number
PSRPSRPhoenix Contact PSR series safety relay (Programmable Safety Relay)
SCPSCPFuncția de siguranță: dedicated for Emergency Stop / Safety Gate monitoring (Safety Control for E-Stop/Door)
24DC24DCControl voltage: DC24V input
ESDESDFunction feature: Emergency Stop Delay
4X14X1Contact configuration: 4 contacte (2 safety NO + 2 auxiliary NO), 1-channel safety input
3030Delay range: adjustable power-off delay 0.1s ~ 30s

Aplicația de bază: Single-channel safety relay for Emergency Stop and Safety Gate monitoring. It complies with safety rating SIL 3 / Cat.4 PL e, with 0.1–30s adjustable power-off delay. Suitable for protection scenarios of automated equipment requiring safety stop delay.

  1. Specificații de bază
Categoria parametrilorSpecificație detaliatăObservații
Safety PerformanceNivel de siguranță: SIL 3 (IEC 61508)Meets highest industrial safety requirements
Nivel de performanță: PL e, Categorie 4 (ÎN ISO 13849-1)
PFHd: 2.5×10⁻⁸/h
Input CharacteristicsTensiune de control: DC24V (19.2~28.8V)Compatible with standard industrial 24V DC control systems
Input Current: Max 40mA
Input Channel: 1 safety input (NC/NO optional)
Modul de resetare: Automat / Manual selectable
Output CharacteristicsContacte de siguranță: 2 pcs N/O (Force-guided)Force-guided safety contacts ensure fail-safe operation
Contacte auxiliare: 2 pcs N/O
Contact Rating: AC-15: 230V/2,5A
DC-13: 24V/2,5A
Max Switching Voltage: 250V AC/DC
Max Switching Current: 6O
Delay CharacteristicsPower-off delay: continuously adjustable 0.1s~30sAdapt to different equipment stopping time requirements
Setting Accuracy: ±10%
Caracteristici fiziceDimensiuni: W22.5mm × H99mm × D121mmSingle-channel width, saves cabinet space
Greutate: Aproximativ. 0.22kg
Montare: 35mm șină DIN (ÎN 60715)
Cablaj: Plug-in screw terminals
Environmental CharacteristicsTemperatura de operare: -20~+60℃Industrial-grade environmental adaptability for harsh working conditions
Temperatura de depozitare: -40~+85℃
Umiditate: 5~95%RH (necondens)
Rezistenta la vibratii: 10~150Hz, 2g
Rezistenta la socuri: 15g
Safety CertificationsCE, UL, CSA, TÜV, ATEXConform standardelor internaționale de siguranță, globally applicable
  1. Lista de accesorii & Installation Guidelines

3.1 Accesorii standard

Safety relay unit ×1

Installation manual ×1

Terminal marking label ×1

Fixing clip ×2 (for DIN rail locking)

Delay adjustment screwdriver ×1 (special tool)

3.2 Precauții de instalare

  1. Mounting Requirement: Install on standard 35mm DIN rail; maintain ≥5mm clearance from adjacent modules for heat dissipation.
  2. Specificații de cablare:

Circuit de control: Connect DC24V to A1(+)、A2(-)

Safety Input: Connect E-stop / safety gate contact to S11S12 (NC contact preferred)

Ieșire de siguranță: Connect safety circuit (de ex. bobina contactorului) la 13-14、23-24

Ieșire auxiliară: Connect alarm / indication circuit to 31-32、41-42

  1. Reset Setting:

Auto Reset: Automatically restore after power cycle

Resetare manuală: Requires external reset signal or manual reset button operation

  1. Delay Adjustment: Use the dedicated screwdriver to adjust the front panel potentiometer to set 0.1–30s power-off delay.
  2. Cross-model & Cross-brand Replacement

4.1 Phoenix Contact Same Series Alternative Models

Model No.Core DifferenceScenariul aplicației
29818001 canal, 2 safety + 2 contacte auxiliare, 0.1–30s delayStandard E-stop / safety gate monitoring (current model)
29818011 canal, 2 safety + 2 contacte auxiliare, 0.1–10s delayEquipment with short stopping time
29818021 canal, 2 safety + 2 contacte auxiliare, 0.1–1s delayFast stop equipment
29818102 canale, 4 safety + 2 contacte auxiliare, no delayDual-channel redundant safety system
29818201 canal, 2 safety + 2 contacte auxiliare, with alarm outputSystem requiring alarm indication

4.2 Cross-brand Equivalent Solutions

MarcaModelParametri cheieNotă de compatibilitate
SchneiderZelio SR2P121BD1 canal, 2 safety contacts, 24În DC, Cat.4Similar function, different wiring layout
Siemens3SK1111-1AB301 canal, 2 safety contacts, 24În DC, SIL 3Different dimensions, cabinet rearrangement required
OmronG9SA-321-T151 canal, 2 safety contacts, 24În DC, Cat.4Delay range 0.05–10s, slightly narrower
ABBMSR12751 canal, 2 safety contacts, 24În DC, SIL 3Higher price, fully identical function
WeidmüllerDRM570730LT1 canal, 2 safety contacts, 24În DC, Cat.4Fixed 1s non-adjustable delay

 

  1. Selecţie & Ghid de înlocuire

5.1 Core Selection Criteria

✅ Safety Level Matching: Ensure required safety rating (SIL/PL/Cat.) does not exceed product capability (SIL 3 / Cat.4 PL e).

✅ I/O Requirement:

Intrare: 1 channel sufficient; confirm NC or NO contact type.

Ieșire: Verify 2 safety + 2 auxiliary contacts meet control demands.

Capacitate de contact: Ensure load current ≤2.5A (AC-15/DC-13).

✅ Delay Requirement: Confirm 0.1–30s adjustable range covers equipment stopping time.

✅ Reset Mode: Select auto or manual reset according to operation needs.

✅ Environmental Adaptation: Operating temperature ≤60℃ and humidity within industrial standard range.

5.2 Upgrade & Opțiuni de înlocuire

Option A: Same Series Function Upgrade

More channels: 2981800 → 2981810 (2 canale, 4 safety contacts)

Add alarm output: 2981800 → 2981820 (with alarm output)

Shorter delay: 2981800 → 2981801 (0.1–10s) sau 2981802 (0.1–1s)

Option B: Migrate from PSRclassic to PSRmini (Space Optimization)

Model de înlocuire: 2981900 (PSRmini-SCP-24DC/ESD/4X1/30)

Avantaj: Only 17.5mm width (5mm narrower), functii identice, saves cabinet space.

Option C: Migrate from PSRclassic to PSRmodular (Extinderea sistemului)

Soluţie: PSRmodular system + safety function modules

Avantaj: Multi-channel expandable; integrates safety gate, E-stop, light curtain and other safety functions, suitable for complex safety systems.

5.3 Depanare comună

Fenomen de eroareCauza posibilaSoluţie
Module indicator offControl power disconnected or faultyCheck DC24V input, measure voltage within 19.2~28.8V
No safety output actionSafety input loop openCheck E-stop / safety gate contact wiring and loop continuity
Abnormal delay timeImproper potentiometer adjustmentReadjust with dedicated screwdriver; calibrate with timer recommended
Eșecul de resetareIncorrect reset mode settingVerify auto/manual reset configuration and check reset signal
Aderenta la contactOverload current exceededMeasure load current; add intermediate relay if necessary

Phoenix Contact 2981800 (PSR-SCP-24DC/ESD/4X1/30) is a single-channel safety relay with adjustable power-off delay, specially designed for emergency stop and safety gate monitoring, reaching the highest safety level SIL 3 / Cat.4 PL e. Its 22.5mm slim design and plug-in wiring facilitate installation and maintenance, while the 0.1–30s adjustable delay adapts to various equipment shutdown requirements. During selection, focus on safety rating, Configurare I/O, delay range and reset mode. For upgrade, choose extended models in the same series or migrate to PSRmini / PSRmodular for space saving or system expansion.

Complete Model List of Phoenix Contact Safety Relays (Structured Classification)

  1. Model Naming Rule Overview
PrefixCod de serieMiddle CodeSensSufixSens
PSRBasic identifier for Phoenix safety relaySCPE-stop / Safety Gate dedicated24DCControl voltage DC24V
PSRReleu de siguranțăSPPStandard Safety ProtectionESDEmergency Stop Delay (0.1-30s)
PSRReleu de siguranțăMCMini Compact4X1Contact: 4 NU (2 safety + 2 auxiliar)
PSRReleu de siguranțăMSMonitoring Safety30Delay time range (0.1-30s)
PSRReleu de siguranțăUNIUniversal ConfigurablePIPush-in spring terminal
PSRReleu de siguranțăMMMotion MonitoringSCScrew terminal
  1. PSRclassic Series (Standard Safety Relays)

2.1 E-Stop / Safety Gate (SCP Series)

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-SCP-24DC/ESD/4X1/3029818001Ch, 2Safety+2Aux, 0.1-30s delaySIL 3/Cat.4 PL eStandard E-stop / Safety Gate
PSR-SCP-24DC/ESD/4X1/1029818011Ch, 2Safety+2Aux, 0.1-10s delaySIL 3/Cat.4 PL eShort stop time equipment
PSR-SCP-24DC/ESD/4X1/129818021Ch, 2Safety+2Aux, 0.1-1s delaySIL 3/Cat.4 PL eFast stop equipment
PSR-SCP-24DC/ESD/5X1/1X2/30029814281/2Ch, 3Safety+1NC+2Aux, 0.1-300s delaySIL 3/Cat.4 PL eLong delay shutdown system
PSR-SCP-24UC/ESA4/3X1/1X2/B29637632Ch, 3Safety+1Aux, no delaySIL 3/Cat.4 PL eDual-channel redundant safety system
PSR-SCP-24DC/MXF3/4X1/2X2/B2903257Multi-Ch, 4Safety+2Aux, 3 safety functionsSIL 3/Cat.4 PL eMulti-function safety monitoring

2.2 Standard Safety Function (SPP Series)

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-SPP-24DC/SDC4/2X1/B29014261Ch, 2Safety contacts, no delaySIL 3/Cat.4 PL eBasic safety loop
PSR-SPP-230AC/ESAM2/3X1/1X2/B29014311Ch, 3Safety+1Aux, AC230VSIL 3/Cat.4 PL eAC power supply system
PSR-SPP-24UC/URM/3X1/3X229014271Ch, 3Safety+3Aux, universal voltageSIL 3/Cat.4 PL eMulti-voltage compatible system
PSR-SPP-24DC/ESD/3X1/1X2/3029814271Ch, 3Safety+1Aux, 0.1-30s delaySIL 3/Cat.4 PL eDelay-type safety system

2.3 Monitorizarea cortinei luminoase (SCR Series)

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-SCR-24DC/3X1/1X229815002Ch, 3Safety+1Aux, dedicated for light curtainSIL 3/Cat.4 PL eStandard light curtain monitoring
PSR-SCR-24DC/4X1/2X229815012Ch, 4Safety+2Aux, dedicated for light curtainSIL 3/Cat.4 PL eComplex light curtain safety system
PSR-SCR-24DC/5X1/1X229815022Ch, 5Safety+1Aux, dedicated for light curtainSIL 3/Cat.4 PL eHigh-density safety output

2.4 Two-Hand Control (SCT Series)

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-SCT-24DC/2X1/1X229816002Ch, 2Safety+1Aux, two-hand controlSIL 3/Cat.4 PL eStandard two-hand operation
PSR-SCT-24DC/3X1/2X229816012Ch, 3Safety+2Aux, two-hand controlSIL 3/Cat.4 PL eComplex two-hand operation
  1. PSRmini Series (Micro Compact, 17.5mm Width)

3.1 Basic Safety Function (MC Series)

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-MC32-3NO-1NC-24-230UC-SP27005251/2Ch, 3Safety+1NC, universal voltageSIL 3/Cat.4 PL eGeneral safety monitoring
PSR-MC34-3NO-1DO-24DC-SP27005481/2Ch, 3Safety+1diagnostic output, DC24VSIL 3/Cat.4 PL eSystem with diagnostic output
PSR-MC45-3NO-1DO-24DC-SC10820241Ch, 3Safety+1diagnostic output, DC24VSIL 3/Cat.4 PL eCompact E-stop system
PSR-MC22-2NO-1NC-24DC-SP27005001Ch, 2Safety+1NC, DC24VSIL 3/Cat.4 PL eSmall safety loop

3.2 Safety Monitoring Module (MS Series)

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-MS21-1NO-1DO-24DC-SC27021921Ch, 1Safety+1digital output, DC24VSIL 3/Cat.4 PL eSafety controller expansion
PSR-MS31-2NO-1DO-24DC-SP27022001Ch, 2Safety+1digital output, DC24VSIL 3/Cat.4 PL eSafety status monitoring
  1. PSRmodular Series (Modular Safety System)

4.1 Main Control Module

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-UNI-L-1X4NO-1DO-24DC-PI14876481/2Ch, 4Safety+1DO, configurableSIL 3/Cat.4 PL eUniversal configurable safety system
PSR-UNI-L-2X4NO-2DO-24DC-PI14876492Ch, 8Safety+2DO, configurableSIL 3/Cat.4 PL eComplex safety system
PSR-UNI-L-1X2NO-1NC-1DO-24DC-PI14876501/2Ch, 2Safety+1NC+1DOSIL 3/Cat.4 PL eSystem with NC output

4.2 Expansion Module

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-EXT-L-1X4NO-24DC-PI14876514-safety output expansionSIL 3/Cat.4 PL eOutput expansion
PSR-EXT-L-1X2NO-1NC-24DC-PI14876522Safety+1NC output expansionSIL 3/Cat.4 PL eMixed output expansion
  1. PSRmotion Series (Motion Monitoring Safety Relay)

5.1 Zero Speed / OverSpeed Monitoring

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-MM25-1NO-2DO-24DC-SC2702355Sensorless zero-speed monitoring, 3-motor de fazăSIL 3/Cat.3 PL eMotor zero-speed safety protection
PSR-MM35-1NO-2DO-24DC-SC2702356Overspeed monitoring, 3-motor de fazăSIL 3/Cat.3 PL eMotor overspeed safety protection
PSR-MM45-1NO-2DO-24DC-SC2702357Zero-speed + overspeed dual monitoring, 3-motor de fazăSIL 3/Cat.3 PL eFull motor speed monitoring

5.2 Rotation Direction Monitoring

ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-MD25-1NO-2DO-24DC-SC2702360Rotation direction monitoring, 3-motor de fazăSIL 3/Cat.3 PL eMotor rotation direction safety control
  1. Safety Coupling Relays (PSR-SCP/SPP Series)
ModelComanda nr.Parametrul de bazăNivel de siguranțăAplicație
PSR-SCP-24DC/FSP/1X1/1X229817001Safety+1Aux contact, coupling functionSIL 3Safety signal isolation
PSR-SCP-24DC/FSP2/2X1/1X229817012Safety+1Aux contact, coupling functionSIL 3Dual-channel safety isolation
PSR-PS21-1NO-1NC-24DC-SC29817021Safety+1NC contact, coupling functionSIL 3Safety signal switching
  1. Key Selection Parameter Comparison
Categoria parametrilorKey IndexSfaturi de selecție
Nivel de siguranțăSIL 1-3, Cat.1-4, PL a-eDetermined by equipment risk assessment; max support SIL 3/Cat.4 PL e
Input Channel1 Canal / 2 CanalSingle channel for basic safety; dual channel for redundant safety
Configurare contactQuantity of safety / contacte auxiliare≥2 safety contacts recommended; auxiliary contacts for alarm & indication
Tensiune de controlDC24V / AC230V / UniversalMatch on-site control system power supply
Function FeatureDelay / Diagnostic / Cross-circuit detectionE-stop requires delay; complex system needs diagnostic function
Mounting Width17.5mm / 22.5mm / 27.5mmChoose PSRmini (17.5mm) for limited cabinet space
Wiring TypeScrew / Push-in springPush-in for frequent wiring; screw type for vibration environment
  1. Note suplimentare

8.1 Poziționarea în serie

PSRclassic: Standard type with complete functions, width starting from 22.5mm, suitable for conventional safety applications.

PSRmini: Micro compact type, only 17.5mm width, saves cabinet space.

PSRmodular: Configurable modular system, suitable for complex safety systems with expandable functions.

PSRmotion: Dedicated for motion monitoring, applicable to motor zero-speed / overspeed / rotation direction safety control.

8.2 Replacement Information

Old models are gradually phased out; priority recommended to select models manufactured after 2020.

Some models are discontinued; refer to Phoenix Contact official website or technical support for replacement.

8.3 Certificare de siguranță

Full series certified by CE, UL, CSA, TÜV, conform cu IEC 61508 and EN ISO 13849-1.

Partial models with ATEX certification for explosive atmosphere applications.

Prev: