Ciupercă 772100 Pilz Safety Relay - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

Ciupercă 772100 Pilz Safety Relay - Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare

electric/

Ciupercă 772100 Pilz Safety Relay

Basic Model Information Part No.: 772100 Numele produsului: PNOZ X2 24VAC Safety Relay Brand: CIUPERCĂ (German safety automation brand) Core Electrical Specifications Supply Voltage: 24 V AC Safety Contacts: 2 deschis în mod normal (NU) safety output contacts Auxiliary Contacts: None Safety Classification EN ISO 13849-1: Pisică. 4 / PL e IEC 61508: SIL 3 Input Circuit: ...

  • Detalii despre produs

Basic Model Information

Partea nr.: 772100

Numele produsului: PNOZ X2 24VAC Releu de siguranță

Marca: CIUPERCĂ (German safety automation brand)

  1. Specificații electrice de bază
  2. Tensiune de alimentare: 24 V și
  3. Contacte de siguranță: 2 deschis în mod normal (NU) safety output contacts
  4. Contacte auxiliare: Nici unul
  5. Safety Classification

ÎN ISO 13849-1: Pisică. 4 / PL e

IEC 61508: SIL 3

  1. Input Circuit: Single-channel E-stop / safety gate input with spring terminal wiring
  2. Contact Ratings

Sarcină rezistivă: 230V / 6O

Minimum Switching Current: 1mA / 5În DC

  1. Functional Description

Standard basic safety relay compatible with E-stop buttons, safety gate switches and safety mats

Auto-reset mode (no reset button; outputs close automatically after power recovery)

Compact module for DIN rail mounting (35mm șină standard)

Housing width: 22.5mm

  1. de mediu & Parametri mecanici

Temperatura de operare: 0 ~ +55 ℃

Temperatura de depozitare: -20 ~ +70 ℃

Clasa de protectie: IP20 (for cabinet installation only)

Certificari: CE, UL, CSA

  1. Typical Replacement Models
  2. Equivalent DC version: 772101 (PNOZ X2 24VDC)
  3. Manual reset version: 772130 (PNOZ X2.1 24VAC)
  4. Wider multi-contact version: PNOZ X3 / X4 series

CIUPERCĂ 772100 (PNOZ X2 24VAC) Complete Terminal, Cablaj, Dimensiune & Troubleshooting Manual

  1. Basic Model Information

Comanda nr.: 772100

Model: PNOZ X2 24VAC

Livra: 24V și

Modul de resetare: Auto-reset (no external start terminals; outputs close upon power restoration)

Contacte de siguranță: 2 force-guided normally open contacts 13-14 / 23-24

Nivel de siguranță: Cat.4 / PL e / SIL3

  1. Definiție completă a terminalului (Top to Bottom)

2.1 Terminale de alimentare (Left Supply Area)

A1: 24V AC Live (L)

A2: 24V AC Neutral (N)

> Supply range: 20.4~26.4V AC; a 1A slow-blow fuse is recommended upstream

2.2 Safety Input Monitoring Terminals (Middle Input Circuit)

S11: Common input terminal (24V AC incoming line)

S12: Canal 1 intrare (one end of E-stop/safety gate NC contact)

S22: Canal 2 intrare (second redundant channel for dual-circuit design)

> This model has no S21 and no Y1/Y2 start terminals, purely auto-reset design

2.3 Safety Output Contacts (Right Load Circuit)

  1. 13-14: 1st set of force-guided safety NO contacts
  2. 23-24: 2nd set of force-guided safety NO contacts

No auxiliary contacts or feedback circuit terminals

  1. Two Standard Wiring Schemes (Field Commonly Used)

Sistem 1: Single-channel Wiring (Only meets PL d, for simple low-risk machines)

Aplicație: Low-risk equipment with single E-stop only

  1. Connect S11 to 24V AC L
  2. Short-circuit S12 and S22 together
  3. Wire E-stop NC contacts in series to the short joint, then route back to A2 (N)

Principiu: Two input lines shorted; internal single-channel monitoring only, unable to detect short circuits between contacts

Sistem 2: Dual-channel Redundant Wiring (Mandatory Cat.4/PL e for Machine Tools & Automation Lines)

Aplicație: Injection molding, stamping, robotică, production line safety gates

  1. S11 = 24V AC L
  2. S12: 1st NC contact of E-stop
  3. S22: 2nd NC contact of E-stop
  4. Parallel the other ends of both contacts and connect to A2 (N)

Avantaje: Detects input earth short circuits, inter-cable short circuits and single contact welding

Standard Output Wiring

Wire contactor coils and main circuit control power in series with 13-14 + 23-24 in series (dual safety cut-off)

Sarcină rezistivă: 230V/6A

Inductive contactor load: Install RC surge suppressor in parallel with coil

Fit a 6A fuse upstream of outputs to prevent contact welding

  1. Dimensiuni de montare & Specificații de cablare

Overall Mechanical Dimensions (mm)

Lățime × Înălțime × Adâncime: 22.5 × 87 × 121

Montare: Snap-on installation on 35mm standard DIN rail

Greutate: Aproximativ. 190g

Protecţie: IP20, cabinet use only

Terminal Wiring Requirements

Screw terminal torque: 0.6 N·m

Wire stripping length: 7mm

Secțiunea cablului: Solid wire 0.2~4mm²; stranded wire with ferrule 0.2~2.5mm²

Max total length of input circuit cables: ≤300m (line resistance ≤30Ω limit for AC models)

  1. Front Panel Indicator Meanings
  2. Green POWER LED: Power supply normal
  3. Green CH1 / CH2 LEDs: Corresponding input channel circuit closed (safe state)

Indicator Status Reference Table

FenomenEquipment Status
POWER LED offNo 24VAC supply, siguranța arsă, reversed/short-circuited A1/A2 terminals
POWER LED on, CH1/CH2 all offE-stop activated, safety gate open, broken input cable or input earth short
POWER LED on, single CH LED offOpen circuit in one dual channel, damaged contact, locked fault due to inter-cable short
All LEDs on, no voltage at outputsInternal contact welding, irreversible module hardware failure
  1. Matricea de depanare (Phenomenon → Root Cause → Resolution Steps)

Vina 1: POWER LED fails to light up after power-on

  1. No 24VAC measured at A1-A2: Check upstream circuit breaker, fuse and transformer supply
  2. Normal voltage at A1/A2 but LED remains off: Internal power supply damaged; înlocui 772100 directly
  3. Terminal short circuit: Cut power, rework wiring and eliminate cable insulation earth leakage

Vina 2: Power supply normal, CH LEDs off, safety outputs de-energized

  1. E-stop NC contact open: Reset E-stop button
  2. Broken input cable: Measure continuity between S11-S12/S22 section by section
  3. Input cable earth short: Disconnect cables and locate grounding fault segment by segment
  4. Single contact failure under dual-channel wiring: Replace dual-circuit E-stop switch

Vina 3: All LEDs illuminated but machine fails to start (no output at 13-14/23-24)

  1. Blown output circuit fuse: Replace fuse and check for shorted contactor coil
  2. Welded safety contacts: Irreparable module damage; install new unit
  3. Load current exceeding 6A: Add intermediate relay to expand output capacity

Vina 4: Random tripping and CH LED extinction during operation (defect intermitent)

  1. Excessively long cables with excessive line resistance: Use thicker cables or shorten wiring routes
  2. Interference from power cables routed alongside safety wiring: Separate cable runs with ≥20cm clearance
  3. High contact resistance caused by oxidized contacts: Replace E-stop / safety gate switch
  4. Strict Forbidden Operations (Violation leads to lost safety certification or burnt module)
  5. Never connect 220V mains to A1/A2; only 24V AC is permitted
  6. Never omit the second contact in dual-channel wiring (Cat.4 compliance cannot be achieved)
  7. Never feed an independent external power source to input circuits; input power must share the same 24VAC supply as module A1/A2
  8. Do not parallel output contacts for capacity expansion; series connection only. Use external safety contactors for load expansion
  9. Never drive high-power inductive loads without fuses; high risk of contact welding
  10. Do not plug/unplug input cables while the module is live; electric arcs will damage internal monitoring circuitry
  11. Equivalent Series Replacement Reference
  12. DC alternative: 772101 (PNOZ X2 24VDC, identical terminal layout, 24V DC supply only)
  13. Manual reset model: 772130 (PNOZ X2.1 24VAC, added Y1/Y2 start terminals requiring external reset button)
  14. Multi-contact upgrade: 774300 PNOZ X3 (3 contacte de siguranță, 45mm latime)
  15. Complete Part Number List for PILZ PNOZ X2 Series (22.5mm latime, 2 FĂRĂ contacte de siguranță, Cat.4/PL e/SIL3)

Benchmark Reference: 772100 = PNOZ X2 24VAC auto-reset, no manual start terminals

1.1 Pure Auto-reset Models (No Y1/Y2 reset terminals, direct equivalent to 772100)

Partea nr.Numele complet al modeluluiTensiune de alimentareTip terminalModul de resetare
772100PNOZ X2 24VAC24V șiFixed screw terminalsAuto-reset
772101PNOZ X2 24VDC24În DCFixed screw terminalsAuto-reset
774053PNOZ X7 110VAC110V șiFixed screw terminalsAuto/Manual dual compatible
774055PNOZ X7 120VAC120V șiFixed screw terminalsAuto/Manual dual compatible
774057PNOZ X7 240VAC240V șiFixed screw terminalsAuto/Manual dual compatible

1.2 Manual Controlled Reset Models (X2.1 series with external Y1/Y2 reset button)

Partea nr.Numele complet al modeluluiTensiune de alimentareTerminaleCaracteristici
772130PNOZ X2.1 24VAC24V șiBorne cu șuruburiExternal reset, dual-channel short-circuit detection
772131PNOZ X2.1 24VDC24În DCBorne cu șuruburiExternal reset
777300PNOZ X2P 24VACDCUniversal 24V AC/DCPlug-in spring terminalsAuto/Manual dual mode

1.3 45mm Wide X2C Series with Feedback Circuits (Controlled start, equipment feedback monitoring)

777303 PNOZ X2P C 24VACDC: Spring terminals with equipment feedback monitoring

774303 PNOZ X2 24VACDC: Universal AC/DC base model

1.4 Distinction Notes (Avoid Selection Mistakes)

  1. 772100 ≠ PNOZ m B0: PNOZ m B0 (marked 772100) is a modular safety controller, completely different product category from PNOZ X2 safety relay. Same part number but unrelated products. All replacements below apply exclusively to PNOZ X2 24VAC safety relay 772100.
  2. Model 772100 X2 only: 22.5mm latime, 2 FĂRĂ contacte de siguranță, fara contacte auxiliare, pure auto-reset.
  3. Cross-brand Equivalent Replacement Table (Potrivire 772100: 24VAC, dublu-canal, 2 Contacte de siguranță NU, auto-reset, Cat.4 PL e SIL3)

2.1 Schneider Preventa XPS Series

Scenariul aplicațieiModel de înlocuireRata de potrivireDescrierea diferenței
Direct drop-in replacement for 772100 (24VAC auto-reset)XPS-AC311095%2 Contacte de siguranță NU, dual-channel E-stop/safety gate monitoring, auto-reset; 22.5mm latime, 24VAC supply
Universal AC/DC versionXPS-AC511090%24VAC/DC universal, functii identice, minor difference in terminal layout
Alternative manual reset modelXPS-AC371085%Requires external reset button, suitable for machines requiring startup confirmation

2.2 ABB Safety Safety Relays

Model de înlocuireRata de potrivireSpecificații cheie
C571.04 24VAC93%2 Contacte de siguranță NU, dual-channel monitoring, auto-reset, Cat.4 PL e, 22.5mm DIN width
C571.05 24UC90%Universal AC/DC, all other functions identical

2.3 OMRON G9SE Series (Most Widely Used Drop-in Equivalent)

ModelTensiune de alimentareRata de potrivireDescriere
G9SE-201 AC2424V și98% Optimal EquivalentDual-channel input, 2 force-guided NO contacts, power-on auto-reset, 22.5mm latime, SIL3 PL e Cat.4, highly consistent terminal logic with PILZ X2
G9SE-201 DC2424În DC98%Equivalent to DC model 772101

2.4 Phoenix Contact PSR Series

ModelRata de potrivireNote de compatibilitate
PSR-SCP-24AC/ESA2/2X192%24VAC, 2 contacte de siguranță, auto-reset, dual-channel short-circuit detection, 22.5mm latime
PSR-SCP-24UC/ESA2/2X190%Universal AC/DC with broader compatibility

2.5 IFM Safety Relays

ModelRata de potrivire
SR0100 24VAC90%Dual-channel E-stop monitoring, 2 Contacte de siguranță NU, auto-reset, Cat.4

2.6 Domestic Certified Equivalents (Cat.4/PL e/TÜV Certified)

MarcaModelRata de potrivire
CovestroSRS2-24AC88%2 Contacte de siguranță NU, dublu-canal, auto-reset
EuchnerES202-24AC90%Popular domestic alternative for machine tools
  1. Replacement Selection Criteria (Must Verify Before Swap)

3.1 Mandatory Identical Parameters (Otherwise Direct Wiring Impossible)

  1. Tensiunea nominală de alimentare: 772100 fixed at 24V AC. DC24V models cannot be directly replaced unless an AC/DC power converter is added.
  2. Reset logic: Original equipment uses auto-reset. Do not select forced manual reset models (X2.1, XPS-AC3710, etc.)
  3. Number of safety contacts: 2 sets of force-guided NO contacts (13-14 / 23-24). Avoid models with 3NO + 1Contacte auxiliare NC.

3.2 Minor Compatible Differences (No Program Modification Required, Minor Wiring Adjustment Only)

  1. Terminal pitch / terminal type: Screw vs spring terminals only require different crimping tools
  2. Indicator layout: No impact on safety functions
  3. Maximum cable length limit: Difference ≤50m among all 22.5mm compact modules, negligible for field wiring
  4. Modification Precautions for Replacement
  5. Optimal zero-modification replacement: OMRON G9SE-201 AC24. Near identical terminal definition, dimensiuni, safety level and auto-reset logic as 772100; electricians can reuse existing wiring without changes.
  6. Schneider XPS-AC3110 mapping: Input terminals S11/S12/S22 correspond to XPS IN1/COM/IN2; output contact series wiring method is fully identical.
  7. Mixed model prohibition: Replacing auto-reset unit with manual reset model will prevent automatic machine startup after power-on; external reset button must be installed additionally.
  8. Safety certification retention: All listed models comply with EN ISO 13849 Cat.4 PL e and IEC 61508 SIL3. Machine overall safety certification remains valid after replacement.
  9. Load protection: 6A fuse must still be fitted on outputs post replacement; RC snubber circuit mandatory for inductive contactor coils.
  10. Quick Selection Recommendations
  11. Imported zero-wiring-modification replacement: G9SE-201 AC24 (OMRON)
  12. Matching Schneider system equipment: XPS-AC3110
  13. Phoenix Contact cabinet integrated solution: PSR-SCP-24AC/ESA2/2X1
  14. Cost-effective domestic alternative: SRS2-24AC (Covestro)
  15. Replacement for original DC model 772101: G9SE-201 DC24 / XPS-AC5110

Prev:

Lasă un răspuns

Lăsaţi un mesaj