The C120N belongs to the Acti9 series high-current întrerupător miniatural (MCB). It is an upgraded high-current variant of the standard C65N, with a maximum rated current of 125A and isolation function. Widely used for power distribution in industrial and building terminals, as well as outgoing circuits in power cabinets.
- Definiția modelului
C120: Seria de produse, high-current MCB (63~125A)
N: Clasa de capacitate de rupere, Icn=10kA @ 400V AC
125O: Rated working current In=125A (reference temperature: 30℃)
Full model requires additional [numărul de pol + curba de declansare]
curba C: Instantaneous tripping at 5~10In, for general power distribution, lighting and resistive loads (Partea nr. A9N18359 / A9N18363 / A9N18369)
curba D: Instantaneous tripping at 10~14In, for loads with inrush current such as motors and transformers (Partea nr. A9N18389)
- Specificații electrice de bază
| Articol | Parametru |
| Curent nominal In | 125O (la 30℃) |
| Operating voltage Ue | AC 230/400V |
| Tensiunea nominală de izolație Ui | 500V |
| Rated short-circuit breaking capacity Icn | 10cel (IEC60898-1) |
| Capacitate maximă nominală de rupere în scurtcircuit Icu | 10kA @400V (IEC60947-2) |
| Tripping type | C / D optional |
| Funcția de protecție | Declanșare la suprasarcină termică + magnetic short-circuit trip, with isolation function (green contact indicator) |
| Rezistenta mecanica | 20,000 operațiuni |
| Rezistenta electrica | 5,000 operațiuni (range 80~125A) |
| Metoda de montare | 35mm Montare pe șină DIN |
| Clasa de protectie | IP20 (terminal side) |
| Temperatura ambiantă de funcționare | -25℃ ~ +70℃ |
- Specificații de cablare
Solid copper cable: Max. 50mm²
Flexible copper cable: Max. 35mm²
Optional aluminum terminal: For 16~50mm² aluminum cables
- Scenarii de aplicare
- High-current outgoing circuits in factory buildings, computer rooms and building distribution cabinets
- Main power incoming, fan and water pump circuits (D-curve recommended)
- Alternative to small-frame moulded case circuit breakers to save cabinet space
Accesorii optionale: Vigi C120 residual current module, contact auxiliar, fault alarm contact, declanșare șunt
- Ghid de selecție & Produse alternative
Note de selecție
- Derating is required when ambient temperature exceeds 30℃;
- D-curve is preferred for motor loads; C-curve for general distribution;
- C120N with 10kA breaking capacity; select C120H (15cel) / C120L (25cel) for circuits with higher short-circuit current.
Alternative interne
Chint: NM1-125 compact MCCB / NB1-125 MCB
Delicios: CDB2 125 series miniature circuit breaker
- Depanare comună
- Călătorii imediat după închidere: Short circuit on downstream side, check cable insulation and load earth fault;
- Trips after period of loaded operation: Supraîncărcare, actual load exceeds 125A, or high ambient temperature causes derating;
- Nu se poate închide, handle stuck: Damaged internal mechanism, or Vigi residual current module triggered;
- Green indicator does not appear: Main contacts are not fully disconnected. Maintenance on downstream circuits is prohibited.
- HS Code Reference
85362000 Low-voltage circuit breaker (for customs declaration reference only, subject to customs verification)
Schneider Acti9 C120N 125A Product Manual (Compiled from Original Datasheet)
Serie: Acti9 C120N High-current Miniature Circuit Breaker (MCB)
Curent nominal: 125O (reference at 30℃)
Capacitate de rupere: Icn=10kA @400V AC
Reference part numbers:
2P C-curve: A9N18363
3P C-curve: A9N18369
4P C-curve: A9N18376
3P D-curve: A9N18389
The C120N is part of Schneider Acti9 high-current MCB family covering 63~125A. It features isolation function. The green contact indicator provides direct visual confirmation that main contacts are open, meeting maintenance safety requirements. It provides thermal-magnetic protection against overload and short-circuit for high-current power distribution in industrial and building distribution cabinets. Compatible with add-on accessories including Vigi C120 residual current module, contacte auxiliare, alarm contacts and shunt releases.
Standarde: GB10963.1, IEC/EN60898-1, IEC/EN60947-2; CCC, Certificat CE
- Specificații electrice
| Articol | Parametru |
| Curent nominal In | 125O (reference ambient temperature:30℃) |
| Rated operating voltage Ue | AC 230/400V; max. 440V și |
| Tensiunea nominală de izolație Ui | 500V |
| Tensiune nominală de rezistență la impuls Uimp | 6kV |
| Capacitate maximă nominală de rupere în scurtcircuit Icu | 10kA @400V AC |
| Capacitate nominală de întrerupere a scurtcircuitului de serviciu Ics | 75% of Icu =7.5kA |
| Rated short-circuit breaking capacity Icn | 10cel (IEC60898-1) |
| Tripping type | curba C: 5~10In instantaneous magnetic trip; curba D:10~14In instantaneous magnetic trip |
| Protection principle | Călătoria termică (suprasarcina) + călătorie magnetică (scurt-circuit) |
| Rezistenta mecanica | 20,000 operațiuni |
| Rezistenta electrica | 5,000 operațiuni (range 80~125A) |
| Current limiting class | Clasă 3 |
| Funcția de izolare | ✅ Disponibil, green indicator for contact open status |
- Mecanic & Specificații de cablare
- Montare: 35mm șină DIN standard, snap-in type, mountable in any orientation
- Clasa de protectie: IP20 (front terminals)
- Capacitatea cablajului
Solid copper cable: Max.50mm²
Flexible copper cable (with cable lug): Max.35mm²
Optional aluminum terminals: For 16~50mm² aluminum cables
- Cuplul de strângere: 3.5 N·m
- Dimensiuni de gabarit (18mm pe stâlp)
2P: 36mm latime; 3P: 54mm latime; 4P:72mm latime
- Mediul de operare
Temperatura mediului ambiant: -25℃ ~ +70℃; derating required above 30℃
Temperatura de depozitare: -40℃ ~ +85℃
Altitudine: No derating ≤2000m; derating required above 2000m
Umiditatea relativă: 5~95%, necondens
- Caracteristici de declanșare
- Declanșare la suprasarcină termică (timp invers)
1.13În: No tripping within 1h (stare rece)
1.45În: Tripping within 1h
- Magnetic instantaneous trip
curba C:5~10 in, distribuția puterii, iluminat, sarcini rezistive
curba D:10~14In, motoare, transformatoare, capacitor loads with inrush current
- Accesorii optionale
- Vigi C120: Add-on residual current protection module, forms RCD+MCB combination
- OF Auxiliary contact: Circuit ON/OFF status signal
- SD Fault alarm contact: Tripping signal for short-circuit / suprasarcina
- MX Shunt release: Remote electrical trip
- MN Undervoltage release: Loss-of-voltage protection
- Bara de distribuție: Comb-type busbar for multi-pole parallel incoming connection
- Instalare & Note de operare
- Derating: Derate rated current when ambient temperature >30℃. Derating also required for multiple devices installed side by side inside enclosed cabinets.
- Isolation verification: When handle is set to OFF position, the green indicator visible confirms main contacts are fully open before downstream maintenance. Handle position alone cannot be used as isolation confirmation.
- Cablaj: Top-in or bottom-in wiring is acceptable. Cable lugs are recommended. Tightening torque 3.5N·m to prevent overheating.
- Model differentiation
C120N:10cel; C120H:15cel; C120L:25cel. Select H/L version for circuits with high short-circuit current.
- Depanare
- Călătorii imediat după închidere: Short circuit or earth fault on downstream side. Test breaker separately after disconnecting load to verify breaker integrity.
- Trips after loaded operation: Actual load exceeds rated current, or high ambient temperature causes derating.
- Nu se poate închide, handle stuck: Damaged mechanism or locked residual current module.
- Overheating when closed: Insufficient terminal torque, cablu subdimensionat, oxidized terminals.
- Model Selection Table (C120N 125A)
| Pol | Curba de declanșare | Numărul piesei |
| 2P | C | A9N18363 |
| 3P | C | A9N18369 |
| 4P | C | A9N18376 |
| 3P | D | A9N18389 |
Schneider Acti9 C120N 125A Overall & Dimensiuni de montare (Original Datasheet)
Referinţă: Height H=81mm, Depth D=73mm, height and depth are consistent for all pole types; width varies with pole count
Sina de montare: 35mm standard symmetrical DIN rail, snap-in installation
| Pol | L × H × D | DIN module (9mm/unit) | Greutate netă |
| 1P | 27 × 81 × 73 mm | 3 unitati | 0.205 kg |
| 2P | 54 × 81 × 73 mm | 6 unitati | 0.410 kg |
| 3P | 81 × 81 × 73 mm | 9 unitati | 0.615 kg |
| 4P | 108 × 81 × 73 mm | 12 unitati | 0.820 kg |
Common model: 3P C120N 125A (A9N18369): 81(W) × 81(H) ×73(D) mm
Related Mounting Dimensions
- Cable stripping length: 15 mm
- Cuplul de strângere a bornei: 3.5 N·m
- Max terminal wiring: Solid wire 50mm² / Flexible wire 35mm²
- Cabinet clearance: ≥20mm wiring space reserved at top and bottom terminals; keep heat dissipation gap for side-by-side installation at high temperature (derating)
Note suplimentare
Depth 73mm: Total depth from DIN rail backplate to front handle of breaker body; cabinet door cutout needs clearance allowance
Height 81mm: Overall vertical height of device body, excluding cable bending allowance
If Vigi C120 residual current module is fitted, overall depth increases, refer to separate accessory datasheet for dimension