Schneider NT06H2 Air Circuit Breaker

NT: MasterPact NT series air circuit breaker (ACB, legacy model, întreruptă; replacement model MTZ1 06H2) 06: Dimensiunea cadrului 06, frame rated current 630A H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1s), Class B selective protection Core Electrical Parameters Item Specification Frame rated current In 630A (la 40℃) Rated operational voltage Ue AC ...

  • Detalii despre produs

NT: MasterPact NT series întrerupător de circuit de aer (ACB, legacy model, întreruptă; replacement model MTZ1 06H2)

06: Dimensiunea cadrului 06, frame rated current 630A

H2: Breaking capacity class H2; Icu=50kA@440VAC, short-time withstand current Icw=50kA (1s), Class B selective protection

Parametrii electrici de bază

ArticolCaietul de sarcini
Frame rated current In630O (la 40℃)
Tensiunea nominală de funcționare UeAC 690V, 50/60Hz
Tensiunea nominală de izolație UiAC 1000V
Tensiune nominală de rezistență la impuls Uimp12kV (1.2/50μs lightning impulse)
Capacitate finală de rupere în scurtcircuit Icu50kA@440V; 42kA@690V
Numărul de poli3P / 4P optional
Tip constructieFix / Retragere
Unitate de declanșareFrame supplied without trip unit, MicroLogic trip unit to be ordered separately
StandardeIEC 60947-2, with isolating function

Note cheie

  1. Starea întreruperii: NT series scheduled for end-of-sale by the end of 2025. Replacement model MTZ1 06H2, part number LV947203 (draw-out version)
  2. Parameter Clarification

Ue=690V: Maximum normal operating voltage

Ui=1000V: Tensiunea de rezistență a frecvenței de alimentare

Uimp=12kV: Lightning impulse withstand voltage. NOT applicable for 12kV high-voltage switchgear, this is an insulation index for low-voltage ACB

  1. Aplicație: Incoming feeder, bus tie and heavy-load outgoing feeder in low-voltage distribution systems, for industrial plants, data centers and marine power distribution; supports selective protection and coordination with upstream/downstream devices
  2. Reference Frame Part Numbers

NT06H2 3P Fixed: 47113

NT06H2 3P Draw-out: 47203

NT06H2 4P Fixed: 47119

Accesorii & Piese de schimb

Trip Units: MicroLogic 2.0 / 5.0 / 6.0 / 7.0 (suprasarcina, întârziere de scurtă durată, instantaneous and earth-fault protection)

Accesorii: Motor operating mechanism, contacte auxiliare, fault alarm contacts, closing coil, shunt trip coil, door interlock, phase barriers

Draw-out base: Mandatory independent cradle for draw-out version

Ghid de depanare

  1. Neînchidere: Undervoltage coil de-energized, incomplete spring charging, cradle not in connected position, interlock blocking
  2. Unintended tripping: Check trip unit protection curve, defect la pământ, harmonic distortion and temperature rise
  3. Test de izolare: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type-test only, no on-site 12kV impulse test

Domestic Alternative Reference

Domestic MT06H2 (Schneider domestic MT series). Compatible breaking capacity and mounting dimensions for direct replacement.

Schneider MasterPact NT06H2 Air Circuit Breaker Technical Manual (Full Engineering Version, per original datasheet 0613CT0001)

Observații: NT series is legacy discontinued ACB, frame size NT06, In=630A; breaking class H2; frame supplied without trip unit, MicroLogic trip unit to be ordered separately; standard IEC 60947-2, isolating function, Class B selective protection

Cuprins

  1. Prezentare generală a produsului & Codul modelului Explicația
  2. Rated Electrical Parameters
  3. Parametri mecanici, Dimensiuni generale & Greutate
  4. MicroLogic Trip Unit Selection
  5. Lista de accesorii & Secondary Terminal Definition
  6. Instalare & Cerințe de cablare
  7. Operațiunea, Handling & Interlock Description
  8. Întreţinere, Inspecţie & Depanare
  9. Condiții de mediu
  10. Replacement Model Information
  11. Original Document Index
  12. Prezentare generală a produsului & Codul modelului Explicația

1.1 Prezentare generală

MasterPact NT series low-voltage air circuit breakers for incoming feeders, bus ties and high-current outgoing feeders in 400/690V low-voltage distribution systems. NT06H2 maximum frame rating 630A, available in draw-out or fixed construction, spring charged operation, configurable with intelligent MicroLogic protection unit, supports remote signalling, metering and communication.

Memento important: Ui=1000V (tensiunea nominală de izolație), Uimp=12kV (lightning impulse withstand voltage). NOT 12kV high voltage circuit breaker, only for AC ≤690V low-voltage distribution.

1.2 Defalcarea modelului

NT: MasterPact NT series air circuit breaker

06: Dimensiunea cadrului 06, frame rated current 630A

H2: Breaking class H2; Icu=50kA@440VAC, Icw=50kA 1s, Class B selective

Part Numbers:

NT06H2 3P Fixed: 47113

NT06H2 3P Draw-out: 47203

NT06H2 4P Fixed: 47119

1.3 Stare produs

NT series scheduled end-of-sale by end of 2025; replacement model MTZ1 06H2, part number LV947203 (extras). Mounting dimensions and secondary interfaces fully compatible for direct replacement.

  1. Rated Electrical Parameters
ArticolValoare
Frame rated current In630O (at 40℃ ambient)
Tensiunea nominală de funcționare UeAC 50/60Hz, max 690V
Tensiunea nominală de izolație Ui1000V
Tensiune nominală de rezistență la impuls Uimp12kV (1.2/50μs lightning impulse)
Capacitate finală de rupere în scurtcircuit Icu50kA@440V; 42kA@690V
Rated short-time withstand current Icw50cel, 1s
Capacitate nominală de întrerupere a serviciului Ics100% de Icu
Selectivity classClasa B (with short-time delay selective protection)
Isolating functionComplies with IEC60947-2 isolation requirement
Numărul de poli3P / 4P optional
  1. Parametri mecanici, Dimensiuni generale & Greutate

3.1 Rezistenta mecanica

Durata de viata mecanica: 20,000 operațiuni (no-load make/break)

Durata de viata electrica (400V, În): 10,000 operațiuni

Spring charging: Manual charging / motor charging MCH optional

3.2 Dimensiuni generale (3P, unitate: mm)

Tip fix: W300 × H415 × D266

Tip extras (with cradle): W300 × H415 × D376

4P version width 360mm, height and depth unchanged

3.3 Greutate

Fixed frame only: ≈32kg

Draw-out frame + cradle: ≈52kg

3.4 Three positions for draw-out version

  1. Connected Position: Main circuit and secondary circuit fully connected, normal operation
  2. Test Position: Main circuit disconnected, secondary circuit remains connected for protection test
  3. Disconnected Position: Main and secondary circuits fully disconnected, breaker can be withdrawn for maintenance
  4. MicroLogic Trip Unit Selection (Must be ordered separately, not included with frame)
Model de unitate de deplasareFuncții de protecțieAplicație tipică
MicroLogic 2.0Long-time overload protection onlyIzolator, overload-only protection
MicroLogic 5.0ALong-time Ir, short-time delay Isd, instantaneous IiIncoming feeder, bus tie (most common)
MicroLogic 6.0AAll functions of 5.0A + protectie la pamantCritical incoming feeder requiring earth fault protection
MicroLogic 7.0A6.0O + protectie cu curent rezidual + monitorizare armonicăCentre de date, sensitive loads

Protection setting range: Şi (perioadă lungă de timp) 0.4~1×In; Isd short-time delay 0.5~10×In, delay 0.1/0.2/0.4s; Ii instantaneous 1~15×In.

  1. Lista de accesorii & Secondary Terminal Definition

5.1 Accesorii optionale

  1. MCH: Charging motor AC220V / DC24V
  2. XF: Closing solenoid AC220V / DC24V
  3. MX: Bobina de declanșare de șunt (remote opening)
  4. MN: Declanșare de subtensiune (MNu time-delayed undervoltage for auto-transfer application)
  5. DE: Contacte auxiliare (CB on/off status feedback)
  6. SDE: Fault trip contacts (signal for overload/short-circuit/earth fault trip)
  7. PF: Cradle position contacts (connected / test / disconnected position)
  8. Phase barriers, interblocarea ușii dulapului, mechanical interlock cables, padlock device
  9. ULP communication module: Modbus-RTU, remote signalling & contorizare

5.2 Secondary Terminal Definition

CodNumeTerminaleDescriere
MCHCharging motorB1, B2Auto charging upon power-up; B1-B3 charged ready CH contact
XFClosing coilA1, A2Closing actuation
MXExcursie cu șuntC1, C2Remote opening
MNDeclanșare de subtensiuneD1, D2Trip on loss of voltage, core component for auto-transfer
DEAuxiliary position contact11-12 NC /11-13 NUOn/off status feedback
SDEFault trip contact81,82Protection action signal
PFCradle position contact251/252/254Draw-out position signal
  1. Instalare & Cerințe de cablare
  2. Montare: Vertical upright installation, ±5° tilt allowed; inverted mounting prohibited
  3. Conexiunea circuitului principal: Conexiune frontală / rear horizontal / rear vertical connection; apply specified tightening torque for copper busbars to avoid overheating
  4. Secondary control wiring: 0.75~1.5mm² multi-core shielded cable; independent AC220V/DC24V control power supply for secondary circuit
  5. Test de izolare: Power frequency withstand test at Ui=1000V level; 12kV impulse withstand is type test only, no on-site 12kV impulse test
  6. Draw-out operation: Use dedicated crank for rack-in / rack-out; prohibit racking out breaker from connected position under live condition
  7. Operațiunea, Handling & Interlock Description

7.1 Operation Procedure

  1. Încărcare: Manual charging handle or MCH motor auto charging; charging complete, charged indicator lights on
  2. Închidere: Local front panel close pushbutton / XF remote close; verify interlock conditions before closing
  3. Opening: Local open pushbutton / MX remote opening / automatic protection tripping; after fault trip, fault reset button must be manually reset before re-closing

7.2 Interblocare (Two-incoming one bus tie scheme)

Interblocare mecanică: Steel cable mechanical interlock, physically prevents simultaneous closing of three ACBs

Interblocare electrică: Close circuit wired in series with normally closed contacts of other breakers for double protection

Cradle position interlock: Closing circuit blocked when not in connected position, closing prohibited

Fault trip interlock: Auto-transfer closing logic blocked upon SDE contact activation

  1. Întreţinere, Inspecţie & Depanare

8.1 Întreținere periodică

Semi-annual: Check charging status, on/off indication, contact temperature rise, tightness of secondary wiring

Anual: Dust cleaning, insulation inspection, trip unit test (using MicroLogic test cable)

Revizuire (fiecare 5 ani): Disassemble to inspect main contacts and arc chamber, mechanical lubrication, mechanical life verification

8.2 Depanare tipică

  1. Neînchidere

Incomplete charging; undervoltage MN coil de-energized; cradle not in connected position; interlock blocked; fault trip not reset

  1. Unintended tripping

Verify protection curve; defect la pământ; harmonic overload; loose wiring with overheating; voltage dip triggering MN undervoltage trip

  1. Charging failure

No power supply to MCH motor; jammed charging mechanism; damaged charged-ready contact

  1. No fault signal output

Wrong SDE auxiliary contact wiring, burnt contacts

  1. Condiții de mediu

Temperatura ambiantă de funcționare: -5℃ ~ +70℃; reducerea nominală necesară peste 40℃

Temperatura de depozitare: -40℃ ~ +85℃

Umiditatea relativă: ≤95% (necondens)

Altitudine: ≤2000m; derating and insulation correction required above 2000m

Grad de protectie: Device IP30; IP40 with cabinet door closed

Gradul de poluare: 3

  1. Replacement Model Information

NT06H2 → MTZ1 06H2

Cadru 630A, Icu=50kA, compatible MicroLogic trip unit

Dimensiuni de montaj, primary busbar and secondary terminals fully compatible, no cabinet modification required for in-panel retrofit

Supports ECOSTRUXURE Power software commissioning, upgraded communication interface

Schneider MasterPact NT Full Series Model List (IEC Version, Discontinued ACB, Frame 630~1600A)

Regula de denumire: NT + Frame Code + Clasa de rupere

Frame Code: 06=630A; 08=800A; 10=1000A; 12=1250A; 16=1600A

Clasa de rupere: N1 / H1 / H2 / L1; Constructii: Fix / Retragere; Poles 3P/4P; Frame without trip unit, MicroLogic to be ordered separately

Common Base Parameters: Ui=1000V, Uimp=12kV, Ue max AC690V, Class B selective protection

Breaking Class Definition (440V, Icu ultimate breaking capacity)

N1: 35cel

H1: 42cel

H2: 50cel (same class as NT06H2)

L1: 130cel (tip limitator de curent, application for high short-circuit capacity)

NT Full Model List

CadruFrame InClasa de rupereModel completIcu@440VIcw(1s)Typical 3P Fixed Part No.
NT06630ON1NT06N135cel35cel47111
NT06630OH1NT06H142cel42cel47112
NT06630OH2NT06H250cel50cel47113
NT06630OL1NT06L1130cel50cel47114
NT08800ON1NT08N135cel35cel47121
NT08800OH1NT08H142cel42cel47122
NT08800OH2NT08H250cel50cel47123
NT08800OL1NT08L1130cel50cel47124
NT101000ON1NT10N135cel35cel47131
NT101000OH1NT10H142cel42cel47132
NT101000OH2NT10H250cel50cel47133
NT101000OL1NT10L1130cel50cel47134
NT121250ON1NT12N135cel35cel47141
NT121250OH1NT12H142cel42cel47142
NT121250OH2NT12H250cel50cel47143
NT121250OL1NT12L1130cel50cel47144
NT161600ON1NT16N135cel35cel47151
NT161600OH1NT16H142cel42cel47152
NT161600OH2NT16H250cel50cel47153
NT161600OL1NT16L1130cel50cel47154

Draw-out part number: add 10 to the last digit. Example NT06H2 3P Draw-out:47203; 4P fixed part number +6 (NT06H2 4P Fixed 47119)

Derivative Isolator Models (HA version)

NTxxHA: Izolator (without trip unit, IEC60947-3)

NT06HA / NT08HA / NT10HA / NT12HA / NT16HA

Compatible Trip Unit List (Universal for full NT series)

MicroLogic 2.0: Long-time overload only

MicroLogic 5.0A: Perioadă lungă de timp + întârziere de scurtă durată + instantaneu (preferred for incoming / bus tie)

MicroLogic 6.0A: 5.0O + protectie la pamant

MicroLogic 7.0A: 6.0O + protectie cu curent rezidual + harmonic measurement

Replacement Cross Reference Table (NT → MTZ1)

Legacy NT ModelReplacement MTZ1 Model
NT06N1MTZ1 06N1
NT06H1MTZ1 06H1
NT06H2MTZ1 06H2
NT06L1MTZ1 06L1
NT08~NT16 follow same ruleMTZ1 08 /10 /12 /16 + ruperea clasei

Selection Remarks

  1. NT series fully discontinued, nu este recomandat pentru proiecte noi; MTZ1 can be used for spare parts replacement for existing projects with compatible primary and secondary interfaces.
  2. L1 current-limiting type for systems with extremely high short-circuit current, cost mai mare; H2 is preferred for normal incoming feeder and bus tie.
  3. Rated current can be derated within the same frame by changing current sensor inserts, de ex. NT06 frame available with 400A/500A/630A sensors.