Întrerupător motor Schneider GV3P50

The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor ...

  • Detalii despre produs

The Schneider GV3P50 motor circuit breaker is an ideal choice for protecting 22kW three-phase motors. Featuring thermal-magnetic tripping, an adjustable current range of 37–50A, a breaking capacity of 100kA and IP20 ingress protection rating, it is widely deployed in industrial automation, fluid conveyance, building facilities and other sectors. Key points: match breaker rating to motor power and operating conditions; avoid non-recommended applications including DC circuits, high-frequency starting and high-altitude environments. Combined with contactors and auxiliary contacts, it forms a complete motor protection and control system.

Segment de codDefiniţieDescriere detaliată
GV3Seria de produseTeSys GV3 range motor circuit breakers for three-phase motor protection
PTip de produsStandard thermal-magnetic trip unit with rotary knob operation
50Curent nominalMax adjustable trip current 50A; thermal trip setting range: 37-50A
Model completGV3P503-pole thermal-magnetic motor breaker, 37-50A, EverLink BTR screw terminals, IP20
Cod de comandăFD6887Schneider official standard part number
  1. Core Technical Specification Table
Categoria parametrilorDate tehniceObservații
Parametrii de bază
Configurația stâlpului3P (3-pol)For three-phase AC circuits
Tip de călătorieTermo-MagneticCombines thermal overload protection & magnetic short-circuit protection
Modul de operareRotary Knob ControlManual switching with ON/OFF marking
ÎncetareaEverLink BTR screw-clamp terminalsFast wiring to reduce loose connection risks
Parametrii electrici
Thermal Trip Adjustment37-50ACompatible with motors of different rated powers
Tensiune nominală de funcționare (Ui)690V și50/60Hz
Tensiune nominală de izolație (Ue)690V șiConform IEC 60947-2
Curent nominal de funcționare (Ie)50OMaximum continuous operating current
Curent de declanșare magnetic700OShort-circuit instantaneous tripping value
Capacitate maximă de rupere (Icu)100celAt 400V
Matched Motor Rating22kW @ 400VFor three-phase asynchronous motors
Mecanic & Ambient Parameters
Protecție la intrareIP20Finger-touch safe against live components
MontareMontare pe șină DINStandard 35mm top-hat rail
GreutateAproximativ. 0.45kgInstalare ușoară & transportation
Temperatura de operare-25°C ~ +60°CSuitable for most industrial environments
Temperatura de depozitare-40°C ~ +85°CWide storage temperature range
Certificari
Main ApprovalsCE, UL, CSA, CCC, EACGlobally certified per international standards
Eco CertificationsRoHS, REACHEU-compliant environmentally friendly design

III. Full GV3P Series Model List

ModelThermal Trip RangeMatched Motor Power @400VCurent de declanșare magneticCod de comandă
GV3P4025–40A18.5kW600OFD6886
GV3P5037-50A22kW700OFD6887
GV3P6548-65A30kW800OFD6888
GV3ME5037-50A22kW700OFD6890
GV3ME6548-65A30kW800OFD6891
GV3ME8056–80A37kW1000OFD6892
GV3ME10070–100A45kW1200OFD6893
  1. Alternative Cross Reference (Modele de înlocuire)
  2. In-house Schneider Replacement
Model originalÎnlocuireDescriere
GV3P50GV3ME50Identical performance; ME is enhanced version with better accessory compatibility
GV3P50New production GV3P50No functional change, only production batch update
  1. Cross-Brand Equivalents
MarcaModel echivalentMatching GradeAvantaje
ABBMS132-50★★★★★Same current rating, interchangeable mounting dimension
Siemens3RV2031-4KA10★★★★☆Thermal-magnetic trip, fits 22kW motors
EatonPKZM0-50★★★★☆3-proiectarea stâlpului, 100kA capacitate de rupere
ChintNDM2-63M/3300★★★☆☆Cost-effective for bulk replacement
DeliciosCDM1-63M/3300★★★☆☆Well-known domestic brand with high cost-performance
  1. Medii de aplicație & Field Cases
  2. Aplicații recomandate

Automatizare industrială: Supraîncărcare & short-circuit protection for 3-phase asynchronous pumps, fans and compressors

Fabricarea: Production line motor control & machine tool protection

Clădire electrică: Central air-conditioning & fire-fighting pump control

Energy Sector: Front-end protection for small generator sets and inverters

Infrastructură: Wastewater treatment equipment & bulk material conveying systems

  1. Aplicații nerecomandate

DC Circuits: Designed exclusively for AC; abnormal tripping characteristics under DC supply

Ultra-Frequent Cycling: Not applicable for >30 starts per hour (accelerates trip unit aging)

High Altitude: Derating mandatory above 2000m elevation

Corrosive Atmosphere: No anti-corrosion coating; unsuitable for strong acid/alkali surroundings

  1. Cazuri tipice de aplicare

Caz 1: Fan System Protection for Food Processing Plant

Echipamente: 3×22kW centrifugal fans, 380V/50Hz

Soluţie: GV3P50 + LC1D65 contactor combination

Rezultat: Triple protection against overload, scurtcircuit & pierdere de fază; equipment failure rate reduced by 40%

Caz 2: Submersible Sewage Pump Control at Wastewater Plant

Echipamente: 4×22kW submersible sewage pumps, 380V/50Hz

Soluţie: GV3P50 + contacte auxiliare + PLC interlock control

Rezultat: Full motor protection plus remote monitoring, lower maintenance expense

  1. Conformitatea transportului aerian & Certificare CE
  2. Conformitatea transportului aerian

UN38.3: Nu este necesar; no built-in lithium battery or supercapacitor inside

Clasa de expediere: General commodity without special transport restriction

Ambalare: Standard industrial carton to avoid transit damage

Shipping Document: Copy of CE certificate + RoHS compliance declaration available

  1. CE Certification Details

Standarde aplicabile: IEC 60947-2 (LV switchgear) & IEC 60947-4-1 (motor control equipment)

Valid Region: European Economic Area (SEE) & global territories accepting CE marking

Validity: Permanently valid complying with current normative requirements

Anchetă: Check Schneider official website product page or certification database

VII. Depanarea defecțiunilor comune

Fault SymptomProbable CausesRemedial Actions
Frequent thermal tripping1. Suprasarcina motorului1. Inspect motor load
2. Underset trip current2. Adjust rotary knob to correct setting
3. Excess ambient temperature3. Improve ventilation or derate operating current
Nu se poate închide1. Tripping latch not reset1. Toggle knob OFF then ON to reset
2. Short circuit in wiring2. Troubleshoot short-circuit faults
3. Blocaj mecanic3. Clean or replace breaker
No protection upon phase loss1. Cablaj greșit1. Recheck three-phase cabling
2. Damaged trip unit2. Replace trip component
3. Severe 3-phase unbalance3. Balance connected loads
Overheated terminals1. Loose terminals1. Retighten terminal screws
2. Undersized cable2. Upgrade to proper wire gauge
3. Terminal oxidation3. Clean terminals or replace unit

VIII. Sizing Guidelines & Reguli de selecție rapidă

Quick Selection Formula Summary

> GV3P series 3-pole thermal-magnetic breakers;

> Suffix number denotes upper current limit;

> 40 = 25–40A, 50 =37–50A, 65 max at 65A;

> Power matching rule: 40 for 18.5kW, 50 for 22kW, 65 for 30kW.

Reguli rapide

  1. Potrivire curentă: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
  2. Power Reference: At 400V, GV3P50 matches 22kW motor (~44A nominal)
  3. Accessory Option: Contact auxiliar: GV3AE11 (1NU+1NC) / GV3AE20 (2NU)
  4. Distanța de montaj: DIN rail install; ≥10mm clearance for heat dissipation, away from heat-generating devices
  5. Instalare & Wiring Instruction
  6. Etape de instalare

Confirm standard 35mm DIN rail

Snap breaker firmly onto rail

Incoming power: top-feed or bottom-feed acceptable

Motor cable connection: terminal tightening torque 2.5Nm recommended

  1. Specificații de cablare

Wire cross-section range: 1.5mm² min ~35mm² max

Terminal: EverLink BTR screw terminal compatible with copper/aluminum conductors

Phase marking: R/S/T corresponds to L1/L2/L3; no neutral connection (3P without N pole)

  1. EMC Protection

Maintain ≥50mm clearance between breaker and contactors

Separate control wiring from power cables to avoid cross-interference

Install EMC filter if needed for EMI suppression

Full Application Overview for Schneider GV3P50 Motor Circuit Breaker

  1. Rezumatul aplicației de bază

Schneider GV3P50 is a 3-pole thermal-magnetic motor circuit breaker with adjustable trip 37–50A, rated for 22kW three-phase asynchronous motors @400V. Its core functions: motor overload, scurtcircuit & phase-loss protection plus manual switching, widely used in below industries:

  1. Detailed Application Classification
  2. Automatizare industrială & Fabricarea
AplicațieEchipamenteProtection RequirementApplication Benefit
Controlul liniei de producțieTransportoare, sorters, mașini de ambalareContinuous running protection against overload shutdownImprove line stability & reduce breakdown loss
Mașini-unelteMilling, lathe & grinder spindle motorsProtection for frequent start-stop & instant short-circuit breakingProtect costly equipment and extend service life
Bulk HandlingBucket elevators, screw conveyorsStall & phase-loss protectionPrevent burnout & cut maintenance cost
General MachineryImprimare, textile & plastic processing machinesProtectie la suprasarcina + emergency manual cut-offSimplify control circuit & enhance operational safety
  1. Fluid Conveyance Systems
AplicațieEchipamenteProtection FeatureTypical Parameter
Pump SetIndustrial pump, fire pump, sewage pumpDual overload + phase-loss protection, moisture-resistant22kW/380V,50Hz, setting 37–50A
Fan UnitCentrifugal/axial/induced draft fansLight-load startup protection against impeller jammingAdapt to current fluctuation from variable duct resistance
CompresorAer & compresoare frigorificeHeavy-start & protectie la supraincalzireTolerate frequent loading/unloading cycles
Vacuum PumpIndustrial & water-ring vacuum pumpsLow-current idle-running damage preventionAdjustable setting for light-load operation
  1. Clădire & Municipal Infrastructure
SectorSistemKey DemandMetoda de montare
HVACCentral air-con, air handler, turn de racireStable continuous-duty protectionDIN rail mounted with contactor interlock
Automatizarea clădirilorFire control, security & elevator room equipmentEmergency cut-off safetyRemote monitoring via PLC
WastewaterAerator & sludge processing unitsPraf & moisture resistanceCabinet installation with IP20 protection
Energie NouăSmall gen-set & invertor PVSupracurent & grid-fault isolationRated up to 690V high-voltage system
  1. Other Industrial Sectors
IndustrieEchipamenteSpecial RequirementMatching Advantage
AgriculturăIrrigation pump & feed processorOutdoor installation against grid voltage swingWide operating temp: -25°C~+60°C
MineritSmall conveyor & mine ventilation fanHeavy startup + high short-circuit withstand100kA high breaking capacity
Mâncare & BăuturăMixer & sterilization equipmentSanitary & easy-clean layoutNo exposed live parts for hygiene compliance
PharmaFarmaceutic & cleanroom machineryPrecise control & low failure rateHigh accuracy thermal-magnetic trip characteristic

III. Aplicații nerecomandate (Avoidance Guide)

Unsuitable ConditionMotivSoluție alternativă
DC CircuitAbnormal tripping characteristic under DC (rated only AC 50/60Hz)Dedicated DC-rated Schneider circuit breakers
>30 Starts/HourAccelerated trip unit ageing & shortened service lifeGV3ME enhanced series or match with soft starter
Altitude>2000mPerformance derating requiredHigh-altitude specified breaker or add upstream protection
Strong Corrosive AtmosphereUncoated terminals prone to oxidationAnti-corrosion coated model or protective enclosure
Explosion Hazard ZonesStandard version without ATEX certificationATEX certified explosion-proof breakers
Single-Phase Motors3-pole structure cannot provide single-phase protectionGV2 single-phase motor breaker series
  1. Detailed Field Application Cases

Case1: 22kW Fan Protection in Food Factory

Setup: 3×22kW centrifugal fans 380V/50Hz, independent control per unit

Sistem: GV3P50 + LC1D65 contactor + GV3AE11 auxiliary contact

Logică: Manual/Auto switch; auto stop & alarm upon overload

Rezultat: Triple protection realized; failure rate -40%, maintenance cost -30%

Case2: Submersible Sewage Pump Control at WWTP

Setup: 4×22kW submersible sewage pumps 380V/50Hz, alternating operation

Sistem: GV3P50 + PLC interlock + level transducer

Stare: Humid environment, 10~15 starts/hour frequent cycling

Rezultat: Anti-stall burnout + remote auto-switching, improved system reliability

Case3: Central Air-conditioning for Shopping Mall

Setup: 3×22kW chilled water pumps with VFD control 380V/50Hz

Sistem: GV3P50 + invertor + temperature sensor

Caracteristică: Speed auto-adjust by return water temp; coordinated protection by inverter + breaker under overload

Rezultat: ≥30% energy saving, service life doubled, superior system stability

  1. Recommended Matching Components & Sfaturi de selecție
  2. Recommended Matching List
AccesoriiPartea nr.FuncţieValoare
Contactor ACLC1D65Remote control for frequent start-stopEnable automatic control & reduce manual operation
Contact auxiliarGV3AE111NO+1NC signal outputAlarm feedback or PLC interlock
Releu termic de suprasarcinaLRD4363Optional secondary overload protectionDouble motor protection for enhanced safety
Control PushbuttonSeria XB4Manual start/stopHMI & emergency shutdown function
  1. Sizing Rules
  2. Power Match: 22kW (~44A @400V) optimally paired with GV3P50 (37-50A)
  3. Trip Setting: Motor rated current ×1.1 ≤ breaker setting ≤ motor rated current ×1.3
  4. Mount Clearance: ≥50mm gap to adjacent contactors; ≥10mm free space for heat dissipation
  5. Wiring Torque: Cable terminal tightening torque fixed at 2.5Nm
  6. Ambient Derate: Derate 1% rated current per every 1°C rise above +40°C ambient temperature