A classic motor protection series from Schneider Electric, designed for low-power motors rated 0.1-32A. It provides protection against short circuit, overload and phase loss. Equipped with a rotary knob for manual closing and tripping, and built-in thermal-magnetic trip unit to deliver delayed overload protection and instantaneous short-circuit protection. The code 10 represents an adjustable setting current range of 4-6.3A, compatible with 1.5-2.2kW three-phase motors at 400V. Models suffixed with C are domestic versions, while those without C are imported versions. Both share identical performance parameters and comply with IEC and GB standards.
- Codul modelului Explicația
| Segment | GV2 | P.M | 10 | C |
| Sens | Seria de produse: TeSys Deca GV2 motor circuit breaker | Tipul operațiunii: Panel Mount Rotary Knob with thermal-magnetic protection | Setting current range code: 4-6.3O | Origin code: Manufactured in China |
- Specificatii tehnice principale
| Categorie | Date tehnice | Observații |
| General Information | ||
| Numele produsului | TeSys Deca GV2PM Motor Circuit Breaker | Specifically designed for motor control and protection |
| Cod de comandă | GV2PM10C | Standard commercial model |
| Stare produs | Active | Standard product of Schneider Electric |
| Parametrii electrici | ||
| Polonii | 3P (Trifazat) | For three-phase asynchronous motors |
| Setarea intervalului de curent | 4-6.3O | Adjustable via rotary knob, for 1.5-2.2kW motors (400V) |
| Curent nominal de funcționare (Ith) | 6.3O | Maximum continuous operating current |
| Tensiune nominală de izolație (Ui) | 690V | Withstand voltage level of insulation system |
| Tensiune nominală de funcționare (Ue) | 400V și (50/60Hz) | Standard industrial voltage |
| Capacitate maximă de întrerupere a scurtcircuitului (Icu) | 100kA @ 400V | Conform IEC 60947-2 |
| Tip de protecție | Termo-magnetic | Delayed overload protection + protectie instantanee la scurtcircuit |
| Parametri mecanici | ||
| Dimensiuni (L×A×D) | 89mm×85mm×91mm | Compact structure to save cabinet space |
| Greutate | Aproximativ. 280g | Easy for installation and maintenance |
| Montare | 35mm Montare pe șină DIN | Conform EN 60715 |
| Terminale | Borne cu șuruburi, for 1.5-4mm² conductors | Suitable for solid and stranded wires |
| Modul de operare | Rotary knob (OFF-ON-RESET) | Manual reset required after tripping |
| Parametrii de mediu | ||
| Temperatura de operare | -20°C ~ +60°C | Adaptable to industrial environments |
| Protecție la intrare | IP20 | Prevents finger access to live parts |
| Certificari | CE, CCC, UL, CSA | Conform standardelor internaționale de siguranță |
- Full Range of GV2PM Rotary Knob Motor Circuit Breakers
| Model | Setarea intervalului de curent | Puterea motorului egală (400V) | Observații |
| GV2PM01C | 0.1-0.16O | 0.025-0.04kW | Minimum current rating |
| GV2PM02C | 0.16-0.25O | 0.04-0.06kW | |
| GV2PM03C | 0.25-0.4O | 0.06-0.1kW | |
| GV2PM04C | 0.4-0.63O | 0.1-0.16kW | |
| GV2PM05C | 0.63-1O | 0.16-0.25kW | |
| GV2PM06C | 1-1.6O | 0.25-0.4kW | |
| GV2PM07C | 1.6-2.5O | 0.4-0.63kW | |
| GV2PM08C | 2.5-4O | 0.63-1.1kW | |
| GV2PM10C | 4-6.3O | 1.1-2.2kW | Modelul actual |
| GV2PM14C | 6.3-10O | 2.2-3kW | |
| GV2PM16C | 9-14O | 3-4kW | |
| GV2PM20C | 13-18O | 4-5.5kW | |
| GV2PM21C | 17-23O | 5.5-7.5kW | |
| GV2PM22C | 23-32O | 7.5-11kW | Maximum current rating |
- Concurent & Modele echivalente
| Marca | Model | Setarea intervalului de curent | Modul de operare | Descriere de înlocuire |
| Schneider Electric | GV2ME10C | 4-6.3O | Push-button | Alternative with different operation mode within the same series |
| Siemens | 3RV2011-0JA10 | 4-6.3O | Rotary knob | Cross-brand functional replacement |
| ABB | MS116-6.3 | 4-6.3O | Rotary knob | Cross-brand functional replacement |
| Eaton | DIL M9-10 | 4-6.3O | Rotary knob | Cross-brand functional replacement |
| Chint | NDM1-63/3300 | 4-6.3O | Rotary knob | Economical domestic alternative |
- Medii de aplicație & Typical Cases
5.1 Aplicații recomandate
Automatizare industrială: Protection for small pumps, fans and conveyor motors; compatible with PLC control circuits
Facilități de clădire: Control and protection for air conditioning fans, pompe de apa, elevator door motors and fire linkage equipment
Mâncare & Beverage Industry: Motor protection for packaging machines, filling machines and small mixers; meets hygiene requirements
Echipament medical: Safety protection for laboratory stirrers, centrifuges and small medical pumps
Utilaje agricole: Protection for outdoor motors such as irrigation pumps, small harvesters and feed mixers
Centre de date: Protection for precision air conditioner fans, cooling water pumps and UPS cooling fans
5.2 Non-recommended Applications
Pornire frecventă: Not applicable for equipment starting more than 10 ori pe oră. GV3 series or soft starters are recommended instead.
Heavy-duty start: Not suitable for motors with starting current over 8 ori mai mare decât curentul nominal. Additional overload protection is required.
Explosive hazardous areas: No explosion-proof certification. Do not use directly in Zone IIC explosive areas.
DC motors: The GV2 series is designed exclusively for AC motors. Use dedicated protective devices for DC motors.
5.3 Cazuri tipice de aplicare
Caz 1: Mixing System in Pharmaceutical Factory
Aplicație: Supraîncărcare, short-circuit and phase loss protection for 1.5kW reactor stirring motors
Configurare: GV2PM10C + LC1D12 Contactor + Control Buttons
Beneficii: Prevents motor burnout caused by agitator jamming; complies with GMP standards and trips rapidly for equipment protection during faults.
Caz 2: Air Conditioning System in Commercial Buildings
Aplicație: Protection and control for 2.2kW fresh air handling units and water pump motors
Configurare: GV2PM10C + Building Automation System (BAS) + Senzori de temperatură
Beneficii: Enables automatic start/stop of fans and pumps, protects motors against overload, reduces maintenance costs and improves energy efficiency by 12%.
Caz 3: Conveyors on Automated Production Lines
Aplicație: Protection and control for 1.1kW small conveyor motors
Configurare: GV2PM10C + PLC + Emergency Stop Buttons
Beneficii: Avoids motor damage from conveyor jamming, works with emergency stop system for safe shutdown, and shortens Mean Time To Repair (MTTR) to within 3 minute.
Caz 4: Aeration System in Wastewater Treatment Plant
Aplicație: Protection and control for 2.2kW small aeration fans
Configurare: GV2PM10C + Liquid Level Sensors + Automatic Control Cabinet
Beneficii: Performs reliably in humid environments, prevents fan burnout from overload, realizes unattended automatic operation and cuts operational costs by 30%.
- Sfaturi de selecție & Quick Reference Rules
Selection Rhythm
Choose GV2PM10C,
Interval de curent 4 to 6.3A,
Matches motors 1.5 to 2.2kW,
Rotary knob operation, IP20 rating,
35mm șină DIN, 89mm latime,
High breaking capacity with thermal-magnetic protection,
Safeguards motors from overload and short circuit,
Reliable for industrial and building applications.
Quick Reference Rules
- Potrivire curentă: 10 = 4-6.3A; 08 = 2.5-4A; 14 = 6.3-10A. Larger figure means wider current range.
- Modul de operare: PM = Rotary knob; ME = Push-button; LP = Magnetic-only type (numai protectie la scurtcircuit).
- Potrivirea puterii: 4-6.3A corresponds to 1.5-2.2kW @ 400V. Approximate formula: Current × 0.5 ≈ Matched motor power (kW).
- Installation Features: 89mm latime, 35mm Montare pe șină DIN, Grad de protecție IP20, ideal for installation inside control cabinets.
- Depanare
| Fenomen de eroare | Cauze posibile | Soluții |
| Deplasări frecvente | Setting current too low | Turn the rotary knob clockwise to increase current within 4-6.3A |
| Suprasarcina motorului / rotor blocat | Check for overloading and eliminate jamming | |
| Phase loss operation | Inspect three-phase power supply and repair broken wires or poor contacts | |
| Neînchidere | Knob not reset | Turn the knob to OFF position then back to ON after tripping |
| Blocaj mecanic | Clear foreign objects or replace damaged components | |
| Cablaj greșit | Recheck three-phase wiring and eliminate short circuits | |
| Overheated contacts | Borne de cablare slăbite | Retighten terminals for good contact |
| Excessive load | Reduce load or replace with higher-rated circuit breaker if needed | |
| Temperatura ambientală excesiv de ridicată | Improve ventilation and keep temperature below 60°C |
- Key Features Summary
- Protecție cuprinzătoare: Thermal-magnetic trip unit provides delayed overload, instantaneous short-circuit and phase loss protection, conform cu IEC 60947-4-1.
- Wide Compatibility: 4-6.3A adjustable current range for 1.5-2.2kW three-phase motors; easy operation via rotary knob.
- Structură compactă: Dimension 89mm×85mm×91mm with 35mm DIN rail mounting to save cabinet space.
- Fiabilitate ridicată: Wide operating temperature range (-20°C ~ +60°C) and IP20 rating for harsh industrial conditions.
- Instalare ușoară & Întreţinere: Standard interface for seamless matching with contactors; simple knob reset after faults.
Application Scenarios of Schneider GV2PM10C (4~6,3A)
This is a 3-pole rotary-knob motor circuit breaker with thermal-magnetic protection. It is suitable for 1.1~2.2kW three-phase asynchronous motors at 400V. Adopting DIN rail mounting, it integrates overload, short-circuit and phase loss protection, and is widely used in industrial, building, light industry and municipal fields.
- Principalele scenarii de aplicare
1.1 Linii de producție automate industriale
Small belt conveyors and roller motors
Workshop auxiliary fans and dust extraction fans
Auxiliary power motors for manipulators and small positioners
Machine tool cooling pumps and lubrication pumps
Combined with PLC and relay circuits for local and remote control & protecţie
1.2 HVAC & Building Electromechanical Systems
Terminal fans, fresh air fans and exhaust fans of central air conditioning
Small circulating water pumps and make-up water pumps for building water supply & drainage
Cooling fans for computer room precision air conditioners
Auxiliary fans and door drive motors in elevator rooms
Fire exhaust fans and damper linkage motors (meeting fire power distribution standards)
1.3 Industria ușoară, Mâncare & Industria ambalajelor
Small mixers, blenders and feeding machines
Packaging machines, labelers and conveyor drive motors
Filling equipment and small roller conveyors
Ventilation fans and washing pumps for food workshops
(Compact body and qualified protection level, suitable for dusty and humid workshop conditions)
1.4 Tratarea apei & Municipal Engineering
Small aeration fans, dosing pumps and reflux pumps in sewage treatment plants
Booster pumps for landscape pools and residential water supply
Small power motors inside on-site control boxes of pumping stations
Fans and water pumps supporting river and pipeline monitoring equipment
1.5 Laboratory & Medical Supporting Equipment
Laboratory stirrers, centrifuges and circulating water pumps
Exhaust and fresh air system motors for medical clean rooms
Medical water purifiers and small delivery pumps
(Sensitive protection effectively prevents equipment stalling and motor burnout)
1.6 Depozitare, Logistică & Supermarkets
Warehouse ventilation fans and dust removal equipment
Condenser fans and fresh air systems for supermarket refrigeration units
Motors for light sorting lines and small roller conveyors
1.7 Utilaje agricole & Outdoor Light-duty Equipment
Small irrigation pumps and spray devices for farmland
Feed mixers and small agricultural ventilation equipment
(Wide temperature adaptability for outdoor simple electrical control boxes)
- Scenarii nerecomandate
- High-frequency starting equipment: Mai mult decât 10 starts per hour may cause false tripping. Dedicated starting solutions are recommended.
- Heavy-load motors with high starting current: Starting current far exceeds normal level; match with thermal relays and contactors additionally.
- Explosive hazardous areas: Without explosion-proof certification, not allowed for direct use in explosive zones.
- DC motors and high-power single-phase motors: Designed for three-phase AC motors only.
- Environments with long-term temperature above +60°C or strong corrosive gas: Protection accuracy and service life will be reduced.
- Common Matching Solutions for On-site Use
- Standard motor circuit: GV2PM10C + LC1D Contactor + Push Buttons (Local start & Stop)
- Automatic control circuit: GV2PM10C + Contactor + PLC (Remote automatic control)
- Fire linkage circuit: GV2PM10C + Fire Module + Contactor (Fire forced start / forced trip)
Contactor,întrerupător de circuit,invertor solar,contor electric,baterii solare


















NH42-63-318x560.png)