LAD6K10F = TeSys Deca front-mounted mechanical latching module (mechanical latch accessory) for contactors. Release coil voltage: 110…127 V AC/DC (110VAC specification as required)
Part Number Rule: LAD6K10 + voltage suffix
LAD6K10B: 24V AC/DC
LAD6K10F: 110~127V AC/DC (matches your 110VAC requirement)
LAD6K10M: 220~240V AC/DC
Funcţie: Clipped onto the front face of LC1D contactors to achieve pulse closing + mechanical holding.
- Send a short pulse to the contactor main coil for closing.
- The mechanical latch locks the contactor, and the main coil can be de-energized while the main circuit remains closed.
- To open the circuit, send a short pulse to the E1/E2 release coil on LAD6K10; manual unlock is also available via the pushbutton.
Scop: For long-term closed circuits, continuous power supply to the contactor coil is eliminated, reducing power consumption and coil overheating.
Contactoare compatibili
LC1D09 ~ LC1D80A, LC1DT20~DT80A, CAD control relays (excluding low-power coil versions)
Specificații electrice cheie
Release coil voltage: 110…127 V AC/DC, 50/60Hz
Consumul de energie: 25VA (AC); 30W (DC)
Tensiunea nominală de izolație Ui: 690V (IEC 60947-5-1)
Rezistenta mecanica: 500,000 operațiuni
Frecvența maximă de funcționare: 1200 cicluri/oră
Coil energization limit: Only pulse operation permitted; maximum continuous energization ≤ 10 secunde. Continuous power supply will burn out the release coil.
Minimum pulse width: ≥100ms for AC circuits; ≥250ms for DC circuits
Clasa de protectie: IP2X
Temperatura ambiantă de funcționare: -25℃ ~ +55℃
Greutate netă: 0.07kg
Montare: Tool-free snap-on front fit; terminals E1, E2 (release coil of latch module)
Operating Logic (Critic)
- Închidere: Apply a short pulse to contactor main coil A1/A2 → contactor closes, LAD6K10 mechanical latch engages → main coil power can be cut off, main circuit stays ON.
- Opening: Send a short pulse to E1/E2 (110VAC release coil) → mechanical latch trips → contactor opens. A manual reset button is provided for local unlocking.
⚠️ Do not energize the contactor main coil and the latch release coil simultaneously.
Selecţie & Informații de înlocuire
- Larger-size counterpart: LA6DK20, compatible with LC1D80~D150 high-current contactors. LAD6K10 only covers up to LC1D80A.
- Alternative interne: Mechanical latch attachments from Chint/Delixi with identical mounting dimensions and control logic; verify terminal definitions and coil power consumption before replacement.
- Spare part note: LAD6K10F is sold separately as an accessory; contactor body is not included.
Ghid de depanare
- Contactor closes but cannot stay latched: Mechanical latch jamming, insufficient pulse duration, excessive wear on contactor stroke.
- Electric release fails: Loose E1/E2 wiring, burnt coil, supply voltage outside 110~127V range; check that the pulse width is long enough.
- Arsarea bobinei: Release coil kept energized longer than 10s (the most common root cause).
Aplicații tipice
Fire-fighting pumps, fani, bus tie breakers, and other power circuits requiring prolonged closed status, to cut continuous coil power and reduce heating.
Physical Dimensions of LAD6K10F (Mechanical Latching Module)
Înălţime: 44 mm
Lăţime: 44 mm
Protruding depth (front extension): 47 mm
Greutate netă: 0.07kg (manufacturer nominal); field measurement approx. 0.088kg (within tolerance)
Metoda de montare: Front snap-on fit directly onto LC1D contactor front face. No increase in contactor width; only adds forward depth.
Cabinet Cutout & Depth Reference
(Omitted redundant duplicated content; below is the full model list in English)
- Full Model List of Mechanical Latching Accessories (Matching LC1D Series)
① LAD6K10 Series (For LC1D09~LC1D80: LC1D09/D25/D40/D65/D80)
LAD6K10B: 24V AC/DC
LAD6K10E: 48V AC/DC
LAD6K10F: 110/127V AC/DC (Current Model)
LAD6K10M: 220/240V AC/DC
LAD6K10U: 256~277V AC/DC
② LA6DK20 Series (For LC1D80~LC1D150 high-current contactors)
LA6DK20B / E / F / M / U (same voltage suffix codes above)
- Combined Model Table: LC1D + LAD6K10F (110V Version for Selection)
| Contactor Body | Compatible Latching Module | Combined Part Number Example (110V) |
| LC1D09 | LAD6K10F | LC1D09F7C + LAD6K10F |
| LC1D12 | LAD6K10F | LC1D12F7C + LAD6K10F |
| LC1D18 | LAD6K10F | LC1D18F7C + LAD6K10F |
| LC1D25 | LAD6K10F | LC1D25F7C + LAD6K10F |
| LC1D32 | LAD6K10F | LC1D32F7C + LAD6K10F |
| LC1D38 | LAD6K10F | LC1D38F7C + LAD6K10F |
| LC1D40A | LAD6K10F | LC1D40AF7C + LAD6K10F |
| LC1D50A | LAD6K10F | LC1D50AF7C + LAD6K10F |
| LC1D65A | LAD6K10F | LC1D65AF7C + LAD6K10F |
| LC1D80 | LAD6K10F (Upper Limit) | LC1D80F7C + LAD6K10F |
| LC1D95 & mai sus | Only LA6DK20F | LC1D95F7C + LA6DK20F |
III. Full List of Common TeSys D Accessories
- Contacte auxiliare: LADN11 (1NU+1NC), LADN20, LADN02
- Timing heads: LADT0, LADT2, LADT4 (ON-delay)
- Electric + mechanical interlock: LA9D0990 (for reversing contactor pairs)
- Coil surge suppression: LAD9R1V (RC snubber)
- Terminal protective cover: LAD965
- Critical Usage Restrictions
- LAD6K10F only supports up to LC1D80; LA6DK20 must be used for LC1D95 and larger models.
- The E1/E2 release coil must only receive pulse signals (≥100ms). Continuous energization will burn out the coil.
- Domestic models end with suffix C; imported models have no suffix C. They share identical dimensions and are fully interchangeable with LAD6K10F.
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor