Serie: Zelio-Time RE7 On-delay Timing Relay | Stare: Întrerupt (Production ceased on 2021-04-02) Core Specifications Item Parameter Function On‑delay (Tip A) Interval de sincronizare 0.05 s … 300 h, multi‑range adjustable Coil Supply 24 V AC/DC Contacts 2 change‑over contacts (2C/O, DPDT), silver‑nickel contacts Conventional thermal current Ith 8 A Mounting DIN‑rail mounting, width 22.5 mm Terminals Screw terminals, tightening ...

  • Detalii despre produs

Serie: Zelio-Time RE7 On-delay Releu de sincronizare | Stare: Întrerupt (Production ceased on 2021-04-02)

Specificații de bază

ArticolParametru
FuncţieÎntârziere la pornire (Tip A)
Interval de sincronizare0.05 s … 300 h, multi‑range adjustable
Coil Supply24 V AC/DC
Contacte2 change‑over contacts (2C/O, DPDT), silver‑nickel contacts
Curentul termic convențional Ith8 O
MontareMontare pe șină DIN, width 22.5 mm
TerminaleBorne cu șuruburi, tightening torque 0.6‑1.1 N·m
Reset time50 Domnișoară; Minimum trigger pulse 20 ms
Timing accuracy±10 % of full‑scale value; Repeat accuracy ±0.2 %
Rezistenta mecanica20 milioane de cicluri

Codul modelului Explicația

RE7: Zelio-Time RE7 timing relay series

T: On-delay function

P: Multi-range timing

13: 2 contacte de schimbare

ACEST: 24 V AC/DC coil supply

Official Replacement Model

RE22R2AMR (Direct functional replacement, la întârziere, 0.05s-300h, 24-240V AC/DC, 2C/O, 22.5 mm DIN-rail footprint)

Nota: RE7TP13BU is no longer factory-supplied; only surplus stock / used units are available on the market. Pentru proiecte noi, use RE22R2AMR directly.

Aplicații tipice

PLC output delay, motor start-up delay, întârziere la iluminare, equipment power-on sequence control.

Judging whether Schneider RE7TP13BU Time-Delay Relay Requires Replacement

RE7TP13BU is discontinued, genuine new factory units are unavailable; most available units are surplus stock or second-hand. As an analog electronic timing relay, its typical failures include timing deviation, contact failure and no-operation. Evaluation covers visual inspection, powered static check, functional test and contact load assessment.

  1. Inspecție vizuală (Power-off status)

Replace the unit if any of the following occurs:

  1. Cracked housing, burn marks, arc scorch marks on terminals or melted plastic;
  2. Terminale libere, oxidat / corroded copper conductors, arc black spots at crimp points;
  3. Sticky, slipping or idling timing adjustment knob that cannot switch ranges;
  4. Visible water intrusion, oil contamination or corrosion on internal PCB;
  5. Illegible or peeled-off nameplate marking, model cannot be confirmed.
  6. Powered Static Check (Coil energized only, no load connected)

Coil supply: 24V AC/DC

  1. Indicator LED completely off after power-on:

Verify supply voltage and polarity. If supply is correct but LED stays off → internal power circuit damage, mandatory replacement.

  1. Flickering or dimming indicator LED: Degraded internal voltage-regulation components, imminent total failure; înlocuire recomandată.
  2. Abnormal buzzing / faint arcing noise upon power-on: Internal PCB leakage; replace immediately.

✔ Normal status: Indicator LED stable ON, no abnormal noise.

  1. Core Functional Test (Critical step for timing performance validation)

Funcţie: Întârziere la pornire

Logică: Coil energized → timing starts; output contacts change state only after preset time elapses.

Test procedure:

  1. Set a short delay e.g. 10 s;
  2. Apply 24 V to coil, monitor 2 change-over contacts with multimeter continuity mode;
  3. Contacts remain in original state immediately after coil energization; contacts shall reliably toggle after 10 s; contacts reset instantly when coil power is removed.

Replacement trigger conditions (any of below)

  1. Contacts toggle immediately upon coil energization (zero delay): Timing chip damage.
  2. Contacts never act when preset time expires: Timing circuit failure.
  3. Severe timing deviation: Setting 10 s but actual delay is 30 s, or inconsistent timing. Allowable tolerance for RE7 is ±10 % full-scale; deviations far beyond this indicate component aging.
  4. Intermittent timing failure; function temporarily restored after power-cycle: Capacitor aging, the most frequent failure mode for this model.
  5. Abnormal reset: Contacts fail to reset and remain latched after coil de-energization.

Supplementary note: Minimum trigger pulse 20 ms. Input pulses shorter than this will not start timing — this is product characteristic, not a fault.

  1. Output Contact Load Test (Under practical load conditions)

Evaluarea contactului: 8 A resistive load for 2 contacte de schimbare

  1. Timing passes no-load test, yet contacts fail to close / open with actual load connected.
  2. Severe terminal overheating under loaded operation.
  3. Obvious arcing at contact switching, intermittent load ON/OFF.

👉 Silver-nickel contact wear / erosion; cannot be repaired, înlocuiți direct.

Nota: Damaged contacts render the unit unsafe even if timing logic works correctly; unexpected equipment sequence malfunctions may occur.

  1. Service-life & Environmental Assessment
  2. Rated mechanical endurance: 20 milioane de cicluri. For equipment with frequent start-stop cycles over many years, consider spare-part replacement even if current performance seems normal.
  3. Long-term exposure to high cabinet temperature, humidity or dust accelerates electrolytic capacitor aging for this legacy series; latent random-failure risks exist.
  4. Replacement-after-failure Selection

Genuine replacement: RE22R2AMR

24-240VAC/DC supply, la întârziere, 0.05s-300h, 2 contacte de schimbare, 22.5 mm DIN-rail mounting footprint.

Quick Troubleshooting Reference Table

FenomenConcluzie
LED off with correct supply voltageÎnlocui
Large timing drift / intermittent faultsÎnlocui
Normal no‑load test, contact malfunction under loadÎnlocui
Slipping knob / burnt housingÎnlocui
Accurate timing, no overheating or arcingMay remain in service

Eșecuri comune & Remedies for Schneider RE7TP13BU Time-Delay Relay

Important notice: RE7TP13BU is discontinued. Electrolytic-capacitor aging is its dominant failure cause. PCB damage cannot be repaired; înlocuiți unitatea completă, dis-assembly for repair is not recommended. Evaluarea bobinei:24V AC/DC, 2 change-over contacts rated 8 A.

Vina 1: No indicator light, no response after coil energization

Cauze posibile

  1. Incorrect supply voltage, loose / poor wiring connections;
  2. Blown fuse or fault in external supply circuit;
  3. Internal power-stage damage (electrolytic-capacitor breakdown, open-circuit coil).

Remedies

  1. Measure coil terminal voltage to confirm 24V AC/DC; verify screw-terminal torque 0.6-1.1 N·m.
  2. If external circuit is healthy and full voltage is present but unit remains dead → internal damage; înlocuiți unitatea.

Do not repeatedly apply power, risk of secondary damage to downstream equipment.

Vina 2: LED ON, but zero delay; contacts act immediately upon power-on

Cauze posibile

  1. Accidental dip-switch mode misconfiguration;
  2. Degraded / broken timing circuitry (timing IC, timing-capacitor breakdown).

Remedies

  1. Confirm mode selection is On-delay, verify no wrong-position dip-switch.
  2. If settings are correct yet contacts toggle instantly → component failure; înlocuiți releul.

Vina 3: Contacts never act when preset time expires

Cauze posibile

  1. Wrong time-range selection; set delay far exceeds actual waiting period;
  2. Undervoltage coil supply;
  3. Internal timing-circuit failure;
  4. Mechanical contact jamming.

Remedies

  1. Test with short-time setting (e.g.10 s) to eliminate configuration error.
  2. Ensure coil supply voltage ≥85 % of rated voltage.
  3. If short-time test still yields no contact action → unit failure; înlocui.

Vina 4: Unstable timing; timing drifts fast/slow intermittently (Most-common failure for this model)

Symptoms: Setpoint 10 s yields actual delays ranging from 5 s to 25 s; temporary recovery after power-cycle, random fault recurrence.

Cauza de bază: Electrolytic-capacitor aging inside RE7 series; cabinet high temperature accelerates degradation; typical aging failure for legacy units.

Remedies

  1. Avoid continuous ambient temperature above 60 °C.
  2. Allowable timing tolerance: ±10 % full-scale; deviation exceeding this threshold indicates component aging.
  3. Random drift cannot be repaired. Replace unit immediately; continued operation risks uncontrolled equipment sequence faults.

Vina 5: Contacts fail to reset and stay latched after coil de-energization

Cauze posibile

  1. Insufficient reset interval: RE7TP13BU requires minimum 50 ms reset time; rapid power-cycle prevents full reset.
  2. Contact welding due to overload-induced contact erosion.
  3. Internal mechanical jamming.

Remedies

  1. Ensure coil de-energization duration >50 ms before re-energization.
  2. Measure contact continuity in power-off condition. Persistent continuity confirms contact welding; mandatory replacement.
  3. Verify downstream-load current does not exceed 8 A resistive rating to prevent repeated damage to new relay.

Vina 6: Good no-load timing performance, yet intermittent ON/OFF and terminal overheating under load

Cauze posibile

Contact wear-erosion; actual load exceeds contact rating. Electrovalve / bobine de contactor (sarcini inductive) require contact derating.

Remedies

  1. 8 A rating applies purely for resistive loads. For inductive loads such as solenoid valves and contactor coils, derate operating current to 3-4 A maximum.
  2. Replace unit if contacts are eroded (nereparabile).
  3. For high-power inductive loads, install intermediate relay for isolation; avoid direct-driving via timing-relay contacts.

Fault7: Adjustment knob slips or cannot switch ranges

Cauze posibile: Worn-out internal plastic gears or potentiometer.

Remediu: Time adjustment function lost; înlocuiți unitatea.

Fault8: LED pâlpâit, internal buzzing noise

Cauza: Degraded power-supply filter capacitor; PCB leakage risk.

Remediu: Potential short-circuit hazard; replace unit immediately, do not keep in service.

Quick-distinguish: External-wiring fault vs Relay-unit internal fault

Disconnect all load wiring from output contacts; energize coil only, measure relay-body contacts with multimeter continuity mode.

  1. Full-function performance in no-load test, failure occurs only under load → contact damage or load over-rating.
  2. Timing abnormality already present in no-load test → internal relay-unit failure.

Replacement Option

Obsolete RE7TP13BU, recommended replacement RE22R2AMR

Nota: Pin-out definitions are not identical between the two models. Cross-check wiring before replacement; direct plug-and-swap is not feasible.

Recomandări de întreținere

  1. For high-temperature cabinet environments, keep spare-stock of legacy RE7 timing relays. Electrolytic-capacitor aging creates hidden faults that only surface during equipment downtime.
  2. Do not drive inductive-loads directly via timing-relay contacts; add intermediate-relay isolation.