Schneider RM17TG00 Phase Sequence & Releu de monitorizare a pierderii de fază - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

Schneider RM17TG00 Phase Sequence & Releu de monitorizare a pierderii de fază - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

PLC/

Schneider RM17TG00 Phase Sequence & Releu de monitorizare a pierderii de fază

RM17: Harmony RM17 series three-phase monitoring relay TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions) 00: 1 contact de schimbare (1C/O) versiune; RM17TG20 in the same series is the 2C/O dual-contact model ✅ Core Functions Monitors three phases L1/L2/L3: Eroare de secvență a fazelor (reverse phase, motor reverse rotation protection) Fază ...

  • Detalii despre produs

RM17: Harmony RM17 series three-phase monitoring relay

TG: Monitors phase sequence and phase loss only (no voltage unbalance, overvoltage or undervoltage functions)

00: 1 contact de schimbare (1C/O) versiune; RM17TG20 in the same series is the 2C/O dual-contact model

✅ Core Functions

Monitors three phases L1/L2/L3:

  1. Eroare de secvență a fazelor (reverse phase, motor reverse rotation protection)
  2. Defecțiune de pierdere de fază (loss of two or more phases; single-phase weak voltage drop will NOT trigger)

Autoalimentat, energized directly from L1/L2/L3, no additional auxiliary alimentare electrică necesar

📋 Key Technical Specifications

ArticolParametru
Monitoring Voltage Range208~480 VAC (operating limit 183~528VAC)
Frecvenţă50/60Hz ±10%
Contacte de ieșire1C/O (1 Deschis normal + 1 În mod normal închis)
Rated Contact Current5A @250VAC, max.1250VA
Power-up Start Delay≤650ms
Fault Response Time≤130ms
Consumul de energie≤22VA @400VAC 50Hz
Montare35mm șină DIN, width 17.5mm (1 modul)
IndicatorLED galben: ON under normal condition, OFF in fault state
CertificariCE, Supratensiune Categoria III, IEC60255

🔌 Terminal Wiring Definition

Terminale superioare: L1, L2, L3 → Connect to three-phase power supply

Lower contact terminals:

11: Comun

14: Deschis normal (NU) (closed in normal state, open under fault)

12: În mod normal închis (NC) (deschis in stare normala, closed under fault)

With correct three-phase supply and proper phase sequence: releul se activează, LED ON; Pierdere de fază / reversed phase → relay de-energizes, LED OFF

🛠️ Typical Application Scenarios

Hoisting equipment, lifturi, linii de transport, water pump sets, preventing motor reverse rotation

Compresoare de aer, chiller unit three-phase power protection

Portable equipment power access detection, emergency power switching judgment

⚠️ Troubleshooting Points

  1. LED stins: No power on three-phase incoming lines or loose wiring;
  2. LED fails to energize after power-up: Most likely reversed phase sequence, swap any two L phases;
  3. Single-phase voltage drop will not trigger RM17TG00. TG series only detects complete phase loss and does not monitor voltage unbalance. For unbalance/overvoltage & protectie la subtensiune, select RM17TE series.

🧩 Same-series Comparison & Referință de înlocuire

RM17TG00: 1C/O, secvența fazelor + pierdere de fază

RM17TG20: 2C/O dual changeover contacts, secvența fazelor + pierdere de fază

RM17TE00: With voltage unbalance, supratensiune, subtensiune, phase loss and phase sequence (full-featured model)

📌 Notes

No potentiometer for threshold adjustment, fixed logic without adjustment knobs;

For three-phase 3-wire system only;

Dry contact output for PLC DI or contactor coil interlock circuit.

Schneider RM17TG20 Troubleshooting Document

Aplicabil: RM17TG00 / RM17TG20 three-phase phase sequence & phase loss relay

Măsuri de siguranță: High-voltage work must follow power cut & voltage verification. Use qualified high-voltage multimeter and wear insulated protective gear for three-phase voltage measurement.

Product Principle Review: Only monitors phase sequence and complete loss of two or more phases; single-phase voltage drop and voltage unbalance will not trigger protection. Self-powered from L1/L2/L3. Stare normală: yellow LED ON, both contact sets energized; Fault state: yellow LED OFF, both contact sets de-energized

  1. Pre-check Preparation
  2. Instrumente: Multimetru digital, cross screwdriver, mănuși izolante
  3. Confirmarea modelului: RM17TG20, rated monitoring voltage 208~440VAC (limit 183~484VAC), long-term operation above 440VAC is not permitted
  4. System Confirmation: Three-phase 3-wire system, no neutral wire connected; this model cannot detect single-phase drop in 3P4W system
  5. Basic Status Description: ≤650ms initialization delay after power on; fault response ≤130ms; relay stays de-energized when fault exists, auto-recovers once fault cleared
  6. Troubleshooting by Fault Symptom

Simptom 1: Yellow LED completely off after power-up, relay contacts no action

Descriere: No indicator light after energizing, contacte 11/14 şi 21/24 fail to close

  1. Opriți, inspect L1/L2/L3 terminals: Check for looseness, oxidation or poor crimping; clean dust and copper oxide on terminals
  2. Porniți, measure line-to-line voltage L1-L2, L2-L3, L1-L3 at relay upper terminals with multimeter

Any line voltage <183V: Undervoltage on power supply, relay cannot operate; check upstream circuit breaker, fuse and cable breakage

No voltage on two or more phases: Upstream phase loss fault, repair power supply circuit

  1. LED still OFF with all three-phase voltages normal:

Check miswiring of L1/L2/L3; confirm power cables are not connected to contact terminals

Inspect module appearance: Cracked housing, burn marks or carbonized terminals → internal damage, replace relay directly

Cross test: Remove relay and connect to known good three-phase supply; if LED remains off, relay is defective

Simptom 2: Three-phase supply normal, LED stays off, relay continuously reports fault (contacts not energized)

Most frequent on-site fault: Secvență de fază inversată

  1. Measure three line voltages and confirm all values between 183~484VAC with balanced three-phase voltage
  2. Opriți, swap any two incoming L phases (de ex. L1 și L3)
  3. Re-energize and observe LED:

LED ON and contacts close: Fault resolved, root cause reversed phase sequence

LED still OFF after twice phase swap: proceed to next step

  1. Check for virtual connection with induced voltage: Multimeter shows normal voltage but voltage collapses under load. TG series cannot identify weak single-phase drop, but will trigger phase loss alarm if single-phase voltage falls below 100V
  2. Still invalid: Relay internal failure, replace for test

Simptom 3: LED is ON, but no signal on output contact circuit (no PLC feedback / contactor fails to act)

Power monitoring circuit healthy, fault lies in secondary dry contact circuit

RM17TG20 has two independent changeover contact sets: 11/12/14 şi 21/22/24, both act synchronously

  1. Power off and verify contact wiring:

11, 21: Common terminals

14, 24: Deschis normal (NU) (închis când este alimentat; open under fault)

12, 22: În mod normal închis (NC) (open when energized; closed under fault)

  1. Porniți (relay normal state, LED ON), measure continuity with multimeter:

11 & 14, 21 & 24: should conduct; 11 & 12, 21 & 22: should be open

  1. Manually create fault (reverse phase sequence), LED OFF:

11 & 14, 21 & 24: deschide; 11 & 12, 21 & 22: conduită

  1. Asynchronous action between two contact sets (one closed, one open): Internal contact damage, must replace relay
  2. Contact status correct but no signal on downstream circuit: Check PLC DI module, external interlock circuit, broken secondary wiring or blown fuse

Simptom 4: Random false tripping during motor operation (LED OFF, protection trip)

  1. Monitor three-phase voltage, focus on voltage dip during motor starting:

⚠️ Important Limitation: RM17TG only detects complete loss of two phases; single-phase voltage dip will not trigger protection. Random tripping is mostly caused by instantaneous two-phase power loss or poor connection

  1. Inspect main circuit contactor, thermal relay terminals and cable lugs for loose connections, overheating and poor contact under high current
  2. Check power cables: Deteriorarea cablului, earth fault or risk of phase-to-phase short circuit
  3. EMI Troubleshooting: Relay routed in parallel with power cables; relocate RM17TG away from VFDs and contactors, use separate cable trunking or shielding
  4. Confirm supply voltage does not exceed RM17TG20 upper limit 440VAC; use RM17TG00 for 480VAC application
  5. Cross replacement test: If fault disappears after installing new relay, original relay is aged and damaged

Simptom 5: Relay does not alarm with single-phase cut-off (protection no action)

This is NOT a fault, it is inherent design limitation!

RM17TG series only detects loss of ≥2 phases. Single-phase disconnection and single-phase voltage drop cannot trigger protection

If single-phase loss, voltage unbalance, supratensiune & undervoltage protection required: Replace with RM17TE00 multi-function monitoring relay

III. Quick Self-check Procedure (On-site Maintenance Checklist)

✅ Step1: Opriți, inspect appearance and wiring (terminale, burn marks, lejeritate)

✅ Step2: Power on and measure L1-L2 / L2-L3 / L1-L3 line-to-line voltages

✅ Step3: Observe LED status to locate fault domain (alimentare electrică / secvența fazelor / relay itself)

✅ Step4: Power off and swap two L phases to verify reversed phase sequence

✅ Step5: Power off and test continuity of two contact sets to confirm switching logic

✅ Step6: Cross replace relay to confirm whether fault comes from relay or external wiring

  1. Common Misconceptions
  2. ❌ Concepție greșită: Relay should protect on single-phase loss

✅ Note: TG series only detects loss of two or more phases; single-phase breakage is not detected.

  1. ❌ Concepție greșită: Front panel adjustment knobs are available for threshold setting

✅ Note: RM17TG has no potentiometer, threshold fixed.

  1. ❌ Concepție greșită: Two contact sets can act independently

✅ Note: Two contact sets operate synchronously; asynchronous action indicates relay damage.

  1. ❌ Concepție greșită: Can be used in 3P4W system (with neutral wire)

✅ Note: For three-phase 3-wire only, neutral wire must NOT be connected.

  1. Replacement Criteria (Replace relay if any condition met)
  2. L1/L2/L3 supply voltage normal, LED remains OFF after phase sequence swap
  3. Two contact sets act asynchronously, contacts burnt or fail to switch
  4. Housing or terminals show black burn marks, bulging or carbonization
  5. Fault eliminated after installing new relay under same power condition
  6. Recomandare de întreținere
  7. Periodic inspection: Tighten L1/L2/L3 input terminals and contact terminals quarterly to prevent vibration-induced looseness
  8. Ambient condition: Operating temperature -20~+60℃; avoid heavy dust, humid or corrosive gas environment
  9. Curatenie: Clean module surface dust with dry brush after power cut, liquid cleaner prohibited
  10. Durata de viață: Mechanical life of contacts >10 milioane de cicluri; electrical life approx.100,000 cycles at 5A@250VAC

Schneider RM17 Series Three-phase Monitoring Relay Full List (Harmony Zelio, 35mm șină DIN, 17.5mm 1-module width)

All models are self-powered from L1/L2/L3, no auxiliary supply required, 5A@250VAC dry contact output, for three-phase 3-wire system

  1. RM17TG (Model de bază: secvența fazelor + phase loss only, no adjustment knobs, fixed threshold)
ModelContacteGama de tensiuneFuncții de bazăAplicație tipică
RM17TG001C/O (1 schimbarea)208~480VACEroare de secvență a fazelor, ≥2 phases loss protection; No unbalance / peste&subtensiuneSingle interlock, water pump and general motor protection
RM17TG202C/O (2 independent changeover)208~440VACEroare de secvență a fazelor, ≥2 phases loss protection; No unbalance / peste&subtensiuneHardware interlock + PLC alarm, ridicarea, lift

TG Series Features: Fără potențiometru, no adjustment window on housing, only yellow status LED; Single-phase voltage drop will not trigger alarm

  1. RM17TT / FATA / TU / THE (Multi-function adjustable type, transparent cover with adjustment knobs)
ModelContacteGama de tensiuneFuncții de monitorizare
RM17TT001C/O208~480VACPierdere de fază + secvența fazelor; rated voltage selectable, delay adjustable; No voltage unbalance, supra/subtensiuneBasic adjustable phase sequence & pierdere de fază, suitable for multi-voltage site
RM17TA001C/O208~480VACPierdere de fază + secvența fazelor + three-phase voltage unbalance; unbalance threshold & delay adjustable; No over/undervoltageMotor winding protection, detect three-phase asymmetry
RM17TU001C/O208~480VACPierdere de fază + secvența fazelor + undervoltage monitoring; pragul de subtensiune & delay adjustable; No overvoltage, no unbalancePower supply drop monitoring, generator set, incoming power supervision
RM17TE001C/O208~480VACFuncții complete: phase loss+phase sequence+voltage unbalance+overvoltage+undervoltage, multiple potentiometers adjustable, true RMS measurementRăcitor, compresor de aer, UPS switching, full protection requirement

III. RM17 Series Single-phase / DC Voltage Monitoring (Aceeași serie, non three-phase)

ModelTipMonitoring RangeContacte
RM17UAS14Tensiune DC9~15VDC1C/O
RM17UAS16AC/DC universal20~80V AC/DC1C/O
RM17UAS15AC/DC universal65~260V AC/DC1C/O
RM17UBE SeriesSingle-phase AC Over & Subtensiune24~240VAC1C/O
RM17UB310Single-phase Voltage Monitoring200~240VAC1C/O
  1. Model Suffix Coding Definition (RM17Txx00)

TG: Tip de bază, fixed threshold, no adjustment knob, secvența fazelor + pierdere de fază

TT: Adjustable basic model, secvența fazelor + pierdere de fază, voltage range selectable

FATA: T + Asymmetry voltage unbalance detection

TU: T + Undervoltage monitoring

THE: Total full functions (secvența fazelor, pierdere de fază, dezechilibra, supratensiune, subtensiune)

00: 1C/O output

20: 2C/O dual independent changeover contacts (only available for TG series)

  1. Tabel de selecție rapidă (Three-phase models)
CerinţăModel recomandat
Only phase sequence+phase loss, single contact output, 480V applicationRM17TG00
Phase sequence+phase loss, dual independent dry contacts for interlock + alarmaRM17TG20
Phase loss+phase sequence, multi-voltage option, delay requiredRM17TT00
Phase loss+phase sequence+three-phase unbalance (motor asymmetry protection)RM17TA00
Phase loss+phase sequence+undervoltage monitoringRM17TU00
Protectie completa: phase loss+phase sequence+unbalance+overvoltage+undervoltageRM17TE00
  1. Common General Specifications
  2. Montare: 35mm șină DIN, 1 modul (17.5mm);
  3. Output Logic: Relay energized (power normal) → contacts closed; fault → contacts open (fail-safe type);
  4. Alimentare electrică: Self-powered directly from L1/L2/L3, fara fir neutru, three-phase 3-wire system only;
  5. Timp de răspuns: TG fixed ≤130ms; TT/TA/TU/TE fault delay manually adjustable;
  6. Evaluarea contactului: 5A 250VAC resistive load; for PLC DI and contactor interlock circuit, not for direct driving of high-power loads

VII. Înlocuire & Upgrade Reference

RM17TG00 ↔ RM17TG20: functie identica, only contact quantity differs

RM17TT00 → RM17TA00: add voltage unbalance detection

RM17TA00 → RM17TE00: add overvoltage and undervoltage window monitoring

Legacy RM22TG series is substitute series (same function, different form factor)