Samwha EOCR from Korea, integrated into the Schneider EOCR product line, made in Korea, exclusively for EOCR motor protection relays.
- Definiția modelului
3CT: Three-phase integrated transformator de curent with three through-hole cores
H2: Cod mărime, corresponding to the cable window for 200A model
200: Primary rated current: 200 O
C: Old version suffix; Z is the new replacement model (3CT-H2-200-Z). Electrical parameters are identical, only version revision, direct plug-and-play replacement.
- Specificații electrice de bază
Transformation ratio: 200/5 O
Clasa de precizie: Clasă 3.0
Rated burden: 1.25 VA (Version C) / 5 VA (New Version Z)
Frecvenţă: 50/60 Hz
Withstand voltage: 1150 V
Short-time thermal stability: 40Ith / 1 doilea
Rezistenta de izolare: ≥10 MΩ @ 500 În DC
Circuit aplicabil: AC 600 V motor circuit
Greutate: aproximativ. 580 g
- Dimensiuni generale
W150 mm × H55 mm × D71 mm
Integral epoxy encapsulation, three circular cable holes; DIN rail / montaj pe panou
Secondary terminals: K1, K2 (three independent windings for each phase); secondary wire: 1.5~4 mm² flexible cable
- Aplicație & Potrivire
✅ Designed exclusively for: EOCR-3DE, FDE, SSD, 3MZ and other digital motor protection relays. It samples three-phase current to implement overload, pierdere de fază, locked rotor and current unbalance protection.
✅ Application scenarios: Three-phase asynchronous motor control cabinets, fani, pompe de apa, compressors and conveyor power circuits.
❌ Not suitable for energy metering (Clasă 3 accuracy for protection only, not for measurement).
- Selectarea modelului & Înlocuire
New in-stock replacement: 3CT-H2-200-Z, direct replacement for 3CT-H2-200-C
Other models in the same series:
3CT-H1-100-Z: 100/5 O
3CT-HH-150-Z: 150/5 O
3CT-H3-300-Z: 300/5 O
3CT-H4-400-Z: 400/5 O
- Ghid de instalare
- Run the main power cable directly through the three holes; P1 = supply side, P2 = motor side. Polarity reversal will cause phase error and false phase-loss tripping. CT secondary circuit must never be open-circuited.
- Use only identical 3CT models with one relay; do not mix CTs with different transformation ratios.
- Temperatura mediului ambiant: -20 ~ +60 ℃; Max altitude: 2000 m.
- Wiring Instruction for 3CT-H2-200-C (Model nou: 3CT-H2-200-Z)
Three-phase integrated CT with independent secondary windings for R/S/T phases, secondary output 5 O. Only compatible with EOCR motor protectors; cannot be connected to ordinary ammeters or metering devices.
Definiția terminalului
Primary side: Three holes for L1(R), L2(S), L3(T) cabluri de alimentare
Polarity rule: P1 (alimentare electrică) → P2 (sarcina motorului); arrow points toward the load. Reversed polarity leads to phase fault and incorrect phase-loss alarm.
Secondary terminals (3 groups from top to bottom):
R phase: K1, K2
S phase: K1, K2
T phase: K1, K2
Secondary cable: 1.5~4 mm² flexible wire; shielded twisted pair is recommended; cable length ≤ 15 m.
Cablaj standard (EOCR-3DE / FDE / 3MZ / iFMZ / i3MZ)
- R-phase K1 → EOCR I1; R-phase K2 → common COM terminal
- S-phase K1 → EOCR I2; S-phase K2 → common COM terminal
- T-phase K1 → EOCR I3; T-phase K2 → common COM terminal
✅ All three K2 terminals are tied together to the protector’s current COM; single-point grounding at the COM terminal is recommended.
❌ Never allow secondary open circuit (will cause accuracy drift and insulation breakdown).
Note on mechanical life: Termenul “viata mecanica” only applies to devices with moving contacts and mechanical structures (contactoare, întreruptoare de circuit, relee). Current transformers (CT) and voltage transformers (PT) are static components without moving parts. Their service indicators are insulation life, thermal stability and environmental durability only.
Întreţinere & Ciclul de înlocuire (On-site O&M Reference)
Normal environment (ventilator & pompa, clean indoor cabinet): Evaluate replacement after 8~12 years
Mediu dur (temperatură ridicată, praf, VFD circuits, frequent direct-on-line motor starting): Check insulation and transformation ratio every 5~7 years
After short-circuit heavy current impact: Test or replace immediately. The iron core will suffer hidden performance degradation, resulting in current sampling deviation and false tripping of the protector.
Notă suplimentară
New model 3CT-H2-200-Z shares the same mechanical structure, iron core and encapsulation as version C, with identical durability. Only the rated burden is upgraded from 1.25 VA to 5 VA, making it more stable for long secondary cables and VFD applications. Mounting holes are fully interchangeable with no cabinet modification required.
- Naming Rule for 3CT-H Series Three-Phase Integrated CT
Format: 3CT-XX-XXX-Suffix
3CT: Three-phase combined current transformer (EOCR dedicated)
H1/HH/H2/H3/H4: Cod mărime (cable window dimension)
Numeral: Primary current (secondary output 5 O)
Sufix: C = Old version (întreruptă); Z = New version (active replacement)
Precizie: Clasă 3.0; Secondary output: 5 O; Compatible with all EOCR motor protectors.
- Lista completă a modelelor (Old C-version + New Z-version, one-to-one match)
Full Specifications (ascending current rating)
- 3CT-HS-75, Raport: 75/5 O
Vechi: 3CT-HS-75-C (întreruptă)
Nou: 3CT-HS-75-Z (in production)
- 3CT-H1-100, Raport: 100/5 O
Vechi: 3CT-H1-100-C (întreruptă)
Nou: 3CT-H1-100-Z (in production)
- 3CT-HH-150, Raport: 150/5 O
Vechi: 3CT-HH-150-C (întreruptă)
Nou: 3CT-HH-150-Z (in production)
- 3CT-H2-200 (Modelul tău), Raport: 200/5 O
Vechi: 3CT-H2-200-C (întreruptă)
Nou: 3CT-H2-200-Z (direct interchange)
- 3CT-H3-300, Raport: 300/5 O
Vechi: 3CT-H3-300-C (întreruptă)
Nou: 3CT-H3-300-Z (in production)
- 3CT-H4-400, Raport: 400/5 O
Vechi: 3CT-H4-400-C (întreruptă)
Nou: 3CT-H4-400-Z (in production)
- Key Differences between C-version & Z-version
Old suffix -C: Rated burden 1.25 VA, limited short secondary wiring length
New suffix -Z: Rated burden upgraded to 5 VA, better stability for long cables and VFD circuits; mounting footprint fully compatible for drop-in replacement without cabinet changes.
- EOCR Protector Matching Table (Interval de curent)
75 A → 3CT-HS-75
100 A → 3CT-H1-100
150 A → 3CT-HH-150
200 A → 3CT-H2-200 (acest model)
300 A → 3CT-H3-300
400 A → 3CT-H4-400
- Suplimentar: Zero-Sequence Split-Core CT in the Same Series
ZCT-035-Z, ZCT-050-Z, ZCT-080-Z, used for earth-fault protection and paired with 3CT series.
Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor



















NH42-63-318x560.png)



