Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

Wechat: +86-13184948252 Whatsapp: 0086-13811255435 E-mail: kent@bestcontactor.com

Despre Contact |

Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker - Contactor,întrerupător de circuit,senzor,Codificator,PLC,Convertor

întrerupător de circuit/

Siemens 3RV2031-4KA10 Motor Protection Circuit Breaker

Tip de produs: SIRIUS 3RV2 series frame S2 motor protection circuit breaker (motor protector), active production model, made in Germany Model Code Explanation 3RV 2 0 31 4 K A 10 3RV: SIRIUS motor protection circuit breaker 2: 2nd generation of 3RV2 series 0: Versiune standard, no pre-fitted auxiliary contacts 31: Frame size S2 4: excursie ...

  • Detalii despre produs

Tip de produs: SIRIUS 3RV2 series frame S2 întrerupător de protecţie a motorului (motor protector), active production model, made in Germany

  1. Codul modelului Explicația

3RV 2 0 31 4 K A 10

3RV: SIRIUS motor protection circuit breaker

2: 2nd generation of 3RV2 series

0: Versiune standard, no pre-fitted auxiliary contacts

31: Frame size S2

4: Trip current rating code

K: Thermal setting range 62~73A

O: Borne cu șuruburi

10: Capacitate de rupere standard (without additional contacts)

  1. Core Technical Data
ArticolSpecificații
Dimensiunea cadruluiS2, width 55mm, Montare pe șină DIN
Polonii3P
Thermal overload setting range62 ~ 73A (adjustable via front knob)
Instantaneous electromagnetic short-circuit trip949O (fix)
Clasa de excursieClasă 10 (for normal motor starting; trips within 10s at 7.2× rated current)
Tensiune nominală de funcționareAC 690V, DC250V
Rated ultimate short-circuit breaking capacity Icu@400V65cel
Tip conexiuneBorne cu șuruburi
Contacte auxiliare încorporateNici unul; auxiliary contact modules must be fitted separately
Puterea motorului aplicabilă (AC400V)Aproximativ. 37kW 3-phase motor
Greutate netă1.172kg
HS Customs Code85362090
  1. Funcții de protecție
  2. Protectie la suprasarcina: Inverse-time thermal trip via bimetallic strip, motor overload protection and phase loss protection
  3. Protecție la scurtcircuit: Instantaneous electromagnetic trip for rapid short-circuit disconnection
  4. Front-mounted TEST pushbutton for manual tripping test of the mechanism
  5. Handle position indication: PE / OFF / fault trip position; padlockable for lockout
  6. Cablaj & Specificații de instalare

Main circuit conductor: Max. 1×35mm² solid/stranded cable; max. 1×25mm² fine-stranded cable with ferrule

Tightening torque for main terminals: 3.0~4.5 N·m, M6 screws

Accepts top-in or bottom-in wiring; DIN35mm rail mounting

Can be assembled with SIRIUS 3RT contactor to form a direct-on-line starter, constituting a motor protection starter unit

  1. Selecţie & Informații de înlocuire

Same-series Replacement (Same Rating)

3RV2031-4KA15: Version with pre-fitted auxiliary contacts (1NU+1NC)

Nota: 3RV2031-4KA10 has no built-in auxiliary contacts. For feedback signals, 3RV2901 auxiliary contact accessory must be mounted externally.

Domestic Alternative Reference

Siemens local China 3RV5/3RV6 series equivalent: 3RV5031-4KA10 (domestic frame S2, 62~73A, terminale cu șuruburi, largely identical parameters)

  1. Aplicații tipice

3-motoare asincrone de fază, fani, pompe de apa, compresoare, conveyor motor circuit protection

Motor starter circuits inside control cabinets, combined with contactors as starter assemblies

Motor protection for machine tools, HVAC, ambalaj, chemical automation equipment

  1. Ghid de depanare
  2. Trips immediately upon motor start: Usually short-circuit trip. Check motor windings and cables for phase-to-phase or earth short circuit.
  3. Trips after running for some time: Supraîncărcare. Recheck motor rated current and reset the adjustment knob; inspect for mechanical jamming.
  4. Nu se poate închide: Defecțiune de mecanism, or previous short-circuit trip not fully reset. Press TEST button to reset before closing.
  5. Second-hand Inspection Checklist
  6. Aspect: No cracked housing, burn marks, or overheating discoloration on terminals
  7. Funcționare mecanică: Smooth handle operation; TEST button triggers trip correctly and resets properly
  8. Continuitate: Main contacts conduct when closed and isolate when open; no internal short circuit
  9. Izolare: Measure insulation resistance between phases and to earth using a megger

Siemens 3RV2031-4KA10 (Frame S2) Dimensiuni de instalare

All 3RV2031 models of frame S2 share identical outer dimensions

Unit Overall Dimensions (L × H × D)

Latime W: 55 mm (55mm cabinet space per unit)

Height H: 140 mm

Depth D: 149 mm (from rail mounting surface to front of operating handle)

Metoda de montare

șină: DIN 35mm standard rail (UNUL TĂU 60715), montaj cu clips; optional screw locking

Orientarea montajului: any orientation (vertical, horizontal installation allowed)

Cabinet Clearances (Disiparea căldurii / Electrical clearance)

Side-by-side mounting: 0mm gap allowed for adjacent units

Vertical clearance top & fund: ≥50mm at upper/lower terminal zones

Clearance to earthed cabinet metalwork: ≥10mm lateral clearance

Cabinet cutout (if door extension handle is used)

The 3RV2 unit is DIN-rail mounted inside the cabinet. If an extended door operating handle (se vinde separat) este necesară:

Cutout width: aproximativ. 48mm, cutout height: aproximativ. 130mm

Nota: No cabinet cutout required without extension handle; unit is fully installed inside enclosure on DIN rail.

Note suplimentare

With 3RV2901 side-mounted auxiliary contact: overall width unchanged, slight increase in depth

When back-to-back assembled with 3RT contactor as starter: total depth equals sum of both components

Siemens 3RV2031-4KA10 Weight

✅ Net weight (unit only, no packaging): 1.17 kg (manufacturer nominal 1.172 kg; use 1.17kg on engineering drawings)

All S2 frame 3RV2031 models have similar weight, range 1.07~1.18 kg. Variations come from internal trip components; standard value for 3RV2031-4KA10 is 1.17 kg.

Note suplimentare

  1. Cu excepția accesoriilor: No 3RV2901 auxiliary contacts, door extension handles or other attachments. Weight increases slightly when accessories are fitted.
  2. Gross weight with factory carton: aproximativ. 1.30 kg (for logistics estimation)
  3. Unit conversion: 1.17 kg ≈ 2.58 lbs

Siemens 3RV2031-4KA10|Cross-brand Comparison + MPCB Product Series List

Reference device: 3RV2031-4KA10, frame S2, 55mm latime, 3P, 62~73A, terminale cu șuruburi, Class10, Icu@400V=65kA, no built-in auxiliary contacts, for 37kW@400V motor

⚠️ Important notice: No fully pin-to-pin drop-in replacement available. The below are function/rating/frame equivalent selections. Cabinet mounting, accesorii, breaking capacity and instantaneous trip values must be verified. Protection coordination validation is mandatory before formal project replacement.

  1. Siemens Internal Cross-reference (Preferred Replacement)
ModelDescriereDifference vs 3RV2031-4KA10
3RV2031-4KA10Reference unit, imported Germany frame S2, 62~73A, terminale cu șuruburi, no built-in auxiliary contactsUnitate de bază
3RV2031-4KA15Același rating actual, fitted with 1NO+1NC auxiliary contactsComes with built-in aux contacts; rest parameters identical
3RV5031-4KA10Siemens China local frame S2, 62~73A screw terminalsParameters largely identical, slightly lower Icu, economical domestic version
3RV1031-4KA10Legacy 3RV1 frame S2, same current ratingOlder generation, eliminat treptat; similar outline but accessories not fully compatible

3RV2 frame size overview

S00: 45mm, max 16A, motor ≤7.5kW

S0: 45mm, max 40A, motor ≤18.5kW

S2: 55mm, max 80A, motor ≤37kW (frame of this model)

S3: 70mm, max 100A, motor ≤45~55kW

  1. Imported Brand Equivalent Cross-reference (62~73A, S2 frame class MPCB)
MarcaSeria de produseModel echivalentKey Parameter Notes & Diferențele
SchneiderTeSys GV3 (GV3ME)GV3ME8056~80A adjustable, butonul rotativ, 3P, terminale cu șuruburi; 55mm frame, Class10. GV2 max 40A, GV2 cannot replace this model. Icu to be checked; instantaneous trip differs from Siemens
ABBMS series motor protection circuit breakerMS165-7360~73A adjustable, 3P, DIN rail, 55mm frame; MS165 is ABB equivalent to S2 frame. MS132 max 32A, insufficient rating, not suitable
Eaton (Moeller)PKZ2 motor protectorPKZ2-7362~73A, 3P, rotary operation, S2 frame, Class10. PKZ1 small frame; PKZ2 corresponds to 3RV2 S2
OmronBM series motor protection breakerBM6R-63Adjustment range near 62~73A, 3P; limited domestic adoption, verify breaking capacity during selection
  1. Alternative de marcă autohtonă (Cost Reduction for Projects)
MarcaSerieModel echivalentObservații
ChintNS2 seriesNS2-80 62~73ANS2 motor protection breaker, 55mm, Class10, terminale cu șuruburi
DeliciosCDV6 seriesCDV6-80 62~73ASame function MPCB, economical domestic type, lower Icu vs imported brands
NaderNDM2-MNDM2-M80 62~73AHigh-end industrial domestic, capacitate de rupere mai mare, suitable for critical circuits
  1. MPCB Product Portfolio Overview by Brand (Thermal-Magnetic DIN Rail Motor Protection Circuit Breaker)

Siemens

3RV2 (SIRIUS main import range: S00/S0/S2/S3, 0.1~100A)

3RV5 / 3RV6 (domestic economical range, S00/S0/S2)

3RV1 (legacy model, eliminarea treptată)

3VU (old compact type, max 63A)

Schneider

GV2: Small frame 45mm, 0.1~40A

gv3: Medium frame 55mm, 40~80A (counterpart to 3RV2 S2)

GV7: Large frame, 80~150A

ABB

MS116: Small frame

MS132: Cadru mediu, max 32A

MS165: 55mm frame up to 80A (counterpart to 3RV2 S2)

MO series (high breaking capacity version)

Eaton (Moeller)

PKZ0 / PKZ1: Low current

PKZ2: S2 frame up to 80A

PKZ3: Large frame

Main Domestic Brands

Chint NS2

Delixi CDV6

Nader NDM2-M

Changshu CM1-M (motor protection variant)

  1. Risks for Replacement Selection (Critical for Engineering)
  2. Different instantaneous short-circuit trip (N factor): 3RV2031-4KA10 fixed at 949A. Schneider GV3 and ABB MS165 have different electromagnetic trip thresholds. Short-circuit protection coordination changes. Direct replacement may cause loss of selectivity.
  3. Capacitate maximă de rupere Icu: 3RV2 is 65kA@400V. Domestic models generally have lower Icu and shall NOT be used for circuits with high prospective short-circuit current.
  4. Interblocare mecanică & contactor assembly: 3RV2 can directly snap onto 3RT contactor to form starter. Cross-brand devices cannot mechanically clip together, separate mounting brackets required.
  5. Auxiliary contact accessory systems are incompatible; mounting depth, terminal torque and maximum cable cross-section differ.
  6. UL/CE certification: No arbitrary brand replacement for export machines.
  7. Recommended Selection Rules

Cabinet retrofit, minimal modification: Siemens 3RV5031-4KA10 (domestic same-brand replacement)

Import brand substitution: Schneider GV3ME80 / ABB MS165-73, short-circuit protection coordination recheck required

Non-critical domestic circuit cost saving: Chint NS2-80 / Delixi CDV6-80

Prev:

Lasă un răspuns

Lăsaţi un mesaj