Siemens 3RW4443-6BC44 Soft Starter

MLFB Order Code Breakdown 3RW 44 43 6 B C 4 4 3RW: SIRIUS soft starter product series 44: High-performance built-in bypass 3-phase fully controlled soft starter (independent thyristor regulation per phase, integrated bypass contactor as standard) 43: Cod mărime, curent nominal 203 A la 40 °C for standard loads 6: Control circuit terminal type ...

  • Detalii despre produs

MLFB Order Code Breakdown

3RW 44 43 6 B C 4 4

  1. 3RW: SIRIUS soft starter product series
  2. 44: High-performance built-in bypass 3-phase fully controlled soft starter (independent thyristor regulation per phase, integrated bypass contactor as standard)
  3. 43: Cod mărime, curent nominal 203 A la 40 °C for standard loads
  4. 6: Control circuit terminal type = screw terminals; main circuit connected via copper busbars
  5. B: Integrated bypass contactor (2/3-phase bypass for zero loss during steady-state operation)
  6. C: Independent 3-phase thyristor control (full 3-phase control to balance 3-phase currents)
  7. 4: Control supply voltage Us = AC 230 V
  8. 4: Main circuit operating voltage Ue = AC 200~460 V
  9. Parametrii electrici de bază (40 °C, Clasă 10 Standard Load)
ArticolValoarea parametrului
Rated current for standard wiring (motor directly connected to soft starter)203 O
Matched motor power at 400 V110 kW
Rated current for inside-delta connection (motor windings split into two branches)352 O
Matched motor power at 400 V for inside-delta wiring200 kW
Gama de tensiune a circuitului principalAC 200~460 V (50/60 Hz)
Control supplyAC 230 V ±10%
Phase control modeAnti-parallel thyristors per phase with independent regulation
Funcții standardIntegrated bypass contactor to bypass thyristors during running
Standard overload trip classClasă 10; Clasă 10/20/30 configurable manually
Funcții de protecțiePhase loss, phase unbalance, suprasarcina motorului, supraîncălzire, thyristor short-circuit, start timeout, earth fault detection
Communication expansionProfibus DP compatible (requires 3RW4900-0KC00 communication module)
GreutateAproximativ. 11.2 kg
Țara de origineGermania

III. Potrivirea încărcării & Selection Limits

  1. Applicable Loads

Pompe de apă, fani, transportoare cu bandă, compresoare de aer, răcitoare, centrifugal equipment (viteză fixă, only smooth start/stop required)

  1. Derating Reference for Heavy-Duty Operation (40 °C)

Clasă 20 sarcina grea (porniri frecvente, high starting torque): permissible current 170 O, matched motor 90 kW

Clasă 30 extra heavy duty (mori cu bile, concasoare): permissible current 145 O, matched motor 75 kW

  1. Prohibited Operating Conditions

Continuous speed regulation, frequent forward/reverse switching, high-frequency jogging (≥30 times per hour)

  1. Hardware Structure & Descrierea cablajului
  2. Circuitul principal: Copper busbar terminals; L1/L2/L3 line side input, T1/T2/T3 motor side output; supports standard wiring and inside-delta wiring
  3. Circuit de control: Screw terminals for start/stop signals, fault outputs, reset, external thermistor input
  4. Panoul operator: Built-in LCD display for setting start ramp, initial voltage, soft stop, current limit and protection thresholds
  5. Instalare: Montare pe perete vertical; minimum 150 mm top/bottom clearance for heat dissipation; ambient temperature 0~40 °C (derate for temperatures above 40 °C)
  6. Ciclul de viață al produsului & Modele de înlocuire
  7. Stare: 3RW44 series discontinued (PLM: PM490 end-of-support phase); original manufacturer stops mass production, only stock spare parts available
  8. Direct OEM Replacement Model (Recommended for New Projects)

3RW5543-6HA14 (new-generation 3RW55 series, same 203 Un curent nominal, 230 V control supply, 200-460 V main voltage, terminale cu șuruburi, integrated bypass)

  1. Differences Between Old & New Models

Smaller footprint, consum redus de energie, native Modbus RTU and optimized protection logic for 3RW55

Different mounting cutout dimensions; copper busbars and mounting brackets need modification during cabinet retrofit

  1. Recommended Matching Protection Devices
  2. Main Circuit Short-Circuit Protection: Moulded case circuit breaker matched to 110 kW motor circuit
  3. Specialized Thyristor Protection: aM/gR ultra-fast fuse 500 V 315 O (mandatory upstream of soft starter, no thyristor short-circuit protection without it)
  4. Additional Motor Protection: External PTC thermistor connectable to control terminals for winding overtrip protection

VII. Typical Troubleshooting Matrix

Simptom de eroareCauza de bazăSoluţie
Overheating alarm during startupBlocked cooling air duct / ambient temp above 40 °C / long-duration heavy-load startupClean dust, improve cabinet ventilation, upgrade to higher-rated soft starter
Phase loss alarmPierdere de putere monofazată, loose busbar connection, broken motor windingStrângeți cablajul, measure 3-phase input voltage and motor winding resistance
Unrestricted starting current, direct full voltage outputBroken-down thyristors, welded bypass contactor contactsDisconnect power supply to test thyristors; replace bypass contact module
Startup timeout tripToo low initial voltage, seized mechanical load, insufficient ramp timeIncrease initial voltage, inspect mechanical load, extend start ramp time

VIII. Avantaje cheie

  1. Independent 3-phase voltage regulation; eliminates 3-phase current unbalance common in 2-phase soft starters, extending motor bearing service life
  2. Integrated bypass eliminates thyristor power loss during steady operation, delivering over 98% energy saving vs non-bypass models
  3. Supports soft stop and pump stop water hammer suppression, ideal for water supply, drainage and HVAC systems
  4. Comprehensive integrated motor protection, eliminating the need for separate thermal overload relays

Full Dimension Specifications of Siemens 3RW4443-6BC44

  1. Overall Equipment Dimensions (L × H × D, Unitate: mm)

210 (Lăţime) × 230 (Înălţime) × 298 (Adâncime)

  1. Decupaj de montare & Fixing Dimensions
  2. Horizontal center distance between mounting holes: 167 mm
  3. Vertical center distance between mounting holes: 190 mm
  4. Fastener specification: M8 bolt, cuplul de strângere 15 N·m
  5. Cabinet panel cutout minimum reserved width ≥210 mm, height ≥230 mm

III. Mandatory Minimum Cabinet Clearance for Heat Dissipation (Vertical Wall Mount)

Top clearance: ≥100 mm

Bottom clearance: ≥75 mm

Side clearance (multiple units side-by-side): ≥5 mm

Equipment rear surface to cabinet backplate: direct contact permitted

  1. Outer Carton Dimensions (Depozitare & Logistics Reference)

348 × 433 × 394 mm, Greutate netă 11.22 kg

  1. Note suplimentare
  2. Clasa de protectie: IP00; for cabinet installation only
  3. All 3RW4443 variants (-6BC34/-6BC44/-2BC45) share identical overall dimensions; differences only in control terminals and supply voltage
  4. Replacement model 3RW5543-6HA14 has a smaller footprint; recalculate cabinet cutout size for retrofits

Lista completă & Function Definition of Control Terminals – Siemens 3RW4443-6BC44

This model is equipped with screw-type control terminals, categorized into five groups: controlul sursei de alimentare, intrări digitale, motor PTC temperature sensing, ieșiri de releu programabile, general fault relay.

  1. Control Power Supply Terminals (Unit Main Supply)
  2. A1, A2

Funcţie: Main control power supply for soft starter

Model rating: AC 230 V ±10%, 50/60 Hz

Wiring rule: A1 live line L, A2 neutral line N

  1. PE

Control circuit protective earth terminal; connect to cabinet earth busbar

  1. L+, L-

Built-in internal DC24 V auxiliary supply for passive digital input switches; external 24 V power supply not required

L+ = DC24 V positive pole; L= DC24 V negative pole (common ground)

  1. 4 Programmable Digital Input Terminals IN1 / IN2 / IN3 / IN4

Logică: Connect one end of switch to L+, the other end to corresponding INx to trigger assigned function; all functions configurable via panel parameters

Factory Default Allocation

IN1: Motor start (Parameter Group 1 rotație înainte)

IN2: Unassigned

IN3: Unassigned

IN4: Fault trip reset

All Customizable Functions

Local manual mode, emergency start, low-speed creep, fast emergency stop, fault reset, 3 groups of forward/reverse motor parameter switching

III. Motor Winding Temperature Sensing Terminals T1, T2

For external motor PTC thermistor connection (motor overheat protection)

Soft starter trips automatically when winding temperature exceeds threshold

Short-circuit T1 and T2 if no PTC fitted to disable thermal protection

  1. 3 Independent Programmable Relay Outputs (Passive dry contacts, AC250 V / 5 O)

Each pair consists of normally-open contacts with fully assignable functions via parameter menu

  1. 13, 14 Ieșire 1

Implicit: Motor running signal (closes after startup completion and bypass contactor pull-in)

  1. 23, 24 Ieșire 2

Implicit: Unassigned; configurable for bypass status, startup-in-progress, pre-alarm, DC braking, etc.

  1. 33, 34 Ieșire 3

Implicit: Unassigned; customizable for all types of equipment status signals

  1. General Fault Relay Terminals 95, 96, 98 (Global Fault Alarm)

3-pole changeover contact for unified fault signaling, widely used in safety circuits

95: Common terminal COM

95-96: În mod normal închis (NC): conductive when unit healthy; opens upon fault trip

95-98: Deschis normal (NU): closes when fault occurs, for fault indicator light / alarm horn wiring

Terminal Summary Table

Terminal GroupNumărul terminaluluiCore Purpose
Alimentare de controlA1, A2AC230 V control voltage input
Pământ protectorPEControl circuit grounding
Încorporat 24 V SupplyL+, L-DC24 V power for digital inputs (positive / sol)
Intrări digitaleIN1, IN2, IN3, IN4Start/stop, reset, parameter switchover, manual mode etc.
PTC Temperature SensingT1, T2Motor winding overheat thermistor interface
Ieșire releu 113, 14Motor running status (deschis în mod normal)
Ieșire releu 223, 24Customizable equipment status (deschis în mod normal)
Ieșire releu 333, 34Customizable equipment status (deschis în mod normal)
Fault Changeover Contact95, 96, 98Global fault alarm (COM + NC + NU)

Supplementary Wiring Guidelines

  1. Tightening torque for control wires: 1.2~1.5 N·m; wire cross-section 0.75~1.5 mm² copper conductors
  2. Digital inputs are passive contact type; power solely from internal L+/Lwithout external PLC 24 V alimentare
  3. Series the normally closed 95/96 contacts in safety circuit to cut upstream contactor power on fault
  4. Profibus communication requires separate 3RW4900-0KC00 module with dedicated port (not part of front control terminals)