Siemens 6ES7132-6HD01-0BB1 Relay Output Module

SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay Output Module Distributed IO ET200SP, 4-channel normally-open digital relay output module, contact isolated type ✅ Model Code Interpretation 6ES7: SIMATIC S7 Automation System 132: ET200SP Digital Output Module 6HD01: 4-channel relay output, 120VDC~230VAC, 5A normally open 0BB1: Single pack (1 unitate pe cutie); `2BB1` = 10-piece bulk pack ...

  • Detalii despre produs

SIMATIC ET200SP RQ 4×120VDC…230VAC/5A NO ST Relay Output Module

Distributed IO ET200SP, 4-channel normally-open digital releu output module, contact isolated type

✅ Model Code Interpretation

6ES7: SIMATIC S7 Automatizare Sistem

132: ET200SP Digital Output Module

6HD01: 4-channel relay output, 120VDC~230VAC, 5A normally open

0BB1: Single pack (1 unitate pe cutie); `2BB1` = 10-piece bulk pack

📋 Key Technical Specifications

ArticolParametru
Număr de canale4 normally-open relay outputs (NU), channel-to-channel isolation
Evaluarea contactului120V DC ~ 230V AC, max. 5A pe canal
Base Unit TypeCompatible with BU B0 / BU B1 base units; color code CC40
Backplane Bus Supply55mA, typical power consumption 1.5W
Funcții de diagnosticareModule supply diagnostics, substitute value output
Temperatura de operare0 ~ +60 ℃ (standard module)
ComunicarePROFINET / PROFIBUS DP (with ET200SP interface module)
Cod HS85389091

🧩 Features

  1. Relay dry contact isolation: Galvanic isolation between PLC low-voltage side and load high-voltage side. Suitable for solenoid valves, contactoare, indicator lamps and other AC loads.
  2. Substitute value: When communication fails or CPU stops, output state can be preset in TIA Portal: hold / reset to 0 / setat la 1.
  3. Channel status LEDs + module diagnostic LED for fault alarm.
  4. Separate base & electronic module design: Hot-swappable electronics while wiring remains on base for easy maintenance.

⚙️ Typical Application Scenarios

Control of 220VAC solenoid valves, small contactors, alarm lamps, fan start/stop in control cabinets

Not suitable for high-frequency switching applications (limited relay mechanical service life; cannot handle high-speed pulses)

Distributed remote IO station deployed with IM155-6 interface module

⚠️ Selection & Note de cablare

  1. Base unit must be BU B0 / BU B1 type, A-type bases are incompatible; recommended BU20-P16+A0+2B.
  2. Relay contacts are passive dry contacts. Load power is not supplied by module backplane, external power supply required.
  3. Sarcini inductive (bobine de contactor) are recommended to connect varistor / freewheeling diode in parallel to extend relay service life.
  4. 5A per channel is rated current; pay attention to heat dissipation when all 4 channels run at full load simultaneously.

📌 Alternative & Modele derivate

6AG1132-6HD01-7BB1: SIPLUS wide-temperature conformal coated version, -40~+70℃, for harsh environments (industria chimică, în aer liber)

Alternative interne: ET200SP compatible 4-channel normally-open 5A relay modules. Verify base compatibility and diagnostic telegram.

Application Scenarios for 6ES7132-6HD01-0BB1 (ET200SP 4-Channel Relay Output Module)

Core features: Passive dry contacts, channel isolation; max. 5A for resistive loads, max. 2A for inductive loads; supports 24V~230V AC/DC loads; PROFINET distributed remote IO. Ideal for low-frequency switching control requiring galvanic isolation between strong and weak circuits.

  1. Industry-specific Applications
  2. Machinery Manufacturing (Cele mai comune)

220VAC pneumatic & hydraulic solenoid valve control (cylinder, hydraulic valve on/off)

Drive coils of small AC contactors to indirectly control fans, pompe, transportoare

Equipment alarm lights, audible & alarme vizuale, panel indicator lamps

Door interlock, guard door signal output, equipment enable signal

Aplicabil: Mașini de ambalat, masini-unelte, linii de producție, mașini de turnat prin injecție, textile machinery remote IO stations

  1. Automatizarea proceselor / Tratarea apei

Remote field cabinet: 220V solenoid valves, dosing pumps, drain valves, agitator start/stop control

Field instrument power switching, lumini de avertizare, on-site audible & alarme vizuale

Water tank level interlock output; remote stations deployed at different plant locations

Avantaj: Relay isolation prevents field high-voltage interference from coupling into PROFINET bus

  1. HVAC & Automatizarea clădirilor

AC220V air damper actuators, electric butterfly valve on/off control

Contactor coil control for fans, ventilatoare de evacuare, pompe de apa

Fire linkage signal output, on-site alarm indication

  1. Energie, PV & Power Auxiliary Control

Switchgear auxiliary circuit, relay loop switching, alarm contact output

Small heater, dehumidifier on/off control

Signal isolation transfer: Convert PLC low-voltage signals to dry contacts for 3rd-party systems (DCS, relay protection)

  1. Supported Load Types
  2. AC220V solenoid valves, lămpi indicatoare, sunete
  3. AC220V contactor / intermediate relay coils
  4. Sarcini rezistive: heating tapes, incandescent lamps (≤5A)
  5. DC24V~DC120V DC loads (dry contacts work for both AC and DC)
  6. Passive contact output for hard-wired interlock with other control systems

III. Aplicații nepotrivite

  1. ❌ High-frequency switching: Mechanical relay has limited service life, not for multiple operations per second. Use transistor DQ modules for high frequency.
  2. ❌ Direct drive of high-power motors (only drives contactor coils, not main motor circuit)
  3. ❌ Inductive load current exceeding 2A (solenoid & contactor are inductive loads; varistor / freewheeling diode required to absorb back EMF)
  4. ❌ Safety circuits (this module is non-failsafe. F-RQ failsafe modules are required for emergency stop and safety gate circuits)
  5. ❌ High inrush current loads (contact erosion risk; each channel needs external 6A max. fast fuse protection)
  6. Architecture Characteristics

ET200SP distributed IO: This module is mounted in remote field enclosures away from the main PLC and connected via IM155-6 PROFINET interface module.

Load wiring for 220VAC is routed locally, reducing long-distance high-voltage cables

Relay isolation protects PLC low-voltage system and improves EMC immunity

Substitute value configurable in TIA Portal: Output state can be defined for bus interruption or CPU stop to ensure safe equipment status

ET200SP Digital Output Module Selection Comparison Sheet

Compare 6ES7132-6HD01-0BB1 (RQ 4-channel relay output) vs common transistor DQ modules

  1. Tabel de comparație a parametrilor de bază
Articol6ES7132-6HD01-0BB16ES7132-6BH01-0BA06ES7132-6BD20-0BA0
Relay Output RQTransistor DQ 16×24VDCTransistor DQ 4×24VDC/2A
Tip ieșirePassive dry contact, normally-open relay NOPNP transistor, active 24VDCPNP transistor, active 24VDC
Număr de canale4 canale16 canale4 canale
Load Voltage Range120VDC ~ 230VAC, AC & Compatibil DCDC24V onlyDC24V only
Rated Current per Channel5A resistive; 2A inductive0.5A pe canal2A pe canal
Galvanic Isolation✅ Channel isolation, strong/weak voltage isolation❌ No channel isolation, common 24V ground❌ No channel isolation
Viteza de răspunsSlow: millisecond level (mechanical contact)Rapid: microsecond levelRapid: microsecond level
Durata de viațăMechanical life ~10⁷ operations (low frequency)Nearly unlimited electronic life, high frequency capableNearly unlimited electronic life
Sarcina tipicăAC220V solenoid valves, bobine de contactor, audible/visual alarms, dry-contact interlockDC24V solenoid valves, lămpi indicatoare, sensor power supplyHigh-current DC24V loads, DC solenoid valves
Base Color CodeCC40CC01CC01
  1. When to select 【6ES7132-6HD01-0BB1 Relay Module】

✅ Recomandat

  1. Load voltage is AC220V, no extra intermediate relay required on site
  2. Galvanic isolation required, heavy field interference, prevent high voltage from damaging PLC IO bus
  3. Need passive dry contact output for hard-wired interlock to 3rd-party DCS / relee de protectie
  4. Low switching frequency (triggered every few minutes/hours, not frequent on/off)
  5. Mixed loads: both AC220V and DC loads up to 120V

❌ Nerecomandat

  1. Frequent switching: multiple start-stop per second (rapid contact wear and shortened lifetime)
  2. Pure DC24V loads with large point count requirement (transistor modules cheaper, higher channel density)
  3. High-speed pulse & motion control output (relay cannot generate pulses)
  4. SIL safety circuits (Failsafe F-series modules required)

III. When to select 【Transistor DQ Module】

✅ Recomandat

  1. All loads are DC24V, frequent switching (continuous actuation of cylinder solenoids)
  2. Requirement for high-speed switching signals or pulse outputs
  3. Large I/O point count, high channel density to save cabinet space
  4. Field loads are low-current DC components without isolation requirement

❌ Nerecomandat

  1. AC220V loads: must add external intermediate relays
  2. Severe field high-voltage interference without isolation; risk of IO module burnout
  3. Quick Selection Rule

Încărca: AC220V, low frequency, isolation required → 6ES7132-6HD01-0BB1

Încărca: DC24V, frequent operation → Transistor DQ (6BH01 for many points / 6BD20 for high per-channel current)

  1. Additional Selection Notes
  2. Sarcini inductive (electrovalve, contactoare) need absorption components: varistor in parallel for AC loads, freewheeling diode for DC loads to suppress back EMF and extend contact life.
  3. Relay module base color code CC40, not interchangeable with transistor DQ base CC01.
  4. Cost reference: Relay modules usually cost more for same channel quantity. Cu toate acestea, overall system cost may be lower when eliminating external intermediate relays.
  5. Failure characteristics: Relay contacts risk sticking; transistor modules mostly fail by breakdown with no mechanical sticking risk.
  6. Special Alternatives

Failsafe output: 6ES7136-6DB00-0CA0 (F-DQ for safety circuits)

Solid-state relay output (no moving contacts, suitable for high-frequency AC switching): ET200SP RQ solid-state relay models