A spus SOCOMEC 48250201 Contor de putere multifuncțional

Marca: SOCOMEC Model Code: DIRIS 48250201 Seria de produse: DIRIS A40 Multi-function Power Meter Complete Order Code: 48250201 Core Information Full Product Name DIRIS A40 Multi-function Energy / Power Monitoring Meter Order Code: 48250201 Configurație standard (Model 48250201) Măsurare: Tensiune trifazată, actual, putere, factor de putere, harmonic, energy metering Communication: Modbus RS485 Dimension: 96×96mm panel mounting Power ...

  • Detalii despre produs

Marca: SOCOMEC

Cod model: DIRIS 48250201

Seria de produse: DIRIS A40 Contor de putere multifuncțional

Complete Order Code: 48250201

Core Information

  1. Numele complet al produsului

DIRIS A40 Multi-function Energy / Power Monitoring Meter

Cod de comandă: 48250201

  1. Configurație standard (Model 48250201)

Măsurare: Tensiune trifazată, actual, putere, factor de putere, harmonic, contorizarea energiei

Comunicare: Modbus RS485

Dimensiune: 96×96mm panel mounting

Alimentare electrică: AC/DC 80–270V

Intrare: Direct voltage input up to 480V; current input requires external CT

Funcții: Cerere, THD harmonic, înregistrarea evenimentelor, time-of-use energy

Ieșire: Basic version without built-in I/O (Select other variants for relay/pulse output)

  1. Reference for Distinguishing Similar Models

48250201: DIRIS A40, Modbus, No I/O

48250202: Version with pulse output

48250203: Version with digital input / ieșire releu

Aplicații tipice

Aparatură de joasă tensiune, busbar cabinets, UPS incoming feeders, data center power distribution, factory energy consumption monitoring; interfacing with SCADA, PLC and energy management systems.

Opțiuni alternative

Original direct replacement: DIRIS A40 series;

Alternative interne: Nayu, Yada, Acrel multi-function network power meters (Modbus register compatibility verification required).

Modbus RTU Register Summary for SOCOMEC DIRIS A40 (Comanda nr. 48250201)

Important Prerequisites

  1. Protocol: Modbus RTU, Codul funcției 03 (Read Holding Registers). All measurement data are stored in holding registers;
  2. Data format: 32-bit signed/unsigned integer (occupies two consecutive 16-bit registers, Big-Endian, high word first);
  3. Address in manual = decimal offset address (PDU address, starts at 0)

For configuration software using 4xxxx format: Offset address + 40001

Exemplu: Offset 786 → Register 40787

  1. Raw values need scaling division to obtain actual engineering values;
  2. Two sets of register maps exist: Old map (Firmware ≤2008) / New map (Firmware ≥2009). The table below is the new standard register map used for most field devices.
  3. Default Communication Parameters

Slave address: 1

Rata baud: 9600

Data bits: 8, Stop bits: 1, Paritate: Nici unul

Parameters can be modified via front panel menu

  1. Common Real-Time Measurement Registers (PDU Offset, FC03)
PDU OffsetReg CountNume parametruScaling FactorUnitateData Type
7862L1-N Voltage U1/100VS32
7882L2-N Voltage U2/100VS32
7902L3-N Voltage U3/100VS32
7922L1-L2 Line Voltage U12/100VS32
7942L2-L3 Line Voltage U23/100VS32
7962L3-L1 Line Voltage U31/100VS32
7982Phase A Current I1/100OS32
8002Phase B Current I2/100OS32
8022Phase C Current I3/100OS32
8042Frecvenţă/100HzS32
8062Total Active Power ΣP/100kWS32
8082Total Reactive Power ΣQ/100stângaS32
8102Total Apparent Power ΣS/100kVAS32
8122Total Power Factor PF/1000S32
8142L1 Active Power P1/100kWS32
8162L2 Active Power P2/100kWS32
8182L3 Active Power P3/100kWS32
  1. Energy Metering Registers (Energy Counter, 32-bit Unsigned)
PDU OffsetReg CountNume parametruUnitateScaling
8602Import Active Energy kWh+kWhRaw value direct use
8622Export Active Energy kWh-kWhRaw value direct use
8642Inductive Reactive Energy kvarh+kvarhRaw value direct use
8662Capacitive Reactive Energy kvarh-kvarhRaw value direct use
8562Operating Hour Counterh/100

⚠️ Model 48250201 basic version has no pulse output or DI/DO; I/O status registers are not required.

  1. Reading Example

Read Total Active Power: Offset address 806, read 2 consecutive registers

Returned data [High Word, Low Word] forms a 32-bit integer → Value ÷100 = kW

Exemplu: Raw reading = 12560 → 12560 /100 = 125.60 kW

  1. Common Pitfalls & Note
  2. Word Order: DIRIS A40 uses Big-Endian (high register = high 16-bit). Most configuration software supports this natively; some drivers require manual swap of high/low word.
  3. Incompatibility between old and new firmware register maps

All readings equal zero: Likely old firmware register map (starts at 0x700).

  1. CT/PT Ratio: After ratio setting inside the meter, register values already represent primary-side actual values. Do NOT multiply by transformer ratio again.
  2. Avoid reading excessive continuous registers in one request; limit to ≤20 registers per command to prevent communication errors.
  3. Extended registers for harmonic, THD, maximum demand and event logs are available and generally unnecessary for conventional data acquisition.
  4. Access Official Full PDF Document

Official Manual Reference: 536103B (DIRIS A40/A41 Modbus communication manual), containing complete register list, alarm parameters and write registers.

Procedure to Modify RS485 Modbus Communication Parameters via Front Panel for SOCOMEC DIRIS A40 (48250201)

Front Panel Button Definition (96×96 Model)

◀ LEFT: Cursor left / Scroll up

▶ RIGHT: Cursor right / Enter & Confirma

▲ UP: Value increase / Scroll up

▼ DOWN: Value decrease / Scroll down

Default Administrator Password: 100

Default Communication Settings: Slave address=1, Baud rate=9600, Data bits=8, Stop bits=1, Parity=None

Step-by-Step Operation

Pas 1: Enter Configuration Menu

Meter displays normal measurement screen (voltage/current view)

  1. Apăsare lungă [▶ RIGHT] confirm key for 3~5 seconds
  2. Screen prompts CODE ?, password input required

Pas 2: Input Password 100

▲ UP: Increment digit

▶ RIGHT: Shift cursor to next digit

Set digits sequentially: `1` → `0` → `0`

After input, long press [▶ RIGHT] to enter main configuration menu

Pas 3: Navigate to Communication Menu

Scroll using ▲ / ▼ to locate:

RS485 COMMUNICATION

Press ▶ RIGHT to enter submenu

Pas 4: Modify Communication Parameters Item by Item

Four configurable items:

  1. COM ADR (Modbus Slave Address)

Gamă: 1~247. Ensure unique address for each meter on the bus.

▶ Enter → Adjust value via ▲▼ → ▶ Confirm

  1. BAUD (Baud Rate)

Opțiuni: 1200 / 2400 / 4800 / 9600 / 19200 / 38400 / 57600 /115200

  1. PARITY

NU: No parity (Recommended for site use)

EVEN: Chiar și paritate

ODD: dd parity

  1. STOP BIT

1 / 2; Standard site setting: 1

⚠️ Critical: Host device (PLC/Gateway/Modbus Poll) parameters must match the meter exactly, otherwise communication failure occurs.

Pas 5: Save and Exit

After all parameters modified:

  1. Scroll to EXIT using ▲▼
  2. Press ▶ RIGHT to confirm exit
  3. Prompt SAVE? YES/NO

Select YES to save; select NO to discard all changes.

After successful saving, meter automatically returns to measurement main screen. New communication settings take effect immediately.

⚠️ Common Faults & Reminders

  1. Forgotten Password 100

Panel modification unavailable. Two solutions:

① Use Easy Config software via RS485 to read or reset password;

② Factory reset (Raportul CT, energy data will be cleared. Proceed with caution).

  1. Troubleshooting checklist if communication fails after parameter modification

No duplicated slave addresses; baud rate, parity and stop bits fully matched

Cablaj RS485: A to A, B to B. Do not reverse polarity

120Ω terminating resistor at bus end to be deployed as required

Confirm model 48250201 integrates built-in RS485; no extra communication module required

  1. Menu Language

Older firmware: English menu `RS485 COMM`

Newer firmware: Chinese menu supported RS485通讯

Recommended Parameter Template

ParametruSetare recomandată
Slave AddressAssign according to site layout (1~247)
Baud Rate9600
Parity PARITYNU (Nici unul)
Stop Bit STOP1