Basic Model Definition
Номер по каталогу: 440R-N23114
Internal Model Code: МСР126.1Т
Бренд: Allen-Bradley (Роквелл Автоматизация), Guardmaster Minotaur Series
Lifecycle: Active production model, manufactured in Czech Republic, standard 1-year warranty
- Основные электрические характеристики
2.1 Источник питания
Номинальное напряжение: 24В переменного/постоянного тока, operating range: 0.85~1.1× rated voltage (20.4~26.4V)
Потребляемая мощность: 4Вт, compatible with 50/60Hz
Terminals A1/A2: Входная мощность
2.2 Safety Inputs (Dual-channel 4-wire with cross short-circuit detection)
2 нормально закрытый (Северная Каролина) safety input paths (S11-S12 / S21-S22)
Supports dual-channel emergency stop, safety door switches and safety light curtains; built-in cross-channel short-circuit fault diagnosis
Maximum input loop resistance: ≤90Ω
2.3 Reset Circuit (S33-S34)
MSR126.1T supports automatic reset and manual reset dual modes
- Автоматический сброс: Short S33 and S34; outputs close automatically after faults are cleared
- Ручной сброс: Connect an external normally open reset pushbutton to S33-S34; manual push is required to restore outputs
Difference from MSR126.1R: MSR126.1R only provides monitored manual reset without automatic reset function
2.4 Safety Output Contacts (Force-guided safety contacts complying with IEC 61810-3)
2 safety normally open (НЕТ) контакты: 13-14, 23-24
Load Ratings:
DC-13: 6A/24V DC; 3A/24V DC (for frequent switching)
АС-15: 5А/250 В переменного тока
Время ответа: Приблизительно. 15РС; Recovery Time: 100РС
No auxiliary alarm contacts
- Safety Certification Ratings (Top Industry Standards)
ИСО 13849-1: Категория 4 / ПЛ е
МЭК 61508 / МЭК 61511: СИЛ 3
В 954-1: Safety Category 4, Категория 0 Останавливаться
Сертификаты: CE, cULus, CCC, BG, C-Tick
- Mechanical Dimensions & Монтаж
Ширина: 22.5мм (compact DIN rail mounting)
Габаритные размеры: 110мм (ЧАС) × 75mm (Д) × 22.5mm (Вт)
Масса: 160г
Терминалы: Fixed screw terminals (non-pluggable), Степень защиты IP20
Рабочая температура: -25℃ ~ +70 ℃
- Front Panel LED Indicator Meanings
- PWR (Зеленый): Steady on when power supply is normal
- CH1 (Зеленый): Illuminated when Channel 1 input circuit is closed
- CH2 (Зеленый): Illuminated when Channel 2 input circuit is closed
All three LEDs on → Safety output contacts closed; Any single channel open → Outputs cut off
- Типичные сценарии применения
- Dual-channel emergency stop button circuit monitoring
- 4-wire safety door switches (with short-circuit detection)
- Safety light curtain / light screen safety circuits
- Safety cut-off for machine tools, automated production lines and packaging equipment
Suitable for equipment requiring high safety ratings of PL e / уровень безопасности SIL3
- Series Model Comparison for Selection
| Catalog No. | Internal Code | Режим сброса | Источник питания | Channel Configuration |
| 440R‑N23114 | МСР126.1Т | Selectable Auto/Manual Reset | 24В переменного/постоянного тока | Dual-channel 4-wire |
| 440R‑N23113 | MSR126.1R | Monitored Manual Reset Only | 24В переменного/постоянного тока | Dual-channel 4-wire |
| 440R‑N23112 | MSR126T | Auto/Manual Reset | 230В и | Dual-channel 4-wire |
- Brief Wiring Logic
- Connect 24V AC/DC power to terminals A1/A2
- Wire two NC safety switches (аварийная остановка / дверные выключатели) in series to S11-S12 and S21-S22 respectively
- Short-circuit S33-S34 for automatic reset; connect an NO pushbutton in series for manual reset
- Wire the safety coil of main contactors in series across terminals 13-14 и 23-24
- Disconnection of any safety input or cross-channel short-circuit will simultaneously open both NO outputs to cut power supply
- Troubleshooting Guidelines
- PWR LED off: Power phase loss, insufficient voltage or loose wiring
- Single CH1/CH2 LED off: Corresponding channel switch open or circuit wire breakage
- Both CH1 and CH2 LEDs lit but outputs fail to close: Cross-channel short-circuit fault; power cycle to reset, or reset circuit not shorted / reset button not pressed
- Контактная сварка: Excessive output load; replace contactors with higher capacity
Full Specifications of Safety Output Contacts for Allen-Bradley 440R-N23114
- Basic Contact Structure
- Количество & Тип: 2 independent redundant safety normally open (НЕТ) contacts at terminals 13-14 и 23-24; no auxiliary alarm contacts or delayed outputs
- Contact Construction: Force-guided safety contacts (МЭК 61810-3), dual-channel redundant mechanical interlock. Single contact welding cannot maintain circuit conduction, fulfilling Category 4 / ПЛ е / SIL3 safety architecture
- Контактный материал: AgSnO₂ silver tin oxide, arc-resistant and anti-welding
- Minimum Conducting Current: 10мА (ensures reliable circuit detection by contacts)
- Rated Load Currents (Official Standard Load Categories)
2.1 AC Load (АС-15, standard load for electromagnetic contactors)
250В и: 6А (inductive-resistive load, cosφ=0.35)
UL B300 certified rating: 5А / 250В и
2.2 DC Load (DC-13, электромагнитные клапаны / DC coils)
Frequent switching at 24V DC: 3А (standard switching rating)
Low-frequency light load (0.1Гц) at 24V DC: Макс. 6A for short-term use (long-term high-frequency operation not recommended)
2.3 Continuous Thermal Current Ith (static carrying current without switching)
Maximum static continuous current per single contact: 6А (only for permanent conduction with rare break operations)
- Электрическая выносливость & Operating Timing
- Электрическая выносливость (220В и / 4А / cosφ=0.35)
6A breaking capacity: 100,000 операции
4A light load: 500,000 операции
- Safety Operation Timing
Response time from safety input open to contact break: ≤15ms
Contact pull-in recovery time after fault clearance: Приблизительно. 100РС
- Диэлектрическое выдерживаемое напряжение
Withstand voltage across open contacts: AC750V for 1 минута
Сопротивление изоляции (DC500V test): ≥1000MΩ
- External Protection & Wiring Limitations
- Recommended Fuse for Output Circuit
Slow-blow fuse: 6А; Fast-acting fuse: 10А. Over-rated fuses are prohibited to prevent contact ablation and welding
- Applicable Wire Gauge: 0.2~2.5mm² solid / stranded copper wires; fixed non-pluggable screw terminals
- Maximum Operating Voltage: 250В и / 30В Вашингтоне; overvoltage is strictly forbidden
- Contact Performance Matching Safety Ratings
ИСО 13849-1: Категория 4, ПЛ е (independent cut-off via dual redundant contacts)
МЭК 61508: уровень безопасности SIL3; single contact failure will not disable safety cut-off function
Stop Category: В 60204-1 Категория 0 hard cut-off stop
- Quick Load Selection Table
| Тип нагрузки | Напряжение | Номинальный ток | Сценарии применения |
| AC‑15 | 250В и | 6А | AC contactor coils |
| DC‑13 | 24В Вашингтоне | 3А | DC solenoid valves, DC contactors |
| Static Continuous | ≤250VAC / 30В постоянного тока | 6А | Circuits with permanent conduction and minimal breaking operations |
tic Continuous | ≤250VAC / 30В постоянного тока | 6А | Circuits with permanent conduction and minimal breaking operations |
Контактор,автоматический выключатель,солнечный инвертор,электрический счетчик,солнечные батареи


















NH42-63-318x560.png)