Бренд: Basler Electric (США)
Описание: Microprocessor-based digital automatic voltage regulator for brushless synchronous generator excitation control
Core replacement model: Marathon DVR2000E/DVR2000EC, pin and footprint compatible, plug-and-play retrofit
✅ Four Control Modes
- AVR Automatic Voltage Regulation (По умолчанию):Maintains constant generator terminal voltage, accuracy ±0.25% (at rated power factor and constant frequency)
- FCR Field Current Regulation:Manual excitation current control for commissioning and AVR fault backup, adjustable from 0~3Adc
- PF Power Factor Regulation:For grid paralleling, constant power factor control
- VAR Reactive Power Regulation:For grid paralleling, constant reactive power output control
📌 Основные электрические характеристики
Excitation Output (ШИМ): 75 Vdc/3 Adc continuous; Forcing 150 В постоянного тока /7.5 Adc for 10s (at 200Vac input)
Minimum Excitation Winding Resistance: ≥18 Ω (critical selection parameter)
PMG Power Supply: 180–240 Vac, 200–360 Hz, 350 Вирджиния
Voltage Sensing: Single-phase/three-phase RMS sensing, supports 120/240/480/600Vac
Current Sensing: Single-phase CT, max 5A AC, for reactive droop, PF/VAR control
Коммуникация: Rear RS232 DB9 port, configuration software BESTCOMS™ BE2000E (V2.02.01) for parameter setup, waveform recording and parameter backup
Интерфейсы: 4 цифровые входы, 1 common alarm relay output; front panel HMI + LED status indicators, local parameter modification
🛡️ Protection & Function List
Soft Voltage Ramp: 1–120s adjustable, suppress voltage surge during startup
OEL Over Excitation Limit + Over Excitation Shutdown
В/Гц (Volts/Hertz) Limiting, Under-frequency Load Shedding
Generator Overvoltage Shutdown, Loss-of-Sensing Protection
Regulator Internal Over-temperature Protection
Excitation Crowbar Protection Circuit
Paralleling Functions: Reactive Droop Compensation, Reactive Differential Compensation for multi-generator parallel operation
High THD tolerance design, suitable for non-linear harmonic loads
📎 Supporting Documents (Basler Official)
BE2000E Bulletin Rev11
Instruction Manual Rev G
BESTCOMS Configuration Software
Generator Paralleling Technical White Paper
🧩 Типичные приложения
Industrial diesel/gas brushless synchronous generator sets, standby power supplies, continuous-duty power stations, multi-unit grid paralleling projects. Widely used for retrofit replacement of original Marathon generators.
Basler BE2000E Fault Tree (OEL/OV/SENSE LOSS/OVERTEMP)
General Pre-rules: After fault latch-up, power off for ≥60 seconds to reset. Use BESTCOMS software first to capture fault snapshots, waveform records and real-time readings (excitation current, напряжение возбуждения, terminal sensing voltage). Distinguish between Limit Alarm (LIMIT) and Shutdown Trip (SHUTDOWN). For grid-tied generators, de-parallel and shed loads before troubleshooting to avoid secondary accidents.
Protection Action Logic: Alarm relay AL1/AL2 closes; after trip, regulator reduces excitation, Crowbar circuit activates and voltage regulation output ceases.
- OEL Over Excitation Alarm/Over Excitation Shutdown
Симптомы: OEL LED flashes; BESTCOMS shows excitation current out of limit. Two statuses: OEL Limit (current limiting, no trip), OEL Shutdown (timeout latch-up)
OEL Alarm ON
Шаг 1: Verify generator operating condition
✅ Generator overload, heavy inductive load, excessive reactive power → Shed load, verify rated excitation current of generator
✅ Grid paralleling: Excessive PF/VAR setpoint, unbalanced reactive power sharing, incorrect droop setting → Switch to local AVR mode, check PF/VAR setting, CT wiring and CT ratio
✅ Low frequency/V/Hz action raises excitation (speed drop) → Check prime mover speed and governor
Шаг 2: Parameter check via BESTCOMS
OEL current threshold set too low → Re-set according to rated excitation winding current
OEL delay time set too short → Typical 5~10s; short-duration forcing is permitted, avoid 0s instant trip
Improper soft-start setting, startup surge triggers OEL → Extend soft ramp time
Шаг 3: Hardware circuit measurement (power off and locked out, test excitation winding)
Partial short/turn-to-turn short in excitation winding → Winding resistance far below nameplate minimum value; shorted winding causes high excitation current and repeated OEL
Loose excitation terminals, damaged insulation, earth leakage → Insulation resistance test
Abnormally high PMG supply voltage → Measure PMG input 180–240Vac, troubleshoot PMG if out of range
Шаг 4: Regulator hardware check
Excitation PWM power transistor breakdown/shorted → Continuous high excitation current and OEL latch-up
Replace BE2000E and re-test; if OEL recurs after replacement → Fault in exciter assembly
Примечание: OEL is rotor protection. Repeated OEL events will burn excitation rotor
- OV Generator Overvoltage Alarm
Симптомы: OV LED ON; fixed 0.75s trip delay; threshold default 105~120% rated voltage, программно настраиваемый
OV Alarm ON
Шаг 1: Distinguish true overvoltage vs false sensing alarm
Measure generator terminal voltage with multimeter and compare with BESTCOMS reading
Measured voltage actually high: True overvoltage
Measured voltage normal, software reads high: Sensing circuit fault, refer to SENSE LOSS branch
Шаг 2: Troubleshoot true overvoltage
Overvoltage at no-load startup: High voltage setpoint, excessive PID gain, failed soft ramp
Voltage overshoot after sudden load rejection: Mismatched PID (P/I/D), excessive transient gain
Prime mover speed runaway (governor failure) → Rectify diesel/gas engine governor first
Grid-tied unit: Voltage spike when reactive power is removed during de-paralleling
Шаг 3: Hardware inspection
Failed excitation Crowbar circuit, unable to discharge excitation energy
BE2000E power output transistor shorted, excitation uncontrolled
Excessive PMG supply voltage, excitation drive overflow
Перезагрузить: Выключить на 1 minute after OV latch-up. Do NOT repeatedly start the unit with recurring OV, risk of downstream equipment breakdown
- SENSE LOSS Loss of Sensing
Симптомы: SENSE LOSS LED flashes; protection logic: configurable delay (0–25s) before trip, regulator de-excites to prevent catastrophic overvoltage caused by uncontrolled excitation without valid sensing
SENSE LOSS Alarm ON
Шаг 1: Выключить питание, inspect voltage sensing circuit (most frequent fault point)
Broken sensing wire, свободный терминал, перегоревший предохранитель, сработал автоматический выключатель
Wrong phase sequence, reversed single-phase sensing wiring (BE2000E supports single/three-phase sensing; hardware wiring must match software mode)
Failed PT voltage transformer, PT ratio mismatch with setting, PT secondary open circuit
Sensing cable earth fault, короткое замыкание, повреждение изоляции
Шаг 2: Verify configuration in BESTCOMS
Wrong sensing mode: three-phase hardware with single-phase software setting, или наоборот
Rated voltage setting mismatched with PT secondary output (например. 480V generator set as 600V)
LOS delay set too short, normal voltage fluctuation triggers trip
Шаг 3: Noise and grounding issues
Poor regulator grounding, routed together with power cables, heavy harmonic interference causes intermittent sensing dropout
Extreme high THD from rectifier loads; although the unit is THD tolerant, severe distortion can still trigger loss of sensing
Шаг 4: Regulator hardware judgment
Normal voltage present at sensing terminals but no reading in software → Internal sensing board damage on BE2000E
SENSE LOSS persists after regulator replacement → Fault in generator PT/secondary circuit
Critical Warning: Do NOT bypass SENSE LOSS protection for startup, risk of runaway overvoltage and equipment damage
- OVERTEMP Regulator Over Temperature
Симптомы: OVERTEMP LED flashes; internal temperature sensor triggers over-temperature trip latch-up, protects IGBT/PWM power stage
OVERTEMP Alarm ON
Шаг 1: Ambient and heat dissipation (наиболее частая причина)
Закрытый шкаф, плохая вентиляция, высокая температура окружающей среды, прямой солнечный свет
Heatsink clogged with dust and grease, airflow blocked by cables
Nearby heat sources (ЧРП, контакторы) heating the AVR
Шаг 2: Continuous high excitation under load
Long-term high reactive power, continuous OEL limiting, power devices run hot
Low excitation winding resistance, excitation current constantly near 3A rating
Frequent excitation forcing (150V/7.5A 10s forcing cycle)
Шаг 3: Power supply and wiring
Sustained high PMG supply voltage, increased power stage loss and heat
Loose excitation output terminals, contact resistance heat conducted to regulator
Плохое заземление, common-mode interference causes abnormal heating of internal components
Шаг 4: Regulator hardware check
Drifted/failed internal temperature sensor (OVERTEMP alarm immediately after cold power-up)
Aged power devices, high leakage current, heat even at no-load
Действие: Shut down and cool for 30min before retest; alarm triggers immediately after loading when cooled → Regulator damaged, заменять
Standard General Troubleshooting Workflow for Site
- Lockout-tagout and isolate power; power off ≥60s to clear latched faults
- Включение питания, connect BESTCOMS, retrieve fault logs, waveform records and live measurements (excitation current, sensing voltage, внутренняя температура)
- Fault classification: Operating condition/load/governor/grid issue → Parameter setting issue → External circuit (ПТ, PMG, excitation winding, Коннектикут) → Confirm regulator hardware failure only at last
- После ремонта: Test no-load operation first, then apply load gradually; for grid-tied units, complete AVR regulation and droop test before paralleling
Quick Reference Cheat Sheet
OEL = Excitation current too high (rotor/excitation circuit, excess reactive load, low limit threshold)
OV = Terminal voltage too high (скорость, PID tuning, shorted excitation, load rejection surge)
SENSE LOSS = Voltage sensing signal missing (ПТ, sensing wiring, конфигурация, EMI noise)
OVERTEMP = AVR overheating (плохое охлаждение, continuous high excitation, faulty sensor/power device)
Basler Electric Digital Excitation Regulator (Digital AVR/DECS) Полный список моделей
/Классификация: Серия БЭ (retrofit models, mainly for Marathon replacement), DECS Series (standard digital excitation controllers, mainstream stock). Статус: Active/Obsolete, description and typical application
- Серия БЭ (Модернизация & Сменные модели, BE2000E belongs here)
| Модель | Статус | Краткое описание | Примечания |
| BE2000E | Активный | PMG-fed digital AVR for brushless synchronous generators | Direct drop-in replacement for Marathon DVR2000E / DVR2000EC; PWM output 75Vdc/3A, RS232, BESTCOMS, 4 control modes (AVR/FCR/PF/VAR) |
| BE300PM | Активный | Potting compact digital AVR | Replaces Marathon PM300, PMG supply, built-in OEL & under-frequency compensation, for harsh environment generators |
- DECS Series (Basler Mainstream Digital Excitation Control for Industrial & Power Stations)
Устаревшие модели (Most Obsolete, Used for Retrofit)
| Модель | Статус | Краткое описание | Примечания |
| DECS-15 | Устаревший | Entry-level compact digital AVR | Early small brushless generator sets |
| DECS-100 | Устаревший | Classic compact digital excitation controller | Sub-models: A11 / A15 / B11 / B15; PMG or terminal sensing supply, widely used on diesel generators, BESTCOMS software |
| DECS-200 | Устаревший | Medium-duty excitation controller | Multiple excitation power sources, drives external power modules |
| DECS-200N | Устаревший | Negative forcing version of DECS-200 | For grids with severe disturbance, requires fast de-excitation |
| DECS-300 | Устаревший | Medium power station excitation controller | Grid paralleling, hydro / small turbine generator retrofit |
| DECS-400 | Устаревший | Large static excitation master controller | High-power generators, legacy excitation system upgrade projects |
Current Active Flagship Models (Official Website Primary Offering)
| Модель | Статус | Краткое описание | Примечания |
| DECS-150 | Активный | Economical all-round digital excitation controller | Small/medium diesel & gas generators, paralleling, интегрированная защита, BESTCOMSPlus, экономически эффективный |
| DECS-250 | Активный | High-performance universal digital excitation controller | Popular model; supports PSS Power System Stabilizer, programmable logic, auto PID tuning, grid-tied power stations, standby power, integrated generator protection |
| DECS-250E | Активный | DECS-250 extended version | Expanded I/O, redundant interfaces, for large generator packages |
| DECS-250N | Активный | DECS-250 negative forcing version | Negative excitation forcing, fast voltage suppression under grid disturbance |
| DECS-450 | Активный | High-power premium excitation controller | Середина & large steam / hydro generators, drives external power cabinets, redundant architecture, grid compliance, large power station retrofit |
| DECS-2100 | Активный | Master excitation controller for large / megawatt-scale generators | Drop-in replacement for GE EX2000 and similar large excitation systems, core unit for excitation cabinet packages |
- Auxiliary Supporting Modules (Excitation Accessories, Not Standalone AVR)
VRM-2020: Remote Voltage Regulator Module (works with DGC-2020 genset controller)
ICRM-7/ICRM-15: PWM AVR excitation inrush current limiting protection module
MVC: Manual Voltage Control Unit (backup manual excitation if AVR fails)
- Selection Quick Guide for Replacement
- Direct replacement for Marathon DVR2000E → BE2000E (приколоть & совместимый монтаж, priority choice)
- Standard diesel generator with budget constraint → DECS-150
- General paralleling application requiring PSS and rich protection → DECS-250/DECS-250N
- Hydro/steam high-power generators, excitation cabinet packages → DECS-450/DECS-2100
- Retrofit of old DECS-100/200/300/400 → Upgrade to DECS-250 or DECS-450 preferentially
- Совместимость программного обеспечения
BE2000E: BESTCOMS (legacy version, V2.02.01)
DECS150/250/450: BESTCOMSPlus (new generation software)