Устройство плавного пуска Danfoss MCD202-015-T4-CV1

(Материал №.: 175G5221) VLT® Compact Starter MCD202 Compact Soft Starter Short model code: MCD202015T4CV1 ✅ Model Code Explanation MCD202: MCD202 series, current limit start + built-in motor protection (different from MCD201; MCD201 only has voltage ramp, no built-in motor overload protection) 015: Рейтинг 15 kW T: Трехфазный 4: Main circuit voltage 200–440 VAC CV1: Контроль ...

  • Подробная информация о продукте

(Материал №.: 175G5221)

VLT® Compact Starter MCD202 Compact Плавный стартер

Short model code: MCD202015T4CV1

✅ Объяснение кода модели

MCD202: MCD202 series, current limit start + built-in motor protection (different from MCD201; MCD201 only has voltage ramp, no built-in motor overload protection)

015: Рейтинг 15 кВт

Т: Трехфазный

4: Main circuit voltage 200–440 VAC

CV1: Контроль питания 24 В переменного/постоянного тока

Frame A, Монтаж на DIN-рейку (specifications ≤30 kW support DIN rail mounting)

✅ Основные электрические характеристики

Подходящая мощность двигателя: 15 кВт

Номинальный ток: 34 А

Main supply: 3×200~440 VAC (-15% / +10%), 45–66 Гц

Контроль питания: 24 В переменного/постоянного тока

Start mode: Пуск с ограничением тока + TVR timed voltage ramp soft stop

Встроенный байпас: Да; bypasses SCR after start completion to reduce heat loss

Функции защиты: Перегрузка двигателя (default Class 10), over-temperature, phase sequence loss, потеря фазы, SCR fault, motor PTC thermistor input

Starting capability: Standard 4×Ie for 6 с; heavy-duty mode 4×Ie for 20 с

Метод управления: 2-проволока / 3-wire start-stop, релейный выход

Вес нетто: 2.4 кг; gross weight: 2.9 кг

Рабочая температура окружающей среды: До 50 °C without derating

✅ Типичные применения

Водяные насосы, фанаты, конвейеры, компрессоры. Ideal for scenarios requiring current-limited starting to reduce grid inrush, without needing an external thermal relay.

✅ Сравнение между сериями & Примечания по замене

  1. MCD202-015-T4-CV3: Control supply 110–440 VAC (CV3 version, наиболее распространенный). Not CV1; control circuits cannot be directly interchanged.
  2. MCD201-015-T4-CV1: Same power and voltage rating, but MCD201 has no built-in motor protection and fewer functions.
  3. Successor replacement: The MCD200 series is end-of-life. New projects are recommended to use the MCD600 series equivalent.

✅ Fault Quick Reference (Common for MCD202)

эээ 1: Перегрев

эээ 2: Перегрузка двигателя

эээ 4: Потеря фазы / текущий дисбаланс

эээ 5: Start timeout

эээ 6: SCR fault

эээ 10: PTC motor overheat

✅ Start and stop times are adjustable. The MCD202 uses rotary dip-knob adjustment (no menu display panel).

Примечание: The MCD201 does not support soft stop. Only the MCD202 features TVR voltage-type soft stop.

Parameter Ranges (Manual MG17C241)

  1. Start ramp-up time (Ramp Up): 2~20 s, заводская настройка по умолчанию 10 с

Operating logic: Current limiting is primary, voltage ramp is secondary; current ramp can also be enabled (2/5/15 s preset gears)

  1. Soft stop time (Soft Stop / Ramp Down): 2~20 s by gear selection; can also be set to soft stop disabled for direct power-off shutdown (заводская настройка по умолчанию: soft stop disabled)

Метод регулировки

Four adjustment knobs on the front face:

Ручка 1: Номинальный ток двигателя

Ручка 2: Ограничение стартового тока

Ручка 3: Start ramp-up time (Ramp Up)

Ручка 4: Soft stop ramp-down time (Soft Stop)

Brief Application Guidance (Most common for pump applications)

Фанаты: 5–10 s start time; soft stop is usually not required

Centrifugal pumps for water hammer suppression: Enable soft stop, set 8–15 s soft stop time

Soft stop principle: TVR timed voltage ramp-down. It is not variable-frequency deceleration and cannot provide precise constant-speed slowdown; it is only used to suppress water hammer and light-load buffering.

Limitation Reminders

This compact soft starter uses stepped gear adjustment instead of continuous stepless fine-tuning.

Soft stop only activates after a stop command. Once full-speed bypass is closed, the SCRs are bypassed and no longer regulate voltage.

The start timeout protection must be set in coordination; its value must be longer than the actual start time, otherwise Err5 start timeout will trigger.

MCD202-015-T4-CV1 Start / Stop Time Adjustment Precautions

Основная предпосылка: This unit uses TVR timed voltage ramp start/soft stop + встроенный байпас. It is not a VFD. SCRs only work during the start ramp and soft stop ramp. After bypass pull-in at full speed, thyristors are out of circuit.

  1. Start Ramp-Up Time (Ramp Up)
  2. Adjust the current limit knob together with ramp time; do not only adjust the time setting.

The MCD202 operates in current-limit priority mode. Even if ramp time is set to 20 с, a low current limit may prevent the motor from accelerating and trigger Err5 (start timeout). The ramp only defines the voltage change profile; the current ceiling is locked by the current limit knob.

Field tip: Set current limit first to guarantee rotation, then configure ramp time. For heavy-duty conveyors and compressors, raise current limit before extending start time.

  1. Start timeout protection (Err5) must be longer than the actual acceleration time.

Start timeout range: 2~20 s. Timeout setting actual time to reach full speed, leave a margin of 2–5 s. А 15 s ramp paired with a 10 s timeout will almost certainly trip.

  1. Gear-based adjustment, not continuous stepless regulation

Knob settings are discrete preset steps, not smooth fine adjustment. Fixed range: 2~20 s, заводская настройка по умолчанию 10 с.

  1. Longer start times extend SCR heating; restrict starts per hour.

Long ramp times combined with high current limits increase thyristor heat generation. For frequent start-stop applications, avoid setting maximum 20 s ramp, otherwise Err1 over-temperature occurs easily. The built-in bypass reduces temperature at full speed, but the SCRs bear load and heat during acceleration.

  1. Differentiate between loaded and light-duty starting

Light-duty fans / центробежные насосы: 5–10 s is sufficient. Excessively long ramps may cause low-speed stall and sustained high current.

Ленточные конвейеры, шнековые питатели, насосы для тяжелых условий эксплуатации: Ramp can be extended moderately, paired with higher current limit.

  1. Soft Stop Time (Ramp Down, MCD202 exclusive; unavailable on MCD201)
  2. Soft stop ≠ VFD deceleration; it only reduces voltage gradually.

Constant-speed deceleration cannot be achieved. Torque drops with voltage reduction, and the motor slows by load inertia. For high-inertia fans, even 20 s soft stop may still result in fast coasting; do not expect precise speed control.

  1. Factory default = soft stop disabled. When disabled, the bypass opens and the motor coasts freely.

Soft stop is only enabled for pumps requiring water hammer protection. Soft stop is unnecessary for most fan applications.

Critical point: The bypass contact only opens after soft stop completes and voltage falls to a low level. SCRs remain active and generate heat throughout the soft stop sequence.

  1. Do not use long soft-stop times for low-inertia loads

Малые конвейеры, valve actuators and similar low-inertia loads will draw sustained low-voltage high current under long soft-stop settings, leading to motor overload Err2 or soft starter overheat Err1.

  1. Emergency stop overrides soft stop logic

External emergency stop cuts the circuit directly and skips the soft stop ramp. Soft stop only responds to normal stop commands.

  1. Распространенная ошибка: Bypass Operation Logic

Start sequence: Start command → SCR voltage ramp → full voltage reached → built-in bypass relay closes, SCRs exit operation. The configured start time only applies before bypass closure.

Stop sequence: Stop command → bypass contact opens first, switching back to SCR control before soft stop ramp begins. If bypass contacts are welded or poorly contacting, soft stop fails immediately and faults occur.

Симптом: Soft stop configured but motor cuts off instantly when stopping. Prioritize inspecting the bypass contactor.

  1. Тайминг & Start-Stop Interval

A fixed 2 s interlock delay is built between successive starts to dissipate motor back EMF. Do not program extremely short start-stop pulses in PLC, repeated rapid cycling will trigger main-circuit faults.

Do not send a new start command while the motor is still coasting down. The MCD202 does not support flying start and will see severe inrush current.

  1. Coordination with Motor Protection (CV1 variant has built-in motor protection)

Защита двигателя от перегрузки (Сорт 10) accumulates thermal capacity based on operating current:

Long start ramps with sustained low-speed high current build thermal load and may trip Err2 overload during acceleration.

The motor rated current knob must match the motor nameplate rating, otherwise all protection thresholds are invalid.

  1. Control Supply Variant Note (Your unit CV1: 24 В переменного/постоянного тока)

Start-stop logic is unaffected by the CV1 supply. Однако: Loss of the 24 V control supply disables soft stop, and the motor shuts down directly without ramp.

  1. Recommended Field Commissioning Sequence
  2. Set motor rated current to match the motor nameplate
  3. Set current limit to guarantee successful loaded start
  4. Configure start ramp-up time
  5. Set start timeout = ramp time + safety margin
  6. Enable soft stop only for water hammer control; set to soft-stop off for other loads
  7. Test start-stop under no load, observe indicator timing and monitor for Err1/Err2/Err4/Err5
  8. Fault Mapping

Err5 Start timeout: Current limit too low OR ramp too long OR timeout threshold set too small

Err1 Over-temperature: Частая езда на велосипеде, excessively long start/stop ramps, continuous SCR heating

Err2 Motor overload: Long duration of low-speed high current causing thermal accumulation

Данфосс Soft Starter Full Model List & Material Order Codes (Mainstream 400V for China market, T4 = 200–440 VAC)

Model coding rules for MCD201 / MCD202

CV1: 24 V AC/DC control supply (Your MCD202-015-T4-CV1 is CV1)

CV3: 110–240 VAC / 380–440 VAC control supply (most widely ordered)

T4 = 200–440 V; T6 = 200–575 V

MCD201: Voltage ramp start only, no built-in motor overload protection, no soft stop

MCD202: Пуск с ограничением тока + TVR soft stop + complete motor protection (series you are using)

Статус: MCD200 (MCD201/MCD202) is phased out. New projects select MCD600.

  1. MCD202 (With protection + soft stop, including your model)
Power @400VНоминальный токПолная модельMaterial Order No.
7.5 кВт18 АMCD202-007-T4-CV1175G5210
7.5 кВт18 АMCD202-007-T4-CV3175G5211
11 кВт24 АMCD202-011-T4-CV1175G5212
11 кВт24 АMCD202-011-T4-CV3175G5213
15 кВт34 АMCD202-015-T4-CV1175G5221 (твоя часть)
15 кВт34 АMCD202-015-T4-CV3175G5222
18.5 кВт39 АMCD202-018-T4-CV1175G5224
18.5 кВт39 АMCD202-018-T4-CV3175G5225
22 кВт48 АMCD202-022-T4-CV1175G5227
22 кВт48 АMCD202-022-T4-CV3175G5228
30 кВт60 АMCD202-030-T4-CV1175G5230
30 кВт60 АMCD202-030-T4-CV3175G5231
37 кВт75 АMCD202-037-T4-CV1175G5233
37 кВт75 АMCD202-037-T4-CV3175G5234
45 кВт88 АMCD202-045-T4-CV1175G5236
45 кВт88 АMCD202-045-T4-CV3175G5237
55 кВт105 АMCD202-055-T4-CV1175G5239
55 кВт105 АMCD202-055-T4-CV3175G5240
75 кВт140 АMCD202-075-T4-CV1175G5214
75 кВт140 АMCD202-075-T4-CV3175G5215
90 кВт170 АMCD202-090-T4-CV1175G5217
90 кВт170 АMCD202-090-T4-CV3175G5218
110 кВт200 АMCD202-110-T4-CV1175G5220
110 кВт200 АMCD202-110-T4-CV3175G5242

7.5~30 kW: Монтаж на DIN-рейку; 37 кВт и выше: base mount only

  1. MCD201 (Эконом-версия, no built-in motor protection, no soft stop)
ВластьТекущийПолная модельНомер материала.
7.5 кВт18 АMCD201-007-T4-CV3175G5165
15 кВт34 АMCD201-015-T4-CV3175G5166
18.5 кВт39 АMCD201-018-T4-CV3175G5167
22 кВт48 АMCD201-022-T4-CV3175G5168
30 кВт60 АMCD201-030-T4-CV3175G5170
37 кВт75 АMCD201-037-T4-CV3175G5171
45 кВт88 АMCD201-045-T4-CV3175G5172
55 кВт105 АMCD201-055-T4-CV3175G5173
75 кВт140 АMCD201-075-T4-CV3175G5174
90 кВт170 АMCD201-090-T4-CV3175G5175
110 кВт200 АMCD201-110-T4-CV3175G5176
  1. MCD100 (Micro economy range, 1.5~11 kW, нет встроенного байпаса)

For small fans and pumps, компактный размер, no internal bypass

MCD100-001 (1.5 кВт / 3 А) 175G4001

MCD100-007 (7.5 кВт / 15 А) 175G4005

MCD100-011 (11 кВт / 25 А) 175G4009

  1. MCD600 (New generation flagship, direct replacement for MCD202, graphical menu, расширенные функции)

Sample code: MCD600-xxxB-T4-S1X00CV2; material codes start with 132H. Supports flying start, pump cleaning logic, extended protection and communication options. Power range 7.5~1400 kW

Equivalent replacement for your MCD202-015-T4-CV1 (15 кВт /34 А): MCD600-0034B-T4-S1X00CV1 (CV1 = 24 V control supply)

  1. Common MCD200 Series Spare Part Order Codes

MCD200 remote operator panel: 175G9004

Модуль связи Profibus: 175G9040

Modbus RTU module: 175G9041

EtherNet/IP module: 175G9043

Дополнительные замечания

  1. T6 versions (200–575 V) follow the same naming rule; replace T4 with T6, with separate material numbers.
  2. CV1 and CV3 control supplies are not interchangeable, a frequent site mistake.
  3. MCD202 includes built-in bypass; MCD600 can be ordered with or without bypass.
  4. Уведомление об окончании срока службы: MCD201/MCD202 are stock-only. New projects specify MCD600.