Schneider 3CT-H1-100-C Current Transformer

Full Specification of Schneider 3CT-H1-100-C Current Transformer (Dedicated for EOCR) Model Code Interpretation Code Segment Meaning Description 3CT Product Series Three-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea H1 Specification Code Primary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm 100 Rated Primary Current 100A (numerator ...

  • Подробная информация о продукте

Full Specification of Schneider 3CT-H1-100-C Current Transformer (Dedicated for EOCR)

  1. Интерпретация кода модели
Сегмент кодаЗначениеОписание
3КоннектикутСерия продуктовThree-phase combined current transformer, customized for Schneider EOCR motor protector, manufactured by SAMWHA Korea
H1Specification CodePrimary current rating 100A, circular aperture, applicable for cable outer diameter ≤25mm
100Rated Primary Current100А (numerator of transformation ratio)
СMounting/Terminal TypeTerminal block type; Z stands for direct lead wire type

Quick Identification: 3CT-H1-100-C = Three-phase 100/5A circular-aperture current transformer with terminal block, exclusive for EOCR

  1. Основные технические параметры
Категория параметраСпецификацияRemark
Transformation Ratio100A/5AStandard secondary current 5A, compatible with full EOCR series
Accuracy ClassСорт 1Measuring tolerance ±1%, meets protection and metering requirements
Rated Burden10ВирджинияMax permissible secondary loop impedance 200mΩ
Frequency Range50/60ГцGeneral industrial frequency
Номинальное напряжение изоляцииAC 600VМаксимальное непрерывное рабочее напряжение
Выдерживать напряжение2кВ (50Гц, 1мин)Insulation test standard between windings and earth
Insulation Resistance≥100MΩ (DC 500V)Measured by megohmmeter
Aperture SizeCircular φ25mmStandard bore of H1 series
Overall DimensionW150×H71×D55mmКомпактная структура, space-saving installation
Тип монтажаPanel mountingСовместим со стандартной DIN-рейкой 35 мм.
МатериалFlame-retardant engineering plasticCompliant with UL94 V0 standard
МассаПриблизительно. 0.58кгSingle unit weight
СертификацияCE, ULConforms to international safety standards
Номер заказа3CT-H1-100-CExclusive official Schneider order code
  1. Full Model List (EOCR 3CT Series)
МодельСоотношениеAperture ShapeBore SizeНоминальный токТип монтажа
3CT-HS-75-C/Z75/5АCircularφ22mm75АC=Terminal block, Z=Lead wire
3CT-H1-100-C/Z100/5АCircularφ25mm100АC=Terminal block, Z=Lead wire
3CT-HH-150-C/Z150/5АКвадрат30×30mm150АC=Terminal block, Z=Lead wire
3CT-H2-200-C/Z200/5АКвадрат35×35mm200АC=Terminal block, Z=Lead wire
3CT-H3-300-C/Z300/5АКвадрат45×45mm300АC=Terminal block, Z=Lead wire
3CT-H4-400-C/Z400/5АКвадрат55×55mm400АC=Terminal block, Z=Lead wire
  1. Cross-brand Alternative Comparison
БрендМодельСоотношениеТочностьBurdenДиафрагмаСовместимость
Шнайдер

(SAMWHA)

3CT-H1-100-C100/5АСорт 110Вирджинияφ25mmPerfect match for EOCR
Сименс5SD7410-7100/5АСорт 110Вирджинияφ25mmUniversal type, adaptation test required
АББCT-AR/100100/5АСорт 115Вирджинияφ25mmHigher burden capacity, EOCR compatible
ЧинтBH-0.66/100100/5АСорт 110Вирджинияφ25mmCost-effective domestic alternative
ВкусныйLMZ1-0.66/100100/5АСорт 110Вирджинияφ25mmВнутренняя замена, minor dimension difference

Примечания по замене

  1. Ensure secondary burden capacity ≥10VA for non-Schneider products to guarantee protection precision
  2. Aperture shall match cable outer diameter; H1 series fits cables below 25mm
  3. Calibrate transformation ratio and phase for alternative models
  4. Поиск неисправностей & Обслуживание
Явление неисправностиВозможные причиныInspection StepsРешения
No secondary outputНеправильная проводка, winding open circuit, loose terminalsCheck S1/S2 polarity; test secondary resistance; fasten terminalsCorrect wiring polarity; replace faulty CT; reinforce terminals
Large measuring deviationOverloaded circuit, mismatched ratio, core saturationCalculate loop impedance; verify ratio; check overload currentReduce circuit burden; replace matched model; upgrade CT specification
EOCR false trippingPhase shift, harmonic interference, CT saturationTest three-phase phase difference; check frequency converter interference; monitor surge currentRecalibrate phase; install harmonic filter; adopt high-saturation CT
Insulation failureDampness, insulation aging, mechanical damageMeasure insulation resistance; inspect shell cracks; test winding insulationDry or replace unit; renew CT; repair damaged parts

Правила безопасности

  1. Never test open secondary circuit; short-circuit S1/S2 beforehand to avoid high voltage hazard
  2. Check load and wiring preferentially when deviation exceeds ±2%
  3. Replace CT immediately if insulation resistance below 10MΩ
  4. Приложение & Cases

Применимые сценарии

EOCR motor protection system: Перегрузка по току, undercurrent and phase loss protection

Распределение электроэнергии низкого напряжения: Current monitoring and protection for circuits below AC 600V

Motor control center: Compact layout saves cabinet space

Industrial production lines: Heavy-duty equipment protection in steel, cement and automobile industry

UPS feeder in data center: Precise current monitoring

Inadmissible Scenarios

Long-term operating current over 120A causing core saturation

High frequency (>400Гц) or DC circuits with poor measuring accuracy

Outdoor installation without waterproof enclosure

Secondary circuit burden exceeding 10VA

Typical Cases

Случай 1: Motor Protection in Automobile Workshop

3 sets of 55kW three-phase asynchronous motors equipped with EOCR-3E protector. Model 3CT-H1-100-C is selected. It realizes overcurrent trip and rapid phase loss protection, cutting down failure rate by 40%.

Случай 2: Crane Control Cabinet Renovation

Replace old split CT with combined 3CT-H1-100-C, saving 50% installation space, simplifying wiring and improving operational reliability.

  1. Выбор & Рекомендации по установке

Three-step Selection Method

  1. Calculate current: Multiply rated motor current by 1.1 overload factor
  2. Select aperture: Choose circular or square bore according to cable size
  3. Confirm terminal type: Terminal block for cabinet wiring, lead wire for field wiring

Меры предосторожности при установке

Keep correct S1(I+) and S2(I-) connection to prevent false operation

Strictly prohibit open secondary circuit during installation and maintenance

Total secondary loop impedance shall not exceed 200mΩ

Insulation resistance shall be no less than 100MΩ before commissioning

График технического обслуживания

ЭлементCycleСтандартный
Визуальный осмотрЕжемесячноNo crack, looseness or overheating mark
Terminal tighteningЕжеквартальныйTorque range 2-3N·m
Испытание изоляцииYearlyResistance ≥100MΩ
Ratio calibrationBienniallyTolerance ≤±1%

Schneider 3CT-H1-100-C is a dedicated three-phase 100/5A combined current transformer for EOCR motor protectors. Featuring Class 1 accuracy, 10VA rated burden and compact design, it is widely applied in low-voltage motor protection and power monitoring. Match current, aperture and terminal type properly, and comply with polarity and open-circuit prohibition rules to ensure stable system operation.