ภาพรวมผลิตภัณฑ์ & Model Breakdown
C125N420FM is a 4‑pole molded case circuit breaker from Schneider Electric’s ComPacT NS1250N series, equipped with a MicroLogic 2.0 control unit.
It is used for overload and short‑circuit protection in low‑voltage power distribution systems, widely applied in industrial plants, commercial buildings, and infrastructure projects.
| ส่วนโมเดล | คำอธิบาย |
| C125N | ComPacT NS1250N series, frame size 1250A, breaking capacity 50kA@415VAC |
| 4 | 4‑pole configuration (4ป) |
| 20 | MicroLogic 2.0 control unit (basic protection functions) |
| FM | Fixed mount, manual operation, front connection |
- Core Technical Specifications
| รายการ | ค่า | หมายเหตุ |
| แบบอย่าง | Schneider Electric C125N420FM | Full description: ComPacT NS1250N 4P 1250A 50kA MIC2.0 |
| Frame current | 1250ก | Maximum rated operational current |
| Poles | 4 เสา (4ป) | 3 เฟส + neutral protection |
| Trip unit | MicroLogic 2.0 | Long‑time (ล), short‑time (ส), ทันที (ฉัน) การป้องกัน |
| จัดอันดับปัจจุบัน (Ir) | 1250ก | Adjustable via trip unit |
| Ultimate breaking capacity (ห้องไอซียู) | 50kA@415VAC | Complies with IEC 60947‑2 |
| การติดตั้ง | ที่ตายตัว, front connection | Suitable for standard switchgear |
| Operation | Manual | With mechanical indication and lockability |
| จัดอันดับแรงดันไฟฟ้าของฉนวน (อุ้ย) | 1000VAC | IEC 60947‑2 |
| Rated operational voltage (อือ) | 400/415VAC (50เฮิรตซ์) | Standard 3‑phase voltage |
| Short‑time withstand current (Icw/1s) | 50ที่ | Ensures system stability during faults |
| Protection degree | IP30 | Protection against solid foreign objects |
| Wiring capacity | สูงสุด. 300mm² copper | For high‑current loads |
- คุณสมบัติ & ข้อดี
- การป้องกันที่ครอบคลุม
MicroLogic 2.0 provides 3‑stage protection (L‑S‑I) with adjustable settings.
Supports fault diagnostics and alarm output for easy maintenance.
- Efficient design
Green “T” design reduces panel wiring time by 40%.
Ergonomic operating handle for improved safety and comfort.
Modular structure supports accessories: ผู้ติดต่อเสริม, ผู้ติดต่อปลุก, การปล่อยแรงดันตก, ฯลฯ.
- Reliable performance
50kA high breaking capacity for fast fault interruption.
Mechanical life: ขึ้นไป 10,000 การดำเนินงาน; electrical life: ขึ้นไป 5,000 การดำเนินงาน.
อุณหภูมิแวดล้อม: −5°C to +40°C (full rating), −25°C to +70°C (derated).
- การติดตั้ง & การใช้งาน
4.1 ข้อกำหนดในการติดตั้ง
Suitable for standard distribution boards with industry‑standard mounting depth.
Front connection for easy wiring and maintenance.
Sufficient heat dissipation space required for stable long‑term operation.
4.2 การใช้งานทั่วไป
Incoming protection for main power distribution boards in industrial plants
Power distribution systems for large commercial complexes
UPS input/output protection in data centers
Critical load protection in infrastructure (hospitals, airports, metros)
Main protection for Motor Control Centers (มช)
- Related Models & Alternatives
5.1 Derived models in the same series
| แบบอย่าง | Difference | แอปพลิเคชัน |
| C125N320FM | 3 เสา (3ป) | 3‑phase loads without neutral protection |
| C125N450FM | MicroLogic 5.0 trip unit | Energy measurement and advanced protection |
| C125N420PM | Draw‑out installation | Easy maintenance without power interruption |
| C125N420RM | Plug‑in installation | Fast replacement for backup equipment |
5.2 Cross‑series alternatives
| Replacement | ชุด | Main difference | Price reference |
| NSX1250N 4P MIC2.0 | ComPacT NSX | New generation, breaking capacity 65kA | Approx. +10% |
| Masterpact MTZ12 | Masterpact MTZ | Air circuit breaker for higher power systems | Approx. +50% |
5.3 Competitive brand equivalents
| ยี่ห้อ | Replacement | Rating |
| ซีเมนส์ | 3WL1212‑3CB36‑4GA4 | 1250A 4P 50kA basic protection |
| เอบีบี | Tmax T6H1250 PR221DS‑LSI 4P | 1250A 4P 50kA LSI protection |
| อีตัน | NZM4‑1250N 4P | 1250A 4P 50kA basic protection |
- Purchasing & Usage Tips
- Authentic procurement: Purchase via authorized Schneider Electric distributors or official channels to ensure quality and service.
- เครื่องประดับ: Optional auxiliary contacts, ผู้ติดต่อปลุก, shunt trip, การปล่อยแรงดันตก, ฯลฯ.
- Parameter setting: MicroLogic 2.0 can be programmed; adjust according to load characteristics.
- Maintenance: Routine inspection every 1–2 years, including mechanism, ขั้ว, and protection functions.
> บันทึก: C125N420FM complies with IEC 60947‑2, กิกะไบต์ 14048.2 and other international & national standards. It is fully compatible with Schneider Prisma E, Blokset and other panel systems.
- Selection & Replacement Guidelines
- Compatibility Rules
Industrial relay sockets follow international standard dimensions and are interchangeable across brands if:
Pin count matches relay pole number
จัดอันดับปัจจุบัน (≥10A) meets load
การติดตั้ง (DIN-rail/screw) matches panel design
- Terminal Type Selection
Conventional screw: PTF08A / PTF11A / PTF14A-suitable for low-vibration environments
Finger protection: PTFZ series-suitable for areas with frequent access
Push-In Plus: PTF-PU series-ideal for mass wiring, high vibration resistance
- โมเดลที่เลิกผลิตแล้ว
PTF08A-E / PTF14A-E are discontinued with limited stock.
Use PTFZ series as the preferred replacement.
> บันทึก: PTF series sockets are rated 10A/250VAC, dielectric strength AC 2000V, operating temp −25 °C to +55 องศาเซลเซียส, suitable for 0.5–2.5 mm² copper wires.
คอนแทคเตอร์,เบรกเกอร์,อินเวอร์เตอร์พลังงานแสงอาทิตย์,มิเตอร์ไฟฟ้า,แบตเตอรี่พลังงานแสงอาทิตย์