Model Code Explanation

Code SegmentDescription
27Prefix for Danfoss industrial refrigeration valve product series
HIdentification code for actuator/drive unit category
9075Specific part number, corresponding to ICAD 600A actuator
ICAD 600AProduct type: Smart electric actuator with rated torque of 600N*m
  1. Main Technical Specifications
ItemDetailed Specification
Basic TypeSmart stepper motor actuator with encoder feedback
Compatible ValvesICM 20, ICM 25, ICM 32 series electric valves
Output TorqueRated: 600N·m, Maximum: 900N·m
Operating Time90 seconds for 90° rotation
Power Supply24VDC (+10% / -15%), Load Current: 1.2A
Power-off Protection RangeMin. 19VDC, Max. 26.4VDC
Control Signal0/4-20mA (Load: 200Ω) or 0/2-10VDC (Load: 10kΩ)
Feedback SignalAnalog output 0/4-20mA (Load ≤ 250Ω)
Ingress ProtectionIP67 (Dust-tight and water resistant)
Ambient Temperature-30℃ ~ +50℃ (-22℉ ~ 122℉)
Housing MaterialAluminum alloy housing, PBT plastic top cover
WeightNet Weight: 1.38kg, Gross Weight: 1.79kg
Cable SpecificationPower cable: 3×0.34mm² (approx. 22AWG), Outer diameter 4.8mm
Control cable: 7×0.25mm² (approx. 24AWG), 8-pin M12 connector
CertificationsCE, UL, CRN
Status IndicationDigital display for valve opening degree and alarm information
  1. Cross-brand Equivalent Comparison
BrandEquivalent ModelMain Differences
SiemensSKB62Danfoss ICAD 600A delivers higher torque (600N路m vs 400N路m) and higher protection class (IP67 vs IP65)
HoneywellML7420ADanfoss adopts built-in encoder for higher positioning accuracy; Honeywell features more competitive price
Johnson ControlsM9106-AGA-2Danfoss supports multiple control signals and is compatible with a wider range of valves; Johnson Controls has stronger communication performance
Schneider ElectricVAM2300Danfoss IP67 protection is suitable for harsh environments; Schneider products feature easier installation and more compact size
Danfoss Replacement Model027X0166 (New Model)027H9075 is discontinued. 027X0166 is an upgraded version with full compatibility and improved performance
  1. Full Model List of ICAD Series
ModelTorque RatingCompatible ValvesSpecial FeaturesStatus
027H9075600N·mICM 20/25/32Standard type with encoderDiscontinued, replaced by 027X0166
027H2005600N·mICM 20/25/32Standard type with encoderIn production
027H9078600N·mICMTS SeriesDesigned for transcritical applicationsIn production
027H20061200N·mICM 40-150High-torque type for large-sized valvesIn production
027H1200600N·mICM 20/25/32Standard cable lengthDiscontinued, replaced by 027X0166
027H1207600N·mICM 20/25/32Extended cable lengthDiscontinued, replaced by 027X0166
027H0435ICAD Series15m cable assemblyAccessory
  1. Common Faults & Troubleshooting
Fault DescriptionAlarm CodePossible CausesTroubleshooting Procedures
No movement, power indicator offIncorrect power wiring, abnormal voltage, faulty actuator1. Check 24VDC power connection and polarity
2. Verify voltage within 20.4~26.4VDC
3. Inspect damaged power cables
4. Replace the actuator for testing
Loss of control signalA3Wrong signal wiring, signal out of range, faulty controller1. Check control signal type setting (Parameter 03)
2. Measure input signal within 0/4-20mA or 0/2-10VDC range
3. Check shielding and earthing of signal cables
4. Replace the controller for testing
Valve jammedA9Foreign matters inside valve, damaged valve stem, insufficient lubrication1. Disconnect the motor and check valve operation manually
2. Remove valve cover and clear debris
3. Inspect bent or damaged valve stem
4. Re-lubricate the valve stem
Motor overheatingA8Excess ambient temperature, poor ventilation, overload1. Confirm ambient temperature does not exceed 50℃
2. Improve ventilation for the actuator
3. Check for extra resistance on the valve
4. Consider replacing with higher torque model
Abnormal feedback signalWrong feedback wiring, defective encoder, incorrect parameter setting1. Check feedback signal wiring
2. Re-calibrate the actuator
3. Inspect encoder connection
4. Replace the encoder module
  1. Application Environments & Industry Cases

Applicable Scenarios

  1. Industrial Refrigeration Systems: Regulate refrigerant flow to precisely control temperature and pressure
  2. Food Processing: Temperature control for cold storage and freezer rooms to keep food fresh
  3. Chemical Industry: Temperature control for low-temperature reactors and precise flow regulation in hazardous areas
  4. Pharmaceutical Industry: Constant temperature control for drug storage and production, compliant with GMP standards
  5. Data Centers: Precision air conditioning system to maintain constant temperature and humidity for server rooms

Non-recommended Scenarios

  1. High-temperature environments: Ambient temperature over 50℃ may trigger motor overheat protection
  2. High-pressure conditions: Operating pressure exceeding the valve’s maximum working pressure of 65bar
  3. Severe vibration environments: May affect encoder accuracy without proper vibration damping measures
  4. Corrosive environments: Strong corrosive atmosphere without special protection will damage housing and internal components

Typical Application Cases

Case 1: Temperature Control System for Large Freezer

Equipment: ICM 32 electric valve + 027H9075 actuator, temperature sensors, PLC controller

Function: Automatically adjust refrigerant flow according to indoor temperature to maintain constant temperature at -25℃

Highlights: ICAD 600A features high control accuracy (0.1%) and IP67 protection, adapting to harsh freezer conditions. Power-off protection ensures system safety. Remote monitoring is realized via 4-20mA communication with PLC.

Case 2: Low-temperature Control for Chemical Reactor

Equipment: ICM 25 electric valve + 027H9075 actuator, pressure sensors, temperature controller

Function: Precisely control coolant flow to keep reactor temperature between -10℃ and +5℃

Highlights: High torque (600N·m) ensures stable valve operation under high pressure. Digital display facilitates on-site commissioning. Multiple alarm functions detect faults timely to guarantee production safety.

  1. Selection Guidelines & Quick Reference Rules

Selection Tips

Match torque with valve size, select protection class based on operating environment, choose proper control signal type, confirm compatibility with valve body, and ensure stable power supply.

Quick Reference Rules

ICAD 600A: 600N·m torque, compatible with ICM 20-32 valves

ICAD 1200A: 1200N·m torque, compatible with ICM 40-150 valves

Part numbers starting with 027H: Danfoss ICAD series actuators

IP67: Suitable for outdoor and humid installation sites

24VDC: Standard power supply, allowable voltage fluctuation: -15% ~ +10%