Mitsubishi NV125-SV 3P 63A Earth Leakage Circuit Breaker

NV = Earth Leakage Circuit Breaker (إلكب); NF = standard MCCB without earth leakage protection; 125 = Frame size AF125A; SV = Standard S model; 3P = 3-pole; 63A = rated operational current In=63A ✅ Core Electrical Specifications Item Parameter Full Model No. NV125‑SV 3P 63A with adjustable earth leakage 100/200/500mA Rated Voltage Ue AC100~440V, ...

  • تفاصيل المنتج

NV = Earth Leakage Circuit Breaker (إلكب); NF = standard MCCB without earth leakage protection; 125 = Frame size AF125A; SV = Standard S model; 3P = 3-pole; 63A = rated operational current In=63A

✅ Core Electrical Specifications

غرضالمعلمة
Full Model No.NV125‑SV 3P 63A with adjustable earth leakage 100/200/500mA
Rated Voltage UeAC100~440V, suitable for 3-phase 3-wire / single-phase 2-wire circuits
التصنيف الحالي في63أ
البولنديين3ص (3 مراحل, neutral not switched)
Short-circuit Breaking Capacity Icu/Ics@AC400V30ال / 30ال
Earth Leakage Sensitivity3-مستوى قابل للتعديل: 100أماه / 200أماه / 500أماه
نوع التسربنوع التيار المتردد, surge resistant, anti-harmonic, suppresses nuisance tripping
وقت التشغيلالأعلى. 0.04ق
البعد الشامل (العرض × الارتفاع × العمق)90mm × 130mm × 90mm
وزنتقريبا. 1.1كجم

📌 Model Code Breakdown

  1. NV: Earth Leakage Circuit Breaker (إلكب, moulded case type with leakage protection)
  2. 125: Frame rating 125A (frame size, this unit rated 63A)
  3. SV: Standard S type (New WS-V generation); CV = Economy type, HV = High breaking capacity type
  4. 3ص: 3-القطب, protects 3 live phases, neutral line does not pass through breaker
  5. 63أ: Continuous rated circuit current 63A

Common suffix: 1.2.500MA = 100/200/500mA adjustable earth leakage

🛠️ Application Scenarios

Industrial control panels, مضخات المياه, المشجعين, small 3-phase power circuits

Integrated protection for equipment: تسرب الأرض, الزائد & حماية ماس كهربائى

Suitable for harmonic-rich environments (VFD, محركات المؤازرة), less prone to nuisance tripping than older generations

تركيب اللوحة, standard screw terminals; الملحقات الاختيارية: Alarm switch AL, Auxiliary switch AX, رحلة تحويلة / Under-voltage coil

⚠️ Selection & ملاحظات الاستبدال

  1. Distinguish NV (ELCB with leakage) vs NF (standard MCCB without leakage). Similar appearance, NOT directly interchangeable.
  2. 3P version does NOT disconnect neutral conductor. Select 4P model NV125-SV 4P if neutral switching is required.
  3. Earth leakage threshold is preset at factory and adjustable via rotary knob on site; 100أماه للحماية الشخصية, 200/500mA for equipment fire protection.
  4. Domestic alternatives reference: CHNT NM1LE-125S/3P 63A, Delixi CDM1LE-125/3P 63A; verify breaking capacity and adjustable leakage range.
  5. Within the same frame size, current rating can be changed directly (63/75/80/100/125أ), mounting dimensions remain unchanged.

🧰 Troubleshooting Quick Reference

Trips immediately upon closing: Priority check for earth leakage or damaged load insulation; try higher leakage threshold.

Overload tripping: Continuous load current >63أ; inspect motor / cable loading.

تعثر ماس كهربائى: Severe short circuit; power off and inspect for phase-to-phase short circuit.

Leakage protection fails to operate: Press red TEST button periodically; verify leakage function monthly.

ميتسوبيشي NV125-SV (WS-V Series) Built-in Accessory List (الفأس / ال / SHT / UVT)

All accessories are clip-on built-in modules, field mountable; compatible for NV125-SV / NF125-SV same frame; accessories installed in the right-side compartment of breaker.

  1. AX Auxiliary Switch

نموذج: الفأس-03SVU

وظيفة: Reports ON/OFF status of main contacts, cannot distinguish manual opening or fault tripping

تصنيف الاتصال: 1a1b (1NO +1NC)

طلب: Send breaker position signal to PLC / مصابيح المؤشر

الأسلاك: Lead wire type; SLT version available with terminal block

  1. AL Alarm Switch

نموذج: ال-03SVU

وظيفة: Activates ONLY when tripped by fault (الزائد, ماس كهربائى, تسرب الأرض); no action during manual opening

تصنيف الاتصال: 1a1b

طلب: Fault trip alarm, SCADA signal upload, مسموع & visual alarm

Combined module: ALAX-03SVU = integrated AX+AL module (provides both position feedback and fault trip signal, الأكثر استخداما على نطاق واسع)

  1. SHT Shunt Trip

Voltage variants:

SHTA240-03SVU: AC100~240V AC shunt trip

SHTA440-03SVU: AC200~440V AC shunt trip

SHTD100-03SVU: DC24V DC shunt trip

لاحقة U: built-in module; L = extended lead; S = special spec

وظيفة: Remote electrical trip via control signal; used for emergency stop, fire linkage circuit cut-off

Important note: Short-time energized type, continuous power supply is prohibited.

  1. UVT Under Voltage Trip

Two types:

UVTN-03SVU Non-synchronous UVT: Instant trip upon voltage drop

UVTS-03SVU Synchronous UVT: Trip at voltage zero-crossing during voltage drop, for large inductive loads to reduce breaking surge

Voltage ratings: AC100/200/240/400V optional

وظيفة: Automatic trip when main circuit voltage drops or power loss; will NOT auto-reclose after voltage recovery, manual closing required on site.

External Accessories for NV125-SV

نموذج التبعياسموصف
TC‑1SVغطاء المحطةInsulation protection for exposed terminals
LC‑1SVPadlock deviceHandle lockout, prevent accidental closing
MI‑05SV3التعشيق الميكانيكيMechanical interlock for 2 قواطع الدائرة (dual power switching)
HLF‑1SVExternal rotary handlePanel mounted operating handle, with door interlock

⚠️ Selection & Installation Restrictions (شديد الأهمية)

  1. One NV125-SV breaker can be fitted with max. one built-in accessory module only. SHT + ALAX cannot be installed together.

الخيار أ: ALAX (موضع + fault signal)

الخيار ب: SHT (remote tripping)

الخيار ج: UVT (under-voltage protection)

  1. Built-in accessories occupy space on the right side of breaker. Do not mount breakers side-by-side with zero clearance when fitted with internal accessories (UVT needs extra space).
  2. Two ordering options:

Breaker pre-fitted with accessories at factory (complete unit order)

Purchase accessory modules separately and assemble on site

  1. ELCB NV125-SV supports SHT/UVT installation for fire linkage and loss-of-voltage protection; accessories are interchangeable with NF125-SV standard MCCB.

Ordering Examples

NV125-SV 3P 63A + ALAX-03SVU (with switch position & fault alarm contacts)

NV125-SV 3P 63A + SHTA240-03SVU (AC220V remote shunt trip)

Full Model List of Mitsubishi NV125-SV (WS-V ELCB)

Frame AF125, Icu=30kA / Ics=30kA @AC400V; Standard AC type leakage 100/200/500mA adjustable; 3P /4P; رحلة حرارية مغناطيسية; dimension W90×H130×D90mm

Naming format: NV125-SV [3ف/4ف] [Rated Current A]

✅ Rated Current Range (في)

16أ, 20أ, 25أ, 32أ, 40أ, 50أ, 63أ, 75أ, 80أ, 100أ, 125أ

✅ Full Model Matrix

3ص (3-مرحلة, neutral not switched)

NV125-SV 3P 16A

NV125-SV 3P 20A

NV125-SV 3P 25A

NV125-SV 3P 32A

NV125-SV 3P 40A

NV125-SV 3P 50A

NV125-SV 3P 63A (target model)

NV125-SV 3P 75A

NV125-SV 3P 80A

NV125-SV 3P 100A

NV125-SV 3P 125A

4ص (3-مرحلة + القطب المحايد, neutral can be disconnected)

NV125-SV 4P 16A

NV125-SV 4P 20A

NV125-SV 4P 25A

NV125-SV 4P 32A

NV125-SV 4P 40A

NV125-SV 4P 50A

NV125-SV 4P 63A

NV125-SV 4P 75A

NV125-SV 4P 80A

NV125-SV 4P 100A

NV125-SV 4P 125A

Derived variants on same WS-V platform

NV125-CV: Economy version, Icu=10kA @AC400V

NV125-HV: قدرة كسر عالية, Icu=50kA @AC400V

NV125-SEV/HEV: Electronic trip ELCB (electronic protection, long/short time delay available)

شرح اللاحقة: 1.2.500MA = 100/200/500mA adjustable leakage (standard for China market); 30mA high-speed leakage variant available for personal protection.

Cross-brand Equivalent Reference (Reference target: NV125-SV 3P 63A, تيار متردد 400 فولت, Icu≥30kA, adjustable leakage 100/200/500mA, الحرارية المغناطيسية)

⚠️ملاحظة هامة: Physical size and accessories are NOT interchangeable; only electrical equivalent. Verify cabinet cutout, wiring and accessory interface for site retrofit. Table based on 63A/3P.

ماركةالنموذج المعادلالمعلمات الرئيسيةملاحظات
Mitsubishi OriginalNV125-SV 3P 63A3ص 63 أ, Icu=30kA@400V, AC leakage 100/200/500mA adjustable, رحلة حرارية مغناطيسيةReference unit, WS-V series
شنايدرEZD125E 3P 63A Vigi (leakage module)3ص 63 أ, Icu=30kA, adjustable residual currentEZD125E + separate Vigi module; split type leakage, not integrated ELCB; بعدا مختلفا
شنايدرNSX100N 3P 63A Vigiوحدة العناية المركزة = 36 كيلو أمبير, adjustable leakageNSX higher performance, سعر أعلى, modular leakage
ايه بي بيT2N160 3P 63A RCDوحدة العناية المركزة = 36 كيلو أمبير, adjustable AC residual currentMCCB body + external RCD module, integrated solution Tmax T2N
سيمنز3VT8106-1AA03-0AA0 + leakage trip module3ص 63 أ, Icu=25kA, optional leakage moduleBreaking capacity slightly lower than Mitsubishi; check short-circuit capacity
مرتبNM1LE-125S/3P 63A3ص 63 أ, Icu=35kA, leakage 100/200/500mA adjustableMain domestic alternative, integrated ELCB, الحرارية المغناطيسية, similar mounting size
لذيذCDM1LE-125/3P 63A3ص 63 أ, Icu=35kA, multi-level adjustable leakageالبديل المحلي, 125AF frame, integrated leakage
كهرباء الناسRMM1LE-125/3P 63A3ص 63 أ, Icu=35kA, adjustable leakageبديل محلي اقتصادي

Key Differences for Replacement Engineering

  1. Leakage construction: Mitsubishi NV125-SV is integrated built-in leakage. Schneider NSX/EZD and ABB Tmax mostly adopt separate external leakage modules, more failure points.
  2. كسر القدرة: NV125-SV Icu=30kA; Icu cannot be downgraded during replacement, risk of breaker failure under bus short-circuit.
  3. توافق الملحقات: Mitsubishi AX/AL/SHT/UVT are right-side clip-on modules; Schneider/ABB accessories are independent modules. Mitsubishi old accessories cannot be reused, new accessories must be purchased for retrofit.
  4. اختيار القطب: 3P only switches 3 live conductors, neutral passes through. Select 4P if neutral protection is required.
  5. Leakage type: Above are all AC type, suitable for standard power frequency loads. For VFD-heavy systems, A/F type leakage is recommended.

Mitsubishi Legacy to WS-V Upgrade

Old NV125-SW / NV125-SVL (old WS series) → NV125-SV (WS-V)

Same outer dimension, mounting hole compatible

Higher short-circuit breaking capacity (old 25kA upgraded to 30kA)

Updated accessory model: old SW accessories incompatible with SV; must use -03SVU series (الفأس-03SVU / ال-03SVU)

Recommended Replacement Priority

  1. Cabinet space & accessory reuse preferred: Original Mitsubishi NV125-SV
  2. Import equivalent upgrade: ABB T2N160 / Schneider NSX100N Vigi
  3. Cost-effective domestic engineering replacement: CHNT NM1LE-125S / Delixi CDM1LE-125

NV125-SV 3P 63A Replacement Retrofit Risk Checklist

Scope: Replace Mitsubishi NV125-SV 3P 63A (إلكب, تيار متردد 400 فولت, Icu=30kA, 100/200/500mA adjustable leakage) with identical model, imported equivalent (ABB/Schneider/Siemens) or domestic alternative (CHNT/Delixi/People). Used for ECN, technical briefing, incoming inspection and pre-commissioning check. ✅=Pass; ❌=Fail; ⚠️=Requires confirmation/rectification

  1. Electrical Parameter Verification (Highest Priority, No Icu Downgrade)
لا.Check Itemمتطلبات / معيار
1التصنيف الحالي فيNew device ≥ 63A and matches circuit design; continuous load ≤0.8×In
2Pole ConsistencyOriginal 3P must use 3P; if changing to 4P for neutral switching, rework wiring & cabinet cutout
3Rated Voltage UeNew device rated voltage ≥ AC400V, compatible with system voltage
4Short-circuit Breaking Icu@AC400VNew Icu ≥ 30kA (must not be lower than original NV125-SV 30kA), risk of breaker damage under bus short-circuit
5ICS (قدرة كسر الخدمة)≥30kA, same as Icu, allows reclose after short-circuit event
6Earth Leakage Protection Typeنوع التيار المتردد (or A/F type); adjustable leakage range 100/200/500mA must be retained
7وقت تشغيل التسرب≤0.04s (عالية السرعة); separately verify for 30mA personal protection version
8Thermal-Magnetic Trip Characteristicالزائد / short-circuit trip curve must match original coordination; electronic trip requires setting verification
9Short-circuit SelectivityRecheck selectivity coordination with upstream and downstream protective devices

⚠️ Red Line Rule①: Do NOT energize any replacement unit with Icu <30ال. Leave panel de-energized rather than downgrade breaking capacity.

  1. التركيب الميكانيكي & Dimension Check
لا.Check Itemمتطلبات / معيار
1Mounting CutoutCompare original NV125-SV (W90×H130×D90mm) with cabinet cutout; re-cut or use adapter plate if dimension mismatch
2نوع التركيبTH35 DIN rail or panel bolt mounting compatible with original bracket
3مساحة الأسلاكIn/out terminal clearance sufficient for cable stripping and crimping (meet minimum cable bending radius)
4Phase ClearanceCreepage & air clearance between phase terminals comply with new device specification
5تبديد الحرارةPanel spacing meets thermal requirement; no tight side-by-side mounting with internal accessories fitted (UVT especially)
6Handle / Door CutoutDoor opening and handle projection match new device; confirm if external rotary handle needs replacement
7Torque for TerminalsTightening torque follows manufacturer manual; conductor cross-section adequate, crimping secure

⚠️ Red Line Rule②: Do not force oversized cutout or suspend breaker without proper support. Use manufacturer drawing or adapter plate.

  1. Accessory Compatibility Check (High Risk, Frequently Missed)
لا.Check Itemمتطلبات / معيار
1Accessory InterfaceOriginal AX-03SVU / ال-03SVU / SHTA/D / UVTN/S cannot be fitted to other brands; purchase new accessories matching new breaker brand
2إنذار / Position SignalRe-select equivalent ALAX accessory for new breaker and rewire secondary circuit
3Shunt Trip SHTReconfigure remote trip, verify AC/DC voltage rating
4Under Voltage Trip UVTReconfigure UVT; verify trip characteristic (synchronous / non-synchronous) against load type
5Mechanical Interlock MIDual power interlock must be matched accessory from new brand; interlocks from different brands are incompatible
6غطاء المحطة / LockoutFit TC/LC protective accessories as per new device spec
7External Leakage Module (Import Split Type)Schneider NSX/EZD, ABB T2N use separate leakage module; confirm module installed and wired correctly

⚠️ Red Line Rule③: Do NOT reuse old Mitsubishi accessories on new breakers. Mismatched assembly causes poor contact, loss of alarm or protection function.

  1. رئيسي & Secondary Wiring Check
لا.Check Itemمتطلبات / معيار
1أسلاك الدائرة الرئيسيةPhase sequence matches busbar, terminals fully tightened
2Neutral Handling3P version neutral passes through unswitched; rewire neutral if replaced with 4P
3Zero-sequence CT / Leakage TransformerIntegrated ELCB has built-in CT, no external CT needed; check CT cable passing direction for split leakage module
4Secondary Control WiresAX/AL contacts to PLC / indicator circuit; verify contact type (1a1b) and voltage rating
5Shunt / UVT Coil WiringSHT is short-time energized, continuous power forbidden; UVT coil voltage matches supply
6Wiring MarkingPhase labels and accessory terminal numbers clear and consistent with drawing
7عزم الدوران الطرفيFollow manufacturer torque specification to avoid overheating / اتصال فضفاض

⚠️ Red Line Rule④: SHT coil is short-time energized, continuous supply burns coil. UVT will not auto-close after voltage recovery; manual closing required in commissioning procedure.

  1. Pre-commissioning Test & قبول
لا.Check Itemمتطلبات / معيار
1اختبار العزلPhase-to-phase / phase-earth insulation resistance meets requirement; disconnect secondary / electronic accessories before test
2اختبار التسرب (TEST Button)Press red TEST button; breaker must trip reliably to validate leakage protection
3Leakage Threshold VerificationTest tripping at 100/200/500mA if site conditions permit
4الزائد / Short-circuit SimulationVerify thermal-magnetic trip if test available; otherwise confirm factory trip characteristic
5Accessory Function TestTest ALAX alarm contact, SHT remote trip, UVT under-voltage trip one by one
6Mechanical OperationManual ON/OFF smooth, no jamming, no missing phase
7عدم التحميل & Load Trial RunClose breaker under no-load first; then energize load, monitor temperature and nuisance tripping
8Earthing ContinuityEquipment and cabinet protective earth secure
9Setting Record FilingDocument new breaker rating, leakage setting and accessory configuration

⚠️ Red Line Rule⑤: Do NOT put into formal operation before passing TEST button leakage verification. ELCB without working leakage protection functions only as ordinary MCCB, no personnel protection.

  1. شروط غير قابلة للتطبيق & العمليات المحظورة
سيناريو / عمليةJudgement
Frequent ON/OFF cycling⚠️ Thermal-magnetic trip not suitable for high cycle rate; use motor protector or add contactor
Heavy corrosion, تراب, التكثيف❌ Standard model not suitable; IP rated enclosure + anti-condensation heater required
VFD & servo heavy harmonic environment⚠️ AC type may nuisance trip; upgrade to A/F type leakage or surge-resistant model
Replace breaker with upstream live❌ Live working prohibited. خارج السلطة, test dead, lockout-tagout (قلب) مطلوب
Reset immediately after leakage trip without investigation❌ Do not repeatedly reclose; troubleshoot insulation/earth fault first
Replace ELCB with standard MCCB (NF)❌ Loss of earth leakage protection, ممنوع منعا باتا
Replace with lower Icu rating❌ Not allowed