مسلسل: Modicon X80 (M340 PLC)
Model explanation: BMXDDI3202KH = BMXDDI3202K + ح; H = Conformal Coating version for harsh environments. Electrical specifications are identical to BMXDDI3202K. Only the PCB is coated with conformal coating for moisture-proof, mould-proof and salt-spray resistance, suitable for ports, النباتات الكيميائية, underground sites, high-humidity and dusty conditions.
✅ Basic Specifications
يكتب: 32-channel isolated digital وحدة الإدخال, حوض (positive logic)
جهد الإدخال: 24VDC, sensor supply range 19~30VDC
Input current per channel: 2.5mA @24V
منطق 1: ≥11V / ≥2mA; منطق 0: ≥5 فولت / ≤0.5mA
مقاومة الإدخال: 9600أوه
وقت الاستجابة: Typical 4ms, maximum 7ms
عزل: Channel-to-channel isolation, مقاومة العزل >10MΩ at 500VDC
الأسلاك: Compatible with 2-wire / 3-wire proximity switches (IEC61131-2 Type3, IEC60947-5-2). Input parallel connection is not allowed
موصل: Single 40-pin FCN interface, single slot, دعم المبادلة الساخنة
استهلاك الطاقة: ≤3.9W; Typical backplane 3.3V consumption 121mA
Enclosure protection: IP20
📌 Matching Cables (40-pin FCN)
- BMXFCWxxx3: Pre-wired loose cables (3m/5m/10m: BMXFCW303 / BMXFCW503 / BMXFCW1003)
- BMXFCCxxx3: Pre-assembled HE10 terminal cables (0.5/1/2/3/5/10م)
🧩 Compatible CPUs
Full Modicon M340 series: BMXP34xx00, BMXP34xx20 (including H versions). General X80 rack, configured via Unity Pro software.
⚖️ Model Comparison
BMXDDI3202K: الإصدار القياسي, no conformal coating, for conventional control cabinets
BMXDDI3202KH: Conformal coated version for harsh environments. Fully interchangeable in program, pinout and cabling.
📎 مرجع الاختيار البديل
Same-platform replacement: No drop-in equivalent. For fewer points, refer to BMXDDI1602K(ح) (16-point Sink DI).
الاستبدال المحلي: Verify sink logic, isolation and filter time, suitable for domestic PLC remote IO modules.
⚠️ Troubleshooting Tips
- لا توجد إشارة الإدخال: Check 24V supply, sensor polarity (حوض, signal connects to 0V), broken pins in prefabricated cables.
- وامض / اثار كاذبة: Check voltage drop and shielding. This module uses fixed hardware filter; filter parameters cannot be modified by software.
- Prefer KH version for humid and corrosive environments; standard K version is prone to PCB corrosion under long-term high humidity.
شنايدر الإدخال الرقمي (من) Module List by Platform
ملحوظة: Suffix H = Conformal coating for harsh environments. X80 platform compatible with M340 / M580; Sink = sinking input, Source = sourcing input; AC = AC input.
- Modicon X80 (BMX series, M340 / M580)
DC Digital Input (BMXDDI)
| نموذج | نقاط | وصف |
| BMXDDI1602K / BMXDDI1602KH | 16 | 24VDC, حوض |
| BMXDDI1603K / BMXDDI1603KH | 16 | 48VDC, حوض |
| BMXDDI1604T | 16 | 125VDC, حوض, درجة حرارة واسعة |
| BMXDDI3202K / BMXDDI3202KH | 32 | 24VDC, حوض (the model you enquired) |
| BMXDDI3203K / BMXDDI3203KH | 32 | 48VDC, حوض |
| BMXDDI3232K / BMXDDI3232KH | 32 | 12/24VDC, Sink/Source configurable |
| BMXDDI6402K / BMXDDI6402KH | 64 | 24VDC, حوض |
AC Digital Input (BMXDAI)
| نموذج | نقاط | وصف |
| BMXDAI0805 | 8 | 220بطالة |
| BMXDAI0814 | 8 | 100~120VAC |
| BMXDAI1602 | 16 | 24VAC/24VDC, مصدر |
| BMXDAI1603 | 16 | 48بطالة |
| BMXDAI1604 | 16 | 100~120VAC |
| BMXDAI1614 | 16 | 220بطالة |
X80 Safety DI (Safety PLC dedicated)
| نموذج | نقاط | وصف |
| BMXSDI1602 | 16 | Safety digital input, 24VDC |
- سلسلة TM3 (Expansion for M221/M241/M251/M262 Compact PLC)
| نموذج | نقاط | وصف |
| TM3DI8 | 8 | 24VDC, محطات المسمار |
| TM3DI8G | 8 | 24VDC, spring clamp terminals |
| TM3DI8A | 8 | 120بطالة |
| TM3DI16 | 16 | 24VDC, محطات المسمار |
| TM3DI16G | 16 | 24VDC, spring clamp terminals |
| TM3DI16K | 16 | 24VDC, HE10 connector |
| TM3DI32K | 32 | 24VDC, HE10 connector |
- Advantys STB Distributed Remote IO
| نموذج | نقاط | وصف |
| STBDDI3725 | 16 | 24VDC Sink |
| STBDDI3420 | 8 | 24VDC Sink |
| STBDDI3610 | 4 | 24VDC Sink |
| STBDAI0200 | 2 | 100~240VAC |
| STBDAI0400 | 4 | 100~240VAC |
- ملاحظات تكميلية
- X80 naming rule: `BMXDDI` = DC DI; `BMXDAI` = AC DI; `K` standard, `KH` conformal coated.
- K and KH variants of the same model are fully interchangeable in pinout, programming and backplane interface, only differing in PCB protection.
- Mixed I/O modules (دي + دو) such as BMXDDM16022 are excluded from this table.
Application Scenarios of Schneider Digital Input (من) وحدات (X80/STB/TM3, إلخ.)
Core function of DI modules: Collect binary switch signals, transfer ON/OFF status from external dry contacts, أجهزة الاستشعار, أزرار الضغط, limit switches and auxiliary contacts of contactors to PLC. It only detects on/off status and does not process analog signals. The following is sorted by industry and signal type, applicable to BMXDDI3202KH and other X80 modules.
- General Signal Acquisition (Used across all industries)
- Pushbuttons, مفاتيح التحديد, أزرار التوقف في حالات الطوارئ
Local cabinet operation, remote control boxes, E-stop signals (general E-stop; safety E-stop should use dedicated safety DI module BMXSDI1602).
- Limit switches, مفاتيح السفر, مفاتيح القرب, أجهزة الاستشعار الكهروضوئية
Equipment position detection: cylinder confirmation, door switches, baffle limit for material level, كشف وجود الكائن.
BMXDDI3202KH is 24VDC Sink, compatible with mainstream NPN proximity switches.
- Auxiliary contacts of contactors / المرحلات, circuit breaker status feedback
Motor running feedback, VFD ready feedback, circuit breaker open/close status, thermal relay fault signals.
- Dry contact signals
Fire alarm systems, التحكم في الوصول, damper/valve position feedback in HVAC, float level switches.
- التدفئة والتهوية وتكييف الهواء
جري / fault feedback of fans and water pumps
مفاتيح الضغط التفاضلي, frost protection switches, air damper / water valve end-position feedback
تصفية إنذار الضغط التفاضلي, high/low float level switches
Feedback of smoke exhaust dampers and fire dampers
Conformal coated KH versions (BMXDDIxxxxKH) are preferred for humid and dusty machine rooms.
- معالجة المياه, إمدادات المياه & الصرف الصحي, Wastewater Plants
Level switches (مستوى عال, مستوى منخفض, overflow)
Pump run, عيب, hand-auto status
Limit signals for bar screens and sludge scrapers
Pulse signals from flow meters (high-speed pulses require dedicated high-speed counter modules; standard DI is not suitable for high-frequency pulses)
Valve open / closed position feedback
KH coated modules are widely used in corrosive, high-humidity wastewater sites.
- التعبئة والتغليف, Assembly Lines & خطوط الإنتاج الآلي
Photoelectric detection for material presence / missing material
Cylinder and clamp confirmation signals
Conveyor belt jam and deviation switches
Barcode detection, silo level switches
Safety gate and guard door status signals
BMXDDI6402K (64-point DI) is commonly used for high-point-count lines to save slots.
- Crane Systems, نقل & Warehouse Logistics
Crane travel limits, upper/lower hard limits, buffer switches
Pallet in-position, bay detection
Roller conveyor deviation and E-stop loop feedback
Roller shutter and guard door status
- Power Distribution Rooms & Energy Monitoring
Circuit breaker and disconnector open/close position feedback for high-voltage cabinets
Cabinet door interlock, earthing switch status
Transformer thermostat switches, cooling fan feedback
DC panel fault alarm dry contacts
BMXDAI AC DI modules are often used for 220VAC cabinet signals.
- زيت & الغاز, الصناعة الكيميائية, الموانئ (البيئات القاسية)
Valve position feedback, pump status, dry contact output of combustible gas detectors
Limit switches and door interlocks for trestle and quay equipment
Salt spray, high humidity and condensation → select KH conformal coated versions (BMXDDI3202KH etc.). Standard K versions are vulnerable to corrosion.
- أتمتة البناء, الحماية من الحرائق & محطات الضخ
Dry contact alarms from fire host, sprinkler pressure switches
Elevator interlock signals, smoke exhaust fan status
Rainwater pumps, sump tank level monitoring
✅ Quick Selection Guide by Scenario
Normal indoor control cabinet, بيئة جافة: BMXDDIxxxK
كيميائي / ميناء / رطوبة عالية & رذاذ الملح: BMXDDIxxxKH (طلاء مطابق)
220VAC contact signals: BMXDAI AC DI
دوائر السلامة, بوابات السلامة, safety E-stop: BMXSDI safety DI
Small machines, low I/O count: TM3DI series
Distributed remote IO with scattered field points: STB Advantys remote DI
⚠️ Scope Limitations (What DI modules cannot do)
- Cannot directly measure 4-20mA or temperature (AI analog modules required)
- Standard DI is not suitable for high-frequency pulse counting (high-speed counter module required)
- Safety functions shall not be implemented via ordinary DI; dedicated safety DI modules are mandatory.
المقاولين,قاطع الدائرة,الاستشعار,التشفير,بلك,محول