توقف (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement. Model Code Explanation PM750: High-end multifunction power monitor of PM700 series MG: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging Core Functions ...

  • تفاصيل المنتج

توقف (discontinued in China on 2014-12-31). No new original units available from manufacturer. Only second-hand or surplus stock parts on market. METSEPM53 series is the preferred replacement.

شرح كود النموذج

PM750: High-end multifunction power monitor of PM700 series

ملغ: Modbus RS485 communication version, equipped with digital I/O, harmonic measurement and min/max value logging

الوظائف الأساسية

  1. True RMS full electrical measurement: 3-مرحلة / single-phase voltage, حاضِر, قوة نشطة/رد فعل/ظاهرية, عامل الطاقة, تكرار; phase-wise & total active energy kWh, reactive energy kvarh, يطلب / peak demand, الحد الأقصى & minimum value recording.
  2. Power quality: Total Harmonic Distortion (ثد), harmonic analysis up to 15th order, sampling rate 32 samples per cycle.
  3. I/O Interface: 2 المدخلات الرقمية (من), 1 static digital output (يفعل). DO configurable for pulse output (energy pulse), alarm output or remote control. DI for status acquisition or demand synchronization trigger.
  4. وظيفة التنبيه: 15 groups of user-defined threshold alarms (الجهد الزائد, انخفاض الجهد, التيار الزائد, power limit violation, إلخ.), local indication + alarm report via communication.
  5. تواصل: RS485, Modbus RTU protocol, up to 19200bps, compatible with PLC, SCADA and energy management systems.
  6. عرض: Backlit LCD, 6-line display, panel cutout mounting.

المواصفات الكهربائية الرئيسية

غرضتحديد
Measuring VoltageLine-to-line: 10~480V AC; Phase-to-neutral:10~277V AC, 45~65Hz
الإدخال الحاليCT secondary 0.005~6A (5A/1A CT both supported)
مزود الطاقةتكييف:115~415 فولت; العاصمة:125~250V; Power consumption ≤5VA
دقةCurrent ±0.4%; Voltage ±0.3%; Power ±0.5%; Active energy Class 0.5S (IEC62053-22)
من12~36VDC, الاسمي 24VDC, 2.5kV isolation
يفعلStatic transistor output, supports pulse / alarm mode

تطبيق نموذجي

LV/MV switchgear, factory power distribution room, توزيع الطاقة في البناء, computer room incoming cabinet. Used for power monitoring, energy consumption statistics, power quality monitoring and status acquisition; commonly used as spare parts for legacy project retrofits.

OEM Replacement Models (مفتاح)

PM750MG → METSEPM5330 (RS485 Modbus); For Ethernet version: METSEPM5340 (مودبوس تكب)

PM53 series is upgraded replacement for PM750, full & enhanced function coverage, identical panel cutout size for direct mounting. Modbus register addresses are incompatible, reconfiguration required. High-end alternative: PM8240/PM8243.

قائمة التحقق الشائعة لاستكشاف الأخطاء وإصلاحها

  1. No current / reversed current reading: CT S1/S2 reversed; CT secondary shorting link not removed; CT ratio not configured in meter.
  2. Modbus communication failure: Missing termination resistor, A/B wire reversal, mismatched address/baud rate; unstable meter supply.
  3. DO no action: Verify DO mode configuration (pulse/alarm) and polarity of external circuit.
  4. Abnormal harmonic reading: الأسلاك فضفاضة, insufficient PT/CT accuracy, heavy distortion on load side.

ملاحظات تكميلية

Cutout dimension: 92×92mm, panel flush mounting

المعايير: اللجنة الانتخابية المستقلة 62053, ANSI C12.20; compatible with 3P3L /3P4L / أنظمة أحادية الطور

Second-hand spare note: LCD backlight aging, damaged RS485 transceiver chip, parameter loss due to internal battery depletion.

  1. PM750MG Modbus RTU Register Summary (Holding Registers, 4xxxx, 16قليل; Energy values as 32bit, يحتل 2 consecutive registers)

Protocol Notes: مودبوس ار تي يو, register starts at 40001 (شنايدر معيار). Some software uses 0-based addressing (40000), pay attention to offset. For float /32bit unsigned integer, high word first. Energy registers come with multiplier register; readings must be multiplied by multiplier factor.

Firmware version: V3.050 (common firmware for PM700 series)

Modbus Address(4xxxx)Data Typeاسموصف
40001UINT16V1 Phase Voltageالجهد المرحلة, multiplier register 40013
40002UINT16V2 Phase Voltage
40003UINT16V3 Phase Voltage
40004UINT16V12 Line Voltage
40005UINT16V23 Line Voltage
40006UINT16V31 Line Voltage
40007UINT16I1 Phase A Currentحاضِر, multiplier register 40014
40008UINT16I2 Phase B Current
40009UINT16I3 Phase C Current
40010UINT16Frequency Hz
40011UINT16Total Active Power kWPower multiplier 40015
40012UINT16Total Reactive Power kvar
40013UINT16Voltage Multiplier (10^n)على سبيل المثال. value=2 → ×100
40014UINT16Current Multiplier (10^n)
40015UINT16Power Multiplier (10^n)
40016UINT16Total Power FactorRange 0~1000, divide by 1000
4,002,040,021UINT32Total Active Energy kWh40020=High word,40021=Low word; multiplier 40108
4,002,240,023UINT32Total Reactive Energy kvarh
4,002,440,025UINT32Total Apparent Energy kVAh
40030UINT16Phase A THDCurrent total harmonic distortion
40031UINT16Phase B THD
40032UINT16Phase C THD
40040UINT16DI StatusBit0=DI1,Bit1=DI2
40041UINT16DO StatusBit0=DO1
40045UINT16Alarm Status WordAlarm mask
40108UINT16Energy Multiplier (10^n)Energy reading ×10^n, مهم!

Energy Calculation Example: 40020=0012, 40021=ABCD; 40108=2 → 0x0012ABCD ×10² = 1254860 ×100 = 125486000 Wh = 125486 كيلووات ساعة

Harmonics: 1~15th harmonic magnitudes, registers start at 40050, per-phase harmonic amplitude.

Communication Basic Parameters (PM750MG)

بروتوكول: مودبوس ار تي يو

معدل الباود: 2400/9600/19200

التكافؤ: لا أحد / Odd / Even; Stop bit:1

Slave address: 1~247

RS485 Terminals: أ, ب; 120Ω termination resistor at bus end

  1. PM750MG vs METSEPM5330 Function & Wiring Migration Comparison Table
غرضPM750MG (Old Meter)METSEPM5330 (Replacement Meter)Migration Notes
Cutout Size92×92mm92×92mmIdentical panel cutout, direct mounting
مزود الطاقةAC115~415V / DC125~250VAC100~415V / DC110~250VPower circuit can be reused directly
مدخلات الجهد10~480V line voltage10~480V line voltagePT secondary wiring unchanged; support 3P3L/3P4L
الإدخال الحاليCT secondary 0.005~6ACT secondary 0.005~6ACT S1/S2 wiring unchanged, CT ratio must be reconfigured on new meter
من2من (24VDC)2من (24VDC)External DI wiring can be kept
يفعل1-channel static transistor output2-channel relay DO⚠️Major difference! PM750MG uses transistor DO; PM5330 is dry contact relay. Original DO pulse/alarm circuit needs redesign, higher load capacity.
القياس التوافقيUp to 15th harmonicUp to 31st harmonicPM5330 enhanced power quality capability
Alarm Groups15 المجموعات35 المجموعاتAlarm logic can be migrated, register addresses for alarms are fully different
تواصلRS485 Modbus RTURS485 Modbus RTUPhysical A/B wiring unchanged. Register mapping is fully incompatible! PLC/SCADA program must be rewritten, old register addresses cannot be reused.
Energy TariffSingle tariff4 التعريفاتSupport time-of-use metering
دقةActive energy Class 0.5SActive energy Class 0.5SSame accuracy class
تسجيل البياناتالأعلى & Min valuesالأعلى & دقيقة + Event logPM5330 supports event logging

Retrofit Risk Checklist (Mandatory for Site Replacement)

  1. DO circuit modification: PM750MG transistor output cannot drive heavy load. PM5330 uses relay. If original DO sends pulse to acquisition module, verify dry-contact pulse compatibility with acquisition device.
  2. Host software program reconstruction: Register address, data arrangement and multiplier logic are all different. All tags for PLC / KingView / ForceControl / SCADA must be reconfigured; old program cannot be copied directly.
  3. Parameter re-entry: نسبة الأشعة المقطعية, نسبة PT, system type (3P3L/3P4L), عتبة التنبيه, Modbus address and baud rate all require manual setup. Parameters from PM750MG cannot be imported into PM5330.
  4. Real-time clock: PM750MG internal battery loses parameters on power loss; PM5330 retains parameters after power loss, only clock resets.

ثالثا. Terminal Wiring Comparison

PM750MG Terminal Layout

  1. L1 L2 L3 N Voltage Input
  2. CT1 CT2 CT3 Current Input
  3. محطات الطاقة
  4. DI1 DI2 COM
  5. DO+ DO(الترانزستور)
  6. RS485 A B

METSEPM5330 Terminal Layout

  1. L1 L2 L3 N Voltage
  2. CT1 CT2 CT3 Current
  3. قوة
  4. DI1 DI2 COM
  5. DO1, DO2 (تتابع, independent dry contact)
  6. RS485 A B

الجهد االكهربى, حاضِر, DI and RS485 cables may remain untouched; DO wiring must be rewired.

  1. On-site Replacement Procedure
  2. Power off and confirm safety; record original PM750MG parameters (CT/PT ratio, system type, alarm settings, معلمات الاتصال).
  3. Remove old meter, keep voltage, ط م, DI and RS485 cables.
  4. Install METSEPM5330, connect voltage, ط م, DI and RS485; rework DO wiring separately.
  5. Power up, configure CT/PT ratio, system wiring type, Modbus address, baud rate and alarm thresholds.
  6. Verify real-time measurements: الجهد االكهربى, حاضِر, قوة; confirm CT polarity is correct.
  7. Modify PLC / SCADA Modbus program, debug communication.
  8. Compare accumulated energy readings, run continuous test to verify metering accuracy.

Schneider PowerLogic PM700 Series Full Model List (All discontinued)

Series basics: 92×92mm panel mounting, True RMS measurement, ثد, min/max logging. Suffix Definition

ملغ: With RS485 Modbus RTU communication

كاليفورنيا: North American ANSI version (rarely used in China; Chinese projects prefer models without CA suffix)

ص: 2-channel solid-state pulse output

قائمة النماذج الكاملة

  1. PM700 Base model, لا يوجد اتصال, لا يوجد نبض الإخراج
  2. PM700CA North American base version
  3. PM700MG Base measurement + RS485 Modbus
  4. PM700MGCA NA version + مودبوس
  5. PM700P Base model + 2 solid-state pulse outputs, لا يوجد اتصال
  6. PM700PCA NA version with pulse output
  7. PM700PMG Base + إخراج النبض + RS485 Modbus
  8. PM700PMGCA NA version, pulse + مودبوس
  9. PM710 Base measurement + RS485 Modbus, no DI/DO
  10. PM710CA NA PM710
  11. PM710MG Mainstream domestic PM710 (مودبوس)
  12. PM710MGCA NA PM710MG
  13. PM750 Top tier, RS485 Modbus, 2DI+1DO, alarm function
  14. PM750MG Most common domestic model (target model, Modbus version)
  15. PM750CA NA PM750
  16. PM750MGCA NA PM750MG

Comparison of 4 النماذج الأساسية (Common for China Projects)

نموذجالتكوين الأساسيطلب
PM700Basic electrical +THD/min-max, No comms, no pulseLocal display only, no SCADA connection
PM700PBasic electrical +THD, 2 pulse outputs, No commsEnergy pulse acquisition, no network
PM710MGBasic electrical +THD, RS485 Modbus, No DI/DORemote power acquisition, no status points needed
PM750MGFull electrical +THD+15th harmonic, RS485 Modbus, 2DI+1DO+threshold alarmsمراقبة الطاقة, remote status acquisition, إخراج التنبيه (largest installed base in China)

التوقف & Replacement Summary

APAC discontinuation date: 2015-04-30; Americas:2015-08-30. No new original production, only surplus / قطع غيار مستعملة.

PM700 / PM700P / PM710 → METSEPM51xx (PM5100 series)

PM750 / PM750MG → METSEPM53xx (METSEPM5330 RS485; METSEPM5340 Ethernet TCP)

ملاحظات تكميلية

  1. This series does NOT have PM720/PM730/PM740. Many documents are misleading. PM700 series only has four base platforms: PM700, PM700P, PM710, PM750.
  2. CA suffix = North American ANSI variant, differs in wiring logic & تصنيف الجهد. Avoid CA-suffix spares for China retrofits.