Harmony RM22-L Level Control Relay (Conductive Electrode Liquid Level Monitoring)
تفسير النموذج: RM22 series modular control relay; LG = liquid level single detection; 11 = 1 الاتصال التحول (ج/س); MR = power supply 24~240V AC/DC; MT version for 380~415V AC power supply
✅ الوظائف الأساسية
Designed for conductive liquids (ماء, مياه الصرف الصحي, إلخ.) for automatic liquid level control. Two operating modes available:
- Fill Mode (إمدادات المياه) : When liquid level falls below Min electrode → relay energizes, starts fill pump; when liquid level reaches Max electrode → relay de-energizes, stops pump.
- Drain Mode (Sump Pumping) : When liquid level reaches Max electrode → relay energizes, starts drain pump; when liquid level drops below Min electrode → relay de-energizes, stops pump.
It adopts resistance probe detection, judging liquid level based on liquid conductivity, not float switch. Adjustable detection sensitivity.
📋 Electrical Specifications
جهد الإمداد: 24~ 240 فولت تيار متردد/تيار مستمر (عالمي للتيار المتردد & العاصمة), 50/60هرتز; operating range 20.4~264V
استهلاك الطاقة: AC 5VA / DC 1.5W
اتصال الإخراج: 1 changeover contact 1C/O (11-12 مغلقة عادة, 11-14 مفتوحة عادة), ايه سي-15/دي سي-13, 8أ@250 فولت تيار متردد
Power-on delay: 0.6ق
Probe circuit: الأعلى. 12V AC at electrodes, electrode current ≤1mA; maximum probe cable length 1000m
حساسية: St standard sensitivity 5kΩ~100kΩ, continuously adjustable via potentiometer
تصاعد: السكك الحديدية الدين, width 22.5mm
حماية: Sealing transparent protective cover to prevent on-site misadjustment; built-in diagnostic test button + status LED indicator
📌تعريف المحطة الطرفية
| صالة | وصف |
| A1,A2 | Relay working power supply |
| دقيقة | Low liquid level electrode |
| الأعلى | High liquid level electrode |
| ج | Common reference electrode (reference pole) |
| 11 | Contact common terminal |
| 12 | Normally closed NC |
| 14 | Normally open NO |
Wiring note: 3 electrodes inside tank: C common pole, Min minimum liquid level, Max maximum liquid level. Only applicable to conductive liquids; not for insulating oil and other non-conductive media.
🛠️ التطبيقات النموذجية
إمدادات المياه & drainage tanks, sewage pools, أبراج التبريد, water purification equipment, automatic pump start/stop, DIN rail mounting inside control cabinet.
⚠️ Model Differentiation & مرجع الاستبدال
- RM22LG11MR: 24~240V AC/DC, single changeover contact
- RM22LG11MT: 380~415V AC power supply version
- RM22LA32MR: Dual-contact version, two-channel output
استبدال التراث: RM35LM series (توقف, replace with RM22LG for new projects)
مبدأ التشغيل شنايدر RM22LG11MR
المبدأ الأساسي: AC resistive conductive liquid level detection (نوع الموصلية)
A low-voltage AC sensing signal is applied between electrodes. The device measures liquid resistance between two electrodes and compares it with the sensitivity threshold set on the front panel. The internal circuit drives output relay action.
إشارة تيار متردد منخفضة الجهد على جانب المسبار لتجنب التآكل الإلكتروليتي للأقطاب الكهربائية الناتج عن التيار المستمر.
- دائرة الكشف
يقوم التتابع بإخراج إشارة استشعار التيار المتردد ذات الجهد المنخفض (حوالي 12 فولت تيار متردد, الحالي <1mA) بين ج (القطب المشترك), دقيقة (مستوى منخفض), الأعلى (مستوى عال).
يشكل القطب المغمور بالسائل → السائل الموصل مسارًا بين C والقطب, مقاومة منخفضة;
القطب المكشوف فوق السائل ← الدائرة مفتوحة, مقاومة عالية للغاية;
مقياس الجهد يحدد عتبة الحساسية (5كيلو أوم ~ 100 كيلو أوم) : المقاومة المقاسة < العتبة ← الكشف عن السائل; المقاومة > العتبة ← لم يتم اكتشاف أي سائل.
👉 صالح فقط للسوائل الموصلة. لا ينطبق على النفط, مياه فائقة النقاء (الموصلية منخفضة جدا) والسوائل العازلة.
- وضعين للتشغيل (3-نقطة التحكم في مستوى السائل مع منطق ذاكرة التباطؤ)
1) Fill Mode (مكياج مائي)
مستوى السائل تحت الحد الأدنى من القطب: C-Min circuit open → internal relay energizes, 11-14 لا يغلق, starts fill pump.
Liquid level rises, submerges Min but not reaching Max: C-Min conductive, internal memory holds status, pump keeps running.
Liquid level reaches Max electrode: C-Max conductive → relay resets, 11-14 يفتح, توقف المضخة.
If liquid level drops but remains above Min, pump will not start. Two-point start/stop prevents frequent pump cycling.
2) Drain Mode (الصرف الصحي)
Liquid level reaches Max electrode: C-Max conductive → relay energizes, 11-14 لا يغلق, starts drain pump.
Liquid level falls, leaves Max but still higher than Min: memory holds status, pump keeps draining.
مستوى السائل تحت الحد الأدنى من القطب: C-Min open → relay resets, توقف المضخة.
- Single Level Mode (خياري, 2 الأقطاب الكهربائية)
Use only C+Max or C+Min for single-point alarm / يتحكم. Small delay can be enabled to suppress false triggering caused by liquid wave and foam.
- Internal Signal & الإخراج
- A1/A2 supplies power to relay (24~240V AC/DC wide range), power circuit is electrically isolated from probe measurement circuit;
- دائرة القياس تكتسب باستمرار المقاومة بين الأقطاب الكهربائية;
- تحكم الوحدة المنطقية على الحالة بناءً على إشارات الوضع والقطب الكهربائي, محركات الأقراص 1 الاتصال التحول (1ج/س, 11 شائع,12 نورث كارولاينا,14 لا);
- يشير مؤشر LED باللوحة الأمامية إلى حالة الإخراج; زر اختبار مدمج يحاكي حالة تشغيل الحلقة.
- ميزات التصميم الرئيسية
- استشعار التيار المتردد: لا يتم تطبيق جهد التيار المستمر على الأقطاب الكهربائية, يمنع التحليل الكهربائي, جيل الفقاعة, تآكل القطب والتحجيم المتسارع.
- عتبة مقاومة قابلة للتعديل: التكيف مع مياه الصرف الصحي / مياه نظيفة بموصلية مختلفة عبر مقبض الحساسية.
- منطق الذاكرة التباطؤ: يتطلب الاعتراف عالية & نقاط مستوى منخفض, يتجنب تبديل التتابع المتكرر الناجم عن تقلبات السائل الطفيفة.
- الحد الأقصى لطول كابل القطب الكهربائي يصل إلى 1000 متر. احذر من تداخل السعة الشاردة للكابلات الطويلة; يميل التشغيل الخاطئ إلى الحدوث في ظل إعدادات الحساسية العالية.
- مراسلات الخطأ على أساس المبدأ
Electrode scaling → equivalent liquid resistance rises above threshold → liquid present but device reports no liquid;
Conductive foam layer → electrode not touching actual liquid level but circuit conducts → false liquid level detection;
Poor contact of C electrode → measurement reference lost, all liquid level detection invalid.
Troubleshooting for Schneider RM22LG11MR
Pre-diagnosis method: T test button on front panel. Press T when powered on to toggle relay output status, to distinguish unit failure or external electrode / wiring fault.
عيب 1: No response after power on, power LED off
أعراض: A1/A2 supply voltage normal, no LED light, relay no action
الأسباب
- أسلاك A1/A2 فضفاضة, poor terminal contact; wrong polarity for DC supply
- Input voltage out of 24~240V AC/DC operating range
- Internal power circuit damaged (lightning surge, الجهد الزائد العابر, ماس كهربائى)
الحلول
- خارج السلطة, قياس الجهد عند A1/A2, تشديد المحطات; تحقق من القطبية لإمدادات التيار المستمر
- التحقق من العرض ضمن النطاق المقنن; تحقق من المنبع MCB والصمامات
- استبدل الوحدة إذا كان مؤشر LED لا يزال مطفأً بجهد الإمداد الصحيح
عيب 2: لا يعمل التتابع عند غمر القطب الكهربائي (تم الكشف عن السائل ولكن لا توجد استجابة)
أعراض: يغطي السائل القطب الأقصى/الدقيق, حالة التتابع دون تغيير, المضخة لا تبدأ/تتوقف
الأسباب
- القطب مغطى بالتحجيم / الحمأة, المقاومة المكافئة للسائل تتجاوز عتبة الحساسية
- ضعف الاتصال بالقطب المشترك C (الأكثر شيوعا), فقدان مرجع القياس
- كابل القطب الكهربائي مكسور, الأسلاك فضفاضة في محطات Min / Max / C
- تم ضبط الحساسية على مستوى منخفض جدًا (عتبة المقاومة صغيرة جدًا بحيث لا يمكن إجراء مياه الصرف الصحي)
- الموصلية المتوسطة منخفضة للغاية (مياه فائقة النقاء, السائل العازل, غير مناسب لهذا النموذج)
الحلول
- إزالة الأقطاب الكهربائية, ينظف / مقياس البولندية والحمأة; الصيانة الدورية للقطب الكهربائي
- التحقق من الأولوية القطب C: ensure C is immersed in liquid and wiring secure
- خارج السلطة, test cable continuity, tighten Min/Max/C terminals
- Increase sensitivity appropriately (raise resistance threshold, adjustable from 5kΩ~100kΩ)
- For low-conductivity water / زيت, use float level switch instead
عيب 3: Relay false action when liquid level below electrode (detects liquid with no actual liquid), pump starts unexpectedly
أعراض: Liquid level below electrodes, relay reports liquid present, pump starts mistakenly
الأسباب
- Conductive foam / scum on liquid surface closes electrode circuit (common in sewage tank)
- Long electrode cable, stray capacitance causes false trigger (>300m is high risk)
- Sensitivity set too high, minor leakage triggers detection
- Electrode cable routed in parallel with power cable, التداخل الكهرومغناطيسي
- Terminal condensation / leakage between electrodes
الحلول
- Raise electrode mounting position to avoid foam; install foam baffle
- تقليل الحساسية; استخدم كابلًا محميًا لسلك الإشارة الطويل, درع مؤرض من طرف واحد; منفصلة عن كابلات الكهرباء
- تنظيف التكثيف الطرفي, تحسين مقاومة الرطوبة في الخزانة
عيب 4: توقف متكرر للمضخة, تتابع الثرثرة / التذبذب
أعراض: مستوى السائل مستقر ضمن النطاق, التتابع ينشط وينشط بشكل متكرر, دورات المضخة بسرعة
الأسباب
- اضطراب شديد في السوائل, سطح السائل يكتسح الأقطاب الكهربائية بشكل متكرر; التوصيل المتقطع بواسطة الرغوة
- الأقطاب الكهربائية القذرة, مقاومة القطب غير المستقرة
- وضع التشغيل الخاطئ, تم تعطيل منطق التباطؤ (سلك كهربائي واحد فقط)
الحلول
- تمديد الأقطاب الكهربائية, تثبيت الأكمام المضادة للتصاعد; قم بتركيب الأقطاب الكهربائية في المنطقة الثابتة بالخزان
- أقطاب كهربائية نظيفة, ضبط الحساسية وتجنب الإعداد الحرج
- الأسلاك القياسية ذات 3 أقطاب (ج+الحد الأدنى+الحد الأقصى), تمكين منطق ذاكرة التباطؤ المدمج, تجنب التحكم في نقطة واحدة
عيب 5: تتابع LED عادي ولكن اتصال الإخراج لا يوجد إجراء, فشل المضخة في البدء
أعراض: مؤشر المستوى LED صحيح, ولكن المقاولين المصب / المضخة لا تعمل
الأسباب
- الأسلاك الخاطئة لجهات الاتصال الإخراج (11/12/14 المحطات غير متصلة)
- يتجاوز حمل الاتصال التصنيف 8A, تآكل الاتصال / لحام / دائرة مفتوحة
- لا توجد قوة على دائرة التحكم في المصب
الحلول
- قم بإيقاف تشغيل الطاقة والتحقق من أسلاك الاتصال: 11 شائع, 12 نورث كارولاينا,14 لا
- اضغط على زر اختبار T وقياس الاستمرارية بين 11-14; الدائرة المفتوحة = الاتصال تالف, استبدال التتابع
- تحقق من مصدر طاقة التحكم للمضخة / قواطع
عيب 6: الاتصال باللحام, تعمل المضخة بشكل مستمر ولا يمكن أن تتوقف
أعراض: يصل مستوى السائل إلى وضع التوقف, يبقى الإخراج مغلقا, لا يمكن إيقاف تشغيل المضخة
الأسباب
- الزائد على المدى الطويل, القوس الكهربائي يسبب اللحام التلامسي
- لا يوجد امتصاص للتدفق المفاجئ لملف المقاولين, عودة EMF تلحق الضرر بجهات الاتصال
الحلول
- استبدل RM22LG11MR على الفور في حالة لحام جهات الاتصال
- أضف جهاز التحكم عن بعد أو الصمام الثنائي الحر للتحميل الاستقرائي (لفائف المقاولين) لحماية الاتصالات الداخلية 8A
يوصى بتسلسل استكشاف الأخطاء وإصلاحها في الموقع
- تشغيل الطاقة, تحقق من مؤشر الطاقة; LED مطفأ → فحص مصدر الطاقة A1 / A2
- اضغط على زر اختبار T ولاحظ تبديل الإخراج
تبديل الإخراج بواسطة T: الوحدة صحية, خطأ في القطب, cable or liquid medium
No response by T: Relay unit damaged, استبدال مباشرة
- Verify C common electrode fully immersed and wiring tightened
- Clean electrodes and adjust sensitivity knob
- Check if signal cable runs together with power cable; use shielded cable for long distance
- Confirm mode selection: Fill (إمدادات المياه) / Drain (الصرف)
Preventive Maintenance
- Sewage application: Clean electrodes every 3~6 months to prevent scaling
- Keep electrode cable length within 500m where possible; reduce sensitivity and adopt shielded cable if longer
- Ensure cabinet moisture-proof to avoid terminal condensation leakage
- Install surge absorption device for inductive load (قواطع) to protect 8A contacts
Schneider RM22 Harmony Modular Monitoring Relay Full Series List
Series common features: تركيب السكك الحديدية DIN, width 22.5mm (RM22TG20:17.5مم); equipped with T test button, status LED, sealable transparent cover; contact rating: 8أ@250 فولت تيار متردد; suffix MR=24~240V AC/DC universal supply; MT=380~415V AC supply
- RM22L Conductivity Level Monitoring Relay (series of your model)
Conductive electrode liquid level detection for high/low level control of water tank and sewage sump
|RM22LG11MR|1ج/س (1 التحول)|24~240V AC/DC|النموذج القياسي, your reference unit, sensitivity 5k~100kΩ|
|RM22LG11MT|1ج/س|380~415 فولت تيار متردد|High voltage supply level relay|
|RM22LA32MR|2ج/س (2 التحول)|24~240V AC/DC|Dual-channel output, 3 sensitivity levels: LS/St/HS|
|RM22LA32MT|2ج/س|380~415 فولت تيار متردد|Dual-contact high voltage supply level relay|
- RM22T 3-phase Power Monitoring Relay (تسلسل المرحلة / خسارة المرحلة / 3-عدم توازن المرحلة / الجهد الزائد & انخفاض الجهد)
Monitor 3-phase power supply for motor, مضخة مياه, air compressor protection
|RM22TA31|2ج/س|تسلسل المرحلة, خسارة المرحلة, 3-عدم توازن المرحلة|200~240VAC|
|RM22TA33|2ج/س|تسلسل المرحلة, خسارة المرحلة, 3-عدم توازن المرحلة|380~480VAC|
|RM22TU21|2ج/س|تسلسل المرحلة, خسارة المرحلة, انخفاض الجهد|200~240VAC|
|RM22TU23|2ج/س|تسلسل المرحلة, خسارة المرحلة, انخفاض الجهد|380~480VAC|
|RM22TR31|2ج/س|تسلسل المرحلة, خسارة المرحلة, عدم التوازن, overvoltage/undervoltage with delay|200~240VAC|
|RM22TR33|2ج/س|تسلسل المرحلة, خسارة المرحلة, عدم التوازن, overvoltage/undervoltage with delay|380~480VAC|
|RM22TG20|2ج/س|تسلسل المرحلة, خسارة المرحلة (نسخة مدمجة,17.5مم)|183~528VAC|
- RM22U Single-phase / DC Voltage Monitoring Relay (الجهد الزائد & Undervoltage monitoring)
AC/DC single-phase voltage monitoring for DC panel and single-phase power protection
|RM22UA32MR|2ج/س|1~100V AC/DC|24~240V AC/DC|
|RM22UA33MR|2ج/س|15~500V AC/DC|24~240V AC/DC|
|RM22UA33MT|2ج/س|15~500V AC/DC|380~415 فولت تيار متردد|
|RM22UB34MR|2ج/س|Wide range single phase voltage|24~240V AC/DC|
- RM22J Current Monitoring Relay (AC current monitoring, الزائد / تيار خفي)
Work with current transformer CT for motor load current monitoring
|RM22JA21MR|1ج/س|0.1~5A AC|24~240V AC/DC|
|RM22JA32MR|2ج/س|0.1~5A AC|24~240V AC/DC|
- قاعدة ترميز النموذج (RM22XXYYZZ)
- RM22: Series code Harmony modular monitoring relay
- العشرين: Function group
إل جي: مستوى السائل, single sensitivity
ال: مستوى السائل, multi-range sensitivity
TA/TU/TR/TG: 3-phase power monitoring
UA/UB: Single-phase voltage monitoring
و: Current monitoring
- ص: Contact quantity
11: 1 الاتصال التحول (1ج/س)
32: 2 اتصالات التحول (2ج/س)
- ZZ: Power supply code
السيد: 24~240V AC/DC universal (most widely used in engineering)
طن متري: 380~415V AC 3-phase high voltage supply
- Legacy Model Replacement (RM35 → RM22)
RM35LM old level relay → RM22LG / RM22LA
RM35TA/TU old 3-phase protection relay → RM22TA/TR/TU
RM35 series discontinued, select RM22 for new projects
- جدول الاختيار السريع
| طلب | النموذج الموصى به |
| Tank / sump conductivity level, single pump start-stop | RM22LG11MR (النموذج المرجعي الخاص بك) |
| Liquid level control requiring two independent alarm/output channels | RM22LA32MR |
| 3-محرك المرحلة: خسارة المرحلة + تسلسل المرحلة + حماية عدم التوازن | RM22TA33 |
| 3-phase power: خسارة المرحلة + تسلسل المرحلة + زيادة & undervoltage full protection | RM22TR33 |
| مراقبة حمل المحرك الحالي (الاستشعار بالأشعة المقطعية) | RM22JA21MR |
| لوحة العاصمة, انتهت مرحلة واحدة & إنذار انخفاض الجهد | RM22UA33MR |